Operation and maintenance instructions
Series PRE proportional pressure regulator
External sensor version
5000056022
Ver. 00
27
pressure is regulated to the minimum value of the pression nominal range, while at a signal
of 7V the output pressure is regulated to the maximum value of the pression nominal range.
This function does not always improve resolution, which may in any event be limited by the
intrinsic characteristics of the PRE series electronic regulator and its internal components.
•
Minimum/Maximum external sensor output: è possibile impostare il range del segnale
elettrico del sensore esterno. I valori Minimum external sensor output e Maximum external
sensor output corrispondono rispettivamente al valore minimo e massimo del range del
segnale elettrico del sensore esterno. Il software di supervisione “UVIX” verifica la coerenza
dei due valori imponendo che il punto di minimo non sia maggiore del punto di massimo.
Questi parametri permettono di adattare il range del segnale elettrico del sensore esterno
rispetto al range nominale dell’ingresso del PRE.
Se, ad esempio, l’uscita del sensore esterno è nel range 0,5
-4,5V, impostare Minimum external
sensor output pari a 0,5V, Maximum external sensor output pari a 4,5V e il parametro External
Sensor interface nel menù User Interface sul valore “voltage” (range nominale 0
-10V).
Se invece, ad esempio, l’uscita del sensore esterno è nel range 4
-20mA, impostare Minimum
external sensor output pari a 4mA, Maximum external sensor output pari a 20mA e il
parametro External Sensor interface nel menù User Interface sul valore “current” (range
nominale 4-20mA).
12.2.3.
Digital output setup
This group contains the parameters to set the digital output. For more details regarding this
function, refer to the paragraph "Digital output".
•
Digital output mode: sets the digital output operating mode. The available options are: Error,
Switch or Window.
•
Digital output level: sets the operating logic of the digital output based on the type of
connection.
•
Lower limit switch control: sets the lower threshold for the pressure switch mode.
•
Upper limit switch control: sets the upper threshold for the s pressure witch mode.
•
Lower limit window control: sets the lower differential for the pressure window mode.
•
Upperr limit window control: sets the higher differential for the pressure window mode.
12.2.4.
Pressure sensor setup
The parameters of the pressure sensor are contained in this group: these parameters cannot be
modified by the user.
•
Pressure sensor minimum pressure: displays the minimum value in the external pressure
sensor range. Value expressed in the unit of measure setted in the UVIX
menù “Unit of
measure preference”
.