16

8. Electrical connections

The  isolating  amplifier  SIRAX  TV  808  is  plugged  onto  a 
backplane BP 902. A 96 pin connector (model C, DIN 41 612) 
establishes the electrical connections between the isolating 
amplifier and the backplane. The pin connections can be 
seen from Fig. 5. 

Please refer to our backplane instructions for the back-
plane wiring.

Make sure that the cables are not live when 
making the connections!

The  230  V  power  supply  is  potentially 
dangerous!

In the case of “Intrinsically safe” explosion-
proof versions [EEx ia] IIC, the supplementary 
information given on the Type Examination 
Certificate and also local regulations appli-
cable to electrical installations in explosion 
hazard areas must be taken into account.

Also note that, …
… the data required to carry out the prescribed 
measurement must correspond to those marked 
on the nameplate of SIRAX TV 808  (

 measu-

ring  input, 

  measuring  output, 

  power 

supply!).
…  the  total  loop  resistance  connected  to  the 
output (receiver plus leads) 

does not 

exceed the 

maximum permissible value R

ext.

 max., see 

Meas-

uring output” 

in Section “5. Technical data” for 

the maximum values of R

ext.

!

… the measurement input and output cables should 
be twisted pairs and run as far as possible away 
from heavy current cables!
In all other respects, observe all local regulations 
when  selecting  the  type  of  electrical  cable  and 
installing them!

Legend to Figs. 3 and 4:

  = With set of code, 

= Without set of code

Annual mean
relative humidity: 

 75%

Altitude: 

2000 m max.

Indoor use statement!

7.  Mechanical coding of the plug-in module

Where there is a danger of inserting a module in the 
wrong slot, the possibility has to be excluded as 
prescribed in EN 50 020, Section 6.3.2. 

To this end, 

the units must be supplied already equipped with 
coding inserts as shown in Figures 3 and 4.

Order Type

808-611

808-612

Power supply
24…60 V DC/AC

A

B

C

D

E

F

G

H

I

K

L

M

Back

A

B

C

D

E

F

G

H

I

K

L

M

Back

Power supply
85…230 V DC/AC

Fig. 3. Coding of the plug-in module SIRAX TV 808 in 

standard 

(non-Ex) version.

Order Type

808-613

808-614

Power supply
24…60 V DC/AC

A

B

C

D

E

F

G

H

I

K

L

M

Back

A

B

C

D

E

F

G

H

I

K

L

M

Back

Power supply
85…110 V DC /
85…230 V AC

Fig. 4. Coding of the plug-in module SIRAX TV 808 in 

[EEx ia] IIC 

version.

Summary of Contents for SIRAX TV 808-61

Page 1: ...éparateur SIRAX TV 808 61 Operating Instructions Isolating amplifier SIRAX TV 808 61 TV 808 61 Bd f e 125 171 01 06 05 Camille Bauer AG Aargauerstrasse 7 CH 5610 Wohlen Switzerland Telefon 41 56 618 21 11 Telefax 41 56 618 35 35 e mail info camillebauer com http www camillebauer com ...

Page 2: ...2 ...

Page 3: ...ebsanlei tung mit folgenden Symbolen markiert Les conseils de sécurité qui doivent impé rativement être observés sont marqués des symboles ci contre dans le présent mode d emploi The following symbols in the Operating In structions indicate safety precautions which must be strictly observed Geräte dürfen nur fachgerecht entsorgt werden Les appareils ne peuvent être éliminés que de façon appropriée...

Page 4: ...1 Kanal 2 Channel 2 Eingang Input Ausgang Output Anlage Mess Stelle Plant Measuring point G O SS EN M ET R A W A TT C A M I LL E B A U ER Anlage Mess Stelle Messeingang Fühlertyp Temperatur Messbereich Messausgang Anfahr Festwert währ 5 s Einstellzeit Bruchsignalisierung Netzbrumm Unterdrückung Grenzwertfunktion Konfiguration Configuration SIRAX V 644 Plant Measuring point Measuring input Sensor t...

Page 5: ...dauernd 2 fach Messausgang Gleichstrom Standardbereiche 0 20 mA 4 20 mA 20 mA Grenzwerte 0 1 bis 0 20 mA 0 2 1 bis 4 20 mA 1 0 1 bis 20 0 20 mA Bürdenspannung 12 V Rext max kΩ 12 V IAN mA IAN Ausgangsstromendwert Gleichspannung Standardbereiche 0 10 V 2 10 V 10 V Grenzwerte 0 1 bis 0 10 V 0 2 1 bis 2 10 V 1 0 1 bis 10 0 10 V Bürde 2 kΩ Strombegrenzung bei Rext max Ca 1 1 IAN bei Stromausgang Spann...

Page 6: ... Messausgang Abschnitt 6 Technische Daten dass die Messeingangs und Messausgangs leitungen als verdrillte Kabel und möglichst räumlichgetrenntvonStarkstromleitungenverlegt werden Im übrigen landesübliche Vorschriften z B für Deutschland DIN VDE 0100 Bestimmungen für das Errichten von Starkstromanlagen mit Nenn spannungen bis 1000 V bei der Installation und Auswahl des Materials der elektrischen Le...

Page 7: ... oder Stromsignal Je nach Lage U oder I der Steckbrücken ST 4 und ST 3 lässt sich der Ausgang für Spannung oder Stromausgang einstellen Bild 7 Ausgang Steckbrücken ST 4 ST 3 Strom mA Spannung V U I U I U I U I 10 2 Eingangs und Ausgangs Standardbereiche Bei Trennverstärkern mit Standardbereichen lassen sich die Eingangs und oder Ausgangsbereiche mit 2 von 6 Steck brücken B1 bis B6 einstellen Die G...

Page 8: ...ken 2 Schnellverschluss bei vertikaler Einbaulage des Geräte trägers in vertikale Position bringen bei horizontaler Einbaulage in horizontale Lage stellen 3 Schnellverschluss mit Schraubendreher eindrücken bis dieser hörbar einrastet SIRAX 3 GO SSE N ME TRA W A TT C AM I LLE BAU ER SIRAX 1 2 Bild 8 Steck Modul aufstecken 12 Inbetriebnahme Messeingang und Hilfsenergie einschalten Nach dem Ein schal...

Page 9: ...anal 2 Channel 2 Eingang Input Ausgang Output Anlage Mess Stelle Plant Measuring point G O SS EN M ET R A W A TT C A M I LL E B A U ER Anlage Mess Stelle Messeingang Fühlertyp Temperatur Messbereich Messausgang Anfahr Festwert währ 5 s Einstellzeit Bruchsignalisierung Netzbrumm Unterdrückung Grenzwertfunktion Konfiguration Configuration SIRAX V 644 Plant Measuring point Measuring input Sensor type...

Page 10: ...e 2 fois Tension continue en permanence 2 fois Sortie de mesure Courant continu Etendues standards 0 20 mA 4 20 mA 20 mA Valeurs limites 0 1 à 0 20 mA 0 2 1 à 4 20 mA 1 0 1 à 20 0 20 mA Tension de charge 12 V Rext max kΩ 12 V IAN mA IAN Val fin du courant de sortie Tension continue Etendues standards 0 10 V 2 10 V 10 V Valeurs limites 0 1 à 0 10 V 0 2 1 à 2 10 V 1 0 1 à 10 0 10 V Charge 2 kΩ Limita...

Page 11: ...tance des lignes n excède pas la valeur maximum Rext mentionnée sous Sortie de mesure du chapitre 6 Caractéris tiques techniques que les lignes d entrée de mesure et de sortie designaldemesuresoientréaliséespardescâbles torsadés et disposées à une certaine distance des lignes courant fort Au reste respecter les prescriptions nationales pour l installation et le choix du matériel des conducteurs él...

Page 12: ... En fonction du positionnement U ou I des cavaliers ST 4 etST3 ilestpossibledemodifierlesignalde sortietension en signal de sortie courant ou vice versa Fig 7 Sortie Cavaliers ST 4 ST 3 Courant mA Tension V U I U I U I U I 10 2 Entrées et sorties normalisées En fonction des 2 dès 6 cavaliers B1 à B6 en place il est possible de modifier pour les valeurs normalisées le signal d entrée et le signal de ...

Page 13: ...ition verticale pour montageverticaldel appareil danslapositionhorizontale pour montage horizontal 3 Enfoncer à l aide d un tournevis la fixation rapide jusqu à ce que l on entende l encliquetage SIRAX 3 GO SSE N ME TRA W A TT C AM I LLE BAU ER SIRAX 1 2 Fig 8 Enficher le module embrochable 12 Mise en service Enclencher le circuit d entrée de mesure et l alimentation auxiliaire Après l enclenchement...

Page 14: ...nel 1 Kanal 2 Channel 2 Eingang Input Ausgang Output Anlage Mess Stelle Plant Measuring point G O SS EN M ET R A W A TT C A M I LL E B A U ER Anlage Mess Stelle Messeingang Fühlertyp Temperatur Messbereich Messausgang Anfahr Festwert währ 5 s Einstellzeit Bruchsignalisierung Netzbrumm Unterdrückung Grenzwertfunktion Konfiguration Configuration SIRAX V 644 Plant Measuring point Measuring input Sens...

Page 15: ...sly 2 fold Measuring output DC current Standard ranges 0 20 mA 4 20 mA 20 mA Limit values 0 1 to 0 20 mA 0 2 1 to 4 20 mA 1 0 1 to 20 0 20 mA Burden voltage 12 V Rext max kΩ 12 V IAN mA IAN Output circuit full scale value DC voltage Standard ranges 0 10 V 2 10 V 10 V Limit values 0 1 to 0 10 V 0 2 1 to 2 10 V 1 0 1 to 10 0 10 V Burden 2 kΩ Current limiter at Rext max Approx 1 1 IAN for current out...

Page 16: ...mum permissible value Rext max see Meas uring output in Section 5 Technical data for the maximum values of Rext themeasurementinputandoutputcablesshould be twisted pairs and run as far as possible away from heavy current cables In all other respects observe all local regulations when selecting the type of electrical cable and installing them Legend to Figs 3 and 4 With set of code Without set of c...

Page 17: ... Type of output signal voltage or current The output can be configured for a voltage or current signal by inserting the plug in jumpers ST 4 or ST 3 in position U or I Fig 7 Output Jumpers ST 4 ST 3 Current mA Voltage V U I U I U I U I 10 2 Standard input and output ranges Two of six plug in jumpers B1 to B6 are used for selecting the standard ranges of the isolating amplifiers Providing the potenti...

Page 18: ...equickrelease screws on the module to a vertical position respectively if it is mounted horizontally turn the screws to a horizontal position 3 Pressthequickreleasescrewsinwardswiththescrewdriver until there is an audible click SIRAX 3 GO SSE N ME TRA W A TT C AM I LLE BAU ER SIRAX 1 2 Fig 8 Plug the module into the base 12 Commissioning Switch on the measuring input and the power supply The green...

Page 19: ...ten folgender Europäischer Richtlinien überein nachgewiesen durch die Einhaltung folgender Normen The above mentioned product has been manufactured according to the regulations of the following European directives proven through compliance with the following standards Nr No Richtlinie Directive 89 336 EWG 89 336 EEC Elektromagnetische Verträglichkeit EMV Richtlinie Electromagnetic compatibility EM...

Page 20: ...of the following European directives proven through compliance with the following standards Nr No Richtlinie Directive 89 336 EWG 89 336 EEC Elektromagnetische Verträglichkeit EMV Richtlinie Electromagnetic compatibility EMC directive EMV EMC Fachgrundnorm Generic Standard Messverfahren Measurement methods Störaussendung Emission EN 50 081 2 1993 EN 55011 1992 Störfestigkeit Immunity EN 50 082 2 1...

Reviews: