6.4.6 Resetting the communication settings of an AM1000 without display
If the communication settings of the Standard interface are no longer known, on devices with a display
these settings may be locally displayed and modified. For devices without display this is not possible. The
communication settings can then be reset to default settings via the reset button.
Press the sunk-in reset button (located on the
left of the operating LED) for at least 3s. For
that the nameplate needs to be penetrated.
During the reset the operating LED flashes red.
6.5 Communication tests
Via the service menu on the device website you may check if the selected network structure is valid. The
device must be able to reach the DNS server via gateway. The DNS server then allows resolving the URL
of the NTP server to an IP address. The Standard Ethernet interface serves as interface for the
communication tests.
•
Ping: Connection test to any network device (initial: gateway address)
•
DNS: Test, if the name resolution via DNS works (initial: URL of NTP server)
•
NTP: Test, if the selected NTP-Server is in fact a time server (stratum x)
•
SFTP: Test, if access to SFTP server works. A test file will be copied to the base directory of the
server.
6.6 IEC 61850 interface
The features of the IEC61850 interface are described in a separate document:
>> IEC61850 interface SINEAX AMx000/DM5000, LINAX PQx000, CENTRAX CUx000
This document is available via, e.g.:
>>
https://www.camillebauer.com/am3000-en