![Camille Bauer CENTRAX CU3000 Device Handbook Download Page 33](http://html.mh-extra.com/html/camille-bauer/centrax-cu3000/centrax-cu3000_device-handbook_487894033.webp)
PM 1001606 000 07
Device handbook CENTRAX CU3000-CU5000
33/106
6.1 Parametrization of the device functionality
A full parameterization of all functions of the device is possible directly at the device (for devices with
display only) or via web browser.
See:
6.2 Operating LED (CU5000 only)
The operating LED shows the present device state.
Procedure
LED display
Booting of device
•
Flashes green (1 Hz)
•
If successful: Change to static green display
Firmware update
•
Change to update mode: Static red
•
During update: Flashes red (1 Hz)
•
If successful or cancelled: Booting of device
Factory reset or reset of communication
settings
•
During reset: Flashes red (1 Hz)
•
Then: Booting of device
6.3 Installation check
The correct connection of the current and voltage inputs can be checked in two ways.
a)
Sense of rotation check
: Using the sequence of the current and voltage phasors the sense of
rotation is determined and compared to the configured one. The phase rotation indicator is arranged
in the menu “Phasor diagram”.
Test requirement: Magnitude of all connected voltages at least 5% of nominal, magnitude of all
connected currents at least 0.2% of nominal.
Possible results
Correct sense of rotation
Wrong sense of rotation
Missing phase or magnitude too
small