7. Electrical connections

For connecting the external wires, the transmitter has a plug 
connector M12 x 1 / 4 poles or a gland. During the version 
with a gland the connection via a spring-type terminal block 
made in accordance with diagram of connections. 

4-20 mA

12…30 V DC

+        –       

R

ext

Connection allocation plug

1

2

3

4

Pin

Plug

1

+

2

3

not 

connected

4

• 

Do not electricly modify the device nor 
carry out any wiring work when energi-
sed.

• 

Do not plug in or unplug electric connection 
when energised.

8. Electric commissioning

• 

Provide a separate power supply for the device in case 
of consumer loads with high interference levels.

• 

Install the entire plant in an EMC-compatible manner. 
Installation environment and wiring can affect the EMC 
of the device.

9. Maintenance

The device is free of maintenance.

10. Programming instruction

10.1 Control panel

The transmitter is pro-
grammable via switch 
and push-button.

These will be visible 
after opening the top 
cover.

Pressure-time for
programming:
short = 0.1s
long = 1s

10.2 Programming “Linear curve”

1.  Turn the switch to the linear mode (DIP2 „off”)

2.  Choose rotary sense:  DIP1 „off”; Clockwise
 

DIP1 „on”; Counterclockwise

3.  Programming mode „on”

3 x short „0%” (0%; 0%; 0% 

 LED lights permanently)

4.  Bring transmitter to the starting position

Programming 0% 
1 x short „0%” (0% 

 LED flashes shortly 1 x)

5.  Bring transmitter to the end position

Programming 100% 
1 x short „100%” (100% 

 LED flashes shortly 1 x)

6.  Programming mode „off”

3 x short „0%” ( 

 LED lights are no longer)

The zeropoint of a factory programmed linear curve can be 
shifted, if point 1-4 and 6 of the programming instruction 
programming “linear curve” are followed.

If there is in programming mode for about 15 minutes no 
button pressed, the programming mode will be closed au-
tomatically without saving the changed parameters.

10.3 Programming “V-characteristic”

I

out

vmax1

vmax2

20 mA

  4 mA

vmin1

vmin2

Angular 
position

Rotation clockwise

It is important to note that the points vmax1, vmin1, vmin2, 
vmax2 has to turn clockwise!

1.  Turn the switch to the linear mode (DIP2 „on”)

2.  Programming mode „on”

3 x short „0%” (0%; 0%; 0% 

→ 

LED lights permanent-

ly)

3.  Bring transmitter in position „vmax1” of the V-cha-

racteristic
Programming vmax1
1 x short „100%” (100% 

 LED flashes shortly 1 x)

4.  Bring transmitter in position „vmin1” 

Programming vmin1
1 x short „0%” (0% 

 LED flashes shortly 1 x)

5.  Bring transmitter in position „vmin2” of the V-characte-

ristic
Programming vmin2
1 x long „0%” (0% 

 LED flashes shortly 2 x)

6.  Bring transmitter in position „vmax2”

Programming vmax2
1 x long „100%” (100% 

 LED flashes shortly 2 x)

7.  Programming mode „off”

3 x short „0%” (

 LED lights are no longer)

The zeropoint of a factory programmed V-characteristic can 
be shifted, if point 1-3 and 7 of the programming instruction 
programming “V-characteristic” are followed.

If there is in programming mode for about 15 minutes no 
button pressed, the programming mode will be closed au-
tomatically without saving the changed parameters!

10.4 Restoring the factory default setting (Reset)

8.  Programming mode „on”

3 x short „0%” (0%; 0%; 0% 

 LED lights permanently)

9.  Push button „0%” for at least 5 s

(0% 

 LED flashes shortly 5 x; transmitter restart)

11. Declaration of conformity

See page 15.

Summary of Contents for KINAX HW730

Page 1: ...loi Convertisseurs de mesure angulaire d arbres creux programmables KINAX HW730 Operating Instructions Programmable hollow shaft transmitter for angular position KINAX HW730 Camille Bauer AG Aargauers...

Page 2: ...sen werden Das Ger t nicht ausserhalb der Grenz werte betreiben welche in der Anleitung angegeben sind 1 4 Reparaturen und nderungen Reparaturen und nderungen sind aus schliesslich durch den Herstelle...

Page 3: ...35 Wiederholgenauigkeit 0 1 Winkelschritt Hysterese linear Messbereich 180 0 025 Messbereich 180 0 05 Messbereich 360 V Kennlinie 0 025 Temperaturein uss Ausgangsstrom 40 85 C 0 2 10K 5 5 Einbauangab...

Page 4: ...5 10 10 30 6 2 50 5 2 54 2 12 min 20 M6 30 h9 R47 5 5 8 8 3 0 Anbau Beispiel Mit Distanzbolzen kann dieses Mass vergr ssert werden max Anzugsdrehmoment 3 4 Nm 5 8 Abmessungen 59 M4 42 5 28 H7 65 5 14...

Page 5: ...rogrammierung V Kurve Iout vmax1 vmax2 20 mA 4 mA vmin1 vmin2 Dreh winkel Drehung im Uhrzeigersinn Es ist zu beachten dass die Punkte vmax1 vmin1 vmin2 vmax2 im Uhrzeigersinn anzufahren sind 1 Schalte...

Page 6: ...s indiqu es dans le mode d emploi 1 4 R parations et modifications Lesr parationsetlesmodi cationsdoivent uniquement treeffectu esparlefabricant En cas d intervention inappropri e sur l appareil la ga...

Page 7: ...5 ms 5 4 Donn es de pr cision Pr cision de base limite d erreur admissible 0 35 R p tabilit 0 1 tape angle hyst r sis courbe lin aire plage de mesure 180 0 025 plage de mesure 180 0 05 plage de mesure...

Page 8: ...les lectriques le convertisseur de mesure dispose d un connecteur M12 x 1 4 broches ou d unpresse toupe Lorsdel utilisationd unpresse toupe le raccordement est effectu via une borne ches ressort comme...

Page 9: ...pteur 11 Certificat de conformit Voir page 15 8 Mise en service lectrique En cas de seuil de perturbation sonore important pr voir une alimentation s par e pour l appareil Installer convenablement l e...

Page 10: ...perating instructions 1 4 Repair work and modifications Repair work and modi cations shall exclu sively be carried out by the manufacturer In case of any tampering with the device the guaranty claim s...

Page 11: ...oducibility 0 1 Angle step hysteresis linear measuring range 180 0 025 measuring range 180 0 05 measuring range 360 V characteristic 0 025 In uence of temperature output current 40 85 C 0 2 10K 5 5 In...

Page 12: ...8 8 3 0 Installation example With spacers this measure will be increased 54 2 60 8 10 M6 8 8 H8 10 30 47 5 10 10 30 6 2 50 5 2 59 M4 42 5 28 H7 65 5 14 3 50 55 7 78 32 max 77 55 7 12 3 0 10 1 5 5 8 Di...

Page 13: ...t of a factory programmed linear curve can be shifted if point 1 4 and 6 of the programming instruction programming linear curve are followed If there is in programming mode for about 15 minutes no bu...

Page 14: ...2004 108 EC Elektromagnetische Vertr glichkeit EMV Richtlinie Electromagnetic compatibility EMC directive EMV EMC Fachgrundnorm Generic Standard Messverfahren Measurement methods St raussendung Emissi...

Reviews: