Appendix A. Configuring Modem with a Terminal Emulator
A-3
A.3 Programming the Redwing for Use with a
Datalogger
The Redwing needs a few settings changed in it to power-up ready to work
with the datalogger.
Step AT Commands
Response
Description
6
ATS0=1+CICB=0
OK
Sets auto answer in data mode.
7
AT+IFC=0,0
OK
Disables local flow control.
Sets the Redwings RS232 baud
rate and saves settings.
Use the following to determine
baud rate:
CR1000
CR5000
115200
CR23X
38400
8
AT+IPR=[baud rate]; &W
Example:
AT+IPR=9600; &W
OK
CR10(X)
CR510
CR200
CR7
9600
In the above strings, all “0” = zero.
Remove the power from the modem and power it up again. It should be ready
to use at the baud rate set in Step 8. Test the communications before deploying
the modem.