Model 108 Temperature Probe
5
7.1 Wiring to Datalogger
TABLE 7-1. Wire Color, Function, and Datalogger Connection
Wire
Color
Wire Function
Datalogger Connection
Terminal
Black
Voltage-excitation input
U
configured for voltage
excitation
1
, EX
,
VX
(
voltage excitation)
Red
Analog-voltage output
U
configured for single-ended
analog input
1
, SE
(single-ended,
analog-voltage input)
Purple
Bridge-resistor lead
⏚
(analog ground)
Clear
EMF shield
⏚
(analog ground)
1
U
channels are automatically configured by the measurement instruction.
7.2 Datalogger Programming
Short Cut
is the best source for up-to-date datalogger programming code.
If your data acquisition requirements are simple, you can probably create and
maintain a datalogger program exclusively with
Short Cut
. If your data
acquisition needs are more complex, the files that
Short Cut
creates are a great
source for programming code to start a new program or add to an existing
custom program.
Short Cut
cannot edit programs after they are imported and edited
in
CRBasic Editor.
A
Short Cut
tutorial is available in Section
. If you wish to
import
Short Cut
code into
CRBasic Editor
to create or add to a customized
program, follow the procedure in Appendix
(p. A-1)
. Programming basics are provided in the following
section. A complete program example can be found in Appendix
(p. B-1)
If the 108 probe is to be used with long cable lengths or in electrically noisy
environments, consider employing the measurement programming techniques
Electrically Noisy Environments
, and Section
(p. 9)
.
Details of 108 probe measurement and linearization of the thermistor output
Measurement and Output Linearization
(p. 8)
NOTE