R.M. Young Wind Sentry
TABLE 7-4. Parameters for Wind Direction
CR10(X)
CR510
CR200(X)
CR7
21X
CR23X
CR800
CR1000
CR5000
CR3000
Measurement
Range
2500 mV,
slow
5000 mV,
slow/60 Hz
2500 mV,
60 Hz,
reverse
excitation
5000 mV,
60 Hz,
reverse
excitation
Excitation
Voltage
2500 mV
5000 mV
2500 mV
5000 mV
Multiplier 0.1408 0.0704 352 352
Offset 0 0 0 0
7.4.3 Wind Vector Processing Instruction
The
Wind Vector
output instruction is used to process and store mean wind
speed, unit vector mean wind direction, and standard deviation of the wind
direction (optional) from the measured wind speed and direction values.
7.4.4 Example Programs
The following programs measure the 03002 every 5 seconds, and store mean
wind speed, unit vector mean direction, and standard deviation of the direction
every 60 minutes. Wiring for the examples is given in TABLE 7-5.
TABLE 7-5. Wiring for Example Programs
using the 03002-L
Color Description
CR1000 CR10X
Red
Wind Spd. Signal
P1
P1
Black
Wind Spd. Reference
G
Clear
Wind Spd. Shield
G
Green
Wind Dir. Signal
SE 1
SE 1
Blue
Wind Dir. Excitation
VX 1 or
EX 1
E1
White
Wind Dir. Reference
AG
14