Electric lock
It allows to choose the electric lock activation mode during the boom maneuvering phases.
F17
Electric lock
OFF (Default)
1 = The electric lock is deactivated during the boom opening and remains deactivated
until the boom is closed again.
3 = The electric lock is deactivated during the boom opening or closing operations, but
it is active when the barrier is open or closed.
Light E1
For choosing the type of device connected to the output.
F18
Light E1
0 =Flashing light (Default)
1 = Cycle light
The light remains off if an automatic closing time is not set.
Automatic cls
It sets the time that must pass before the automatic closing is activated, once the opening travel end has been reached.
The function does not work if any of the safety devices trigger when an obstacle is detected, or after a total stop, or during a power outage.
F19
Automatic cls
OFF (Default)
From 1 to 180 seconds
Pre-flashing time
It sets the early activation time before each maneuvers.
F21
Pre-flashing time
OFF (Default)
From 1 to 10 seconds
Opening speed
It sets the opening speed (percentage of maximum speed).
The percentage values automatically adapt to the value entered in the function [Boom length].
F28
Opening speed
from 60% to 100% (Default 70%)
Closing speed
Sets the closing speed (percentage of maximum speed).
The percentage values automatically adapt to the value entered in the function [Boom length].
F29
Closing speed
from 60% to 100% (Default 50%)
Travel sensitivity
Adjusting the obstruction detection sensitivity during boom travel.
F34
Travel sensitivity
from 10% to 100% (Default 100%) - 10% = maximum sensitivity - 100% = minimum
sensitivity