Memorizing the programming
⚠
It is OBLIGATORY to conclude the programming procedures with this function so as not to lose
any saved settings!
Press + to select 5.
Press P. The display segments rotate clockwise.
The programming has been memorized.
1
RÒ
Press P for about five seconds, 1 appears.
2
Press +
and select 4.
3
Press P, appears.
4
Press + o - to set the suitable sensitivity level.
5
Minimum Sensitivity level Maximum
6
Press P to save the procedure.
Adjust the obstruction detection sensitivity during boom travel
⚠
The door must be properly balanced. If the sensitivity is too low it could cause the door to malfunction.
⚠
Change the parameter in compliance with the regulations on impact force EN 12453.
By default, the sensitivity is set to a medium level. To increase or reduce sensitivity:
The last phase of programming must always be memorized (function 5).
Once memorization is complete, perform two opening and closing cycles to confirm that the settings have been
saved.