P
ag.
16
- Manuale
- F
A01524M4A
- 05/2022 - © C
AME S.p.A. -
Size
B
Installation examples
Installation type
C
A
Standard
B C
Wall-mounting support
Connection type
D
D
Chain connection
E
Star connection
F
Mixed connection
Installation
Remove the protective band and dome from the beacon base.
E
Drill a hole in the beacon base.
F
Insert the rubber gasket.
Thread the cable through the gasket.
Attach the base using screws and plugs (not supplied).
G
For information on wall-mounting, see fi gures
H
and
I
.
Fasten the control board to the base.
J
Electrical connections
We recommend using a FROR 2 x 1 mm cable, maximum 50 m in length from the
control panel.
Do not use a shielded cable.
Connect the fl ashing beacon to the BUS terminal on the control panel.
K
Up to 2 BUS fl ashing beacons can be connected.
Configuration
Confi gure the fl ashing beacon using the DIP switches on the control board and setting the
parameters on the control panel or via the Setup app.
DIP switches
L
DIP switch 1 (setting the address).
Summary of Contents for 806LA-0050
Page 1: ...806LA 0050 806LA 0070 FA01524M4A IT Italiano EN English FR Français RU Pусский ...
Page 3: ...Pag 3 Manuale FA01524M4A 05 2022 CAME S p A 806LA 0040 806LA 0040 C D ...
Page 4: ...Pag 4 Manuale FA01524M4A 05 2022 CAME S p A E Ø 10 max F ...
Page 5: ...Pag 5 Manuale FA01524M4A 05 2022 CAME S p A G X 3 X 4 H ...
Page 6: ...Pag 6 Manuale FA01524M4A 05 2022 CAME S p A X 3 X 3 X 4 I J ...
Page 7: ...Pag 7 Manuale FA01524M4A 05 2022 CAME S p A BUS K 1 2 3 4 1 2 3 4 1 2 3 4 L ...
Page 8: ...Pag 8 Manuale FA01524M4A 05 2022 CAME S p A AF43S AF868 M N ...