6.4.2 Connection of the standard interface
The standard RJ45 connector serves for direct connecting an Ethernet cable.
Interface: RJ45 connector, Ethernet 100BaseTX
Mode:
10/100 MBit/s, full / half duplex, Auto-negotiation
Protocols: http, https, Modbus/TCP, NTP
Functionality of the LED's
AM1000
AM2000 / AM3000
•
LED right: S
witched on as soon as a network connection exists (link)
•
LED left:
Flashes during communication with the device (activity)
6.4.3 Connection of the IEC61850 interface
The RJ45 sockets X1 and X2 serve for direct connecting Ethernet cables. Both ports are equivalent and
internally connected via a switch.
Interface: RJ45 sockets, Ethernet 100BaseTX
Mode:
10/100 MBit/s, full / half duplex, Auto-negotiation
Protocols: IEC61850, NTP
Functionality of the LED's
AM1000
AM2000 / AM3000
•
LED green: On if a network connection (link) exists, flashes during communication
6.4.4 Connection of the PROFINET interface
The RJ45 sockets X1 and X2 serve for direct connecting Ethernet cables. Both ports are equivalent and
internally connected via a switch.
Note: The interface may only be connected to a local Profinet network, which is designed as SELV circuit
according to IEC 60950-1.
Interface: RJ45 sockets, Ethernet 100BaseTX
Mode:
10/100 MBit/s, full / half duplex, auto-negotiation
Protocols: PROFINET, LLDP, SNMP