PM 1000288 000 00
Device handbook SIRAX BT5100
6/32
5. Electrical connections
Ensure under all circumstances that the leads are free of potential when connecting them!
Please observe that the data on the type plate must be adhered to!
The national provisions have to be observed in the installation and material selection of electric lines!
5.1 General safety notes
Symbol
Meaning
Device may only be disposed of in a professional manner!
Double insulation, device of protection class 2
CAT III
Measurement category CAT III for voltage inputs and power supply
CE conformity mark. The device fulfi lls the requirements of the applicable EC directives. See
declaration of conformity.
Caution! General hazard point. Read the operating instructions.
Attention: Danger to life!
Please note
5.2 Cross sections and tightening torques
Terminals 1 … 8
Single wire: ≤ 4,0mm
2
or multiwire with end splices: 2 x 2,5mm
2
Torque: 0.5 … 0.6Nm rsp. 4.42 … 5.31 lbf in
Terminal A, B, G
Single wire: ≤ 1,5mm
2
or multiwire with end splices: 2 x 0,5mm
2
Torque: max. 0.5 Nm rsp. 4.42 lbf in
All voltage measurement inputs must originate at circuit breakers or fuses rated by 1 Amps. This
does not apply to the neutral connector. You have to provide a method for manually removing
power from the device, such as a clearly labeled circuit breaker or a fused disconnect switch.
When using
voltage transformers
you have to ensure that their secondary connections never will be
short-circuited.
The connection of the inputs depends on the confi gured system (connection type).
5.4 Power supply
A marked and easily accessible current limiting switch has to be arranged in the vicinity of the
device for turning off the power supply. Fusing should be 10 Amps or less and must be rated for
the available voltage and fault current.
5.3 Inputs