Watchdog errors could be due to:
l
Transient voltage
l
Incorrectly wired or malfunctioning sensor
l
Poor ground connection on the power supply
l
Numerous
PortSet()
instructions back-to-back with no delay
l
High-speed serial data on multiple ports with very large data packets or bursts of data
The error "Results for Last Program Compiled: Warning: Watchdog Timer IpTask Triggered" can
result from:
l
The IP communications on the datalogger got stuck, and the datalogger had to reboot
itself to recover. Or communications failures may cause the datalogger to reopen the IP
connections more than usual. Check your datalogger operating system version; recent
operating system versions have improved stability of IP communications.
If
any
of
these
are
not
the
apparent
cause,
contact
Campbell
Scientific
for
assistance
(see
Causes
that
may
require
assistance
include:
l
Memory corruption
l
Operating System problem
l
Hardware problem
l
IP communications problem
9.1.3 Results for last program compiled
Messages generated by the datalogger at program upload and as the program runs are reported
here. Warnings indicate that an expected feature may not work, but the program will still
operate. Errors indicate that the program cannot run. For more information, see
9.1.4 Skipped scans
Skipped scans are caused when a program takes longer to process than the scan rate allows. If
any scan skips repeatedly, the datalogger program may need to be optimized or reduced. For
more information, see:
How to Prevent Skipped Scans and a Sunburn
.
9.1.5 Skipped records
Skipped records usually occur because a scan is skipped. They indicate that a record was not
stored to the data table when it should have been.
9. Tips and troubleshooting
114
Summary of Contents for CR1000X
Page 1: ...Revision 02 21 2019 Copyright 2000 2019 Campbell Scientific ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 16: ...Appendix A Glossary 176 Appendix B Index 214 Table of Contents viii ...
Page 192: ......