CX-12 PLUS DOOR INTERFACE RELAY

INSTALLATION INSTRUCTIONS

Page 4 of 15

File: CX-12 PLUS Manual_R3.indd 
Rev. : March 26, 2020  
Part No: 40-82B241

Washroom Door Controller

For Normally Unlocked Door set dip switches as shown. 
Also refer to Diagram 6. 

 
For Normally Locked Door set dip switches as shown. 
Also refer to Diagram 7. 

Connect the inputs from the various switches according to the 
appropriate diagram. Please note that the Magnetic contact switch 
should be a Normally Closed switch (contacts closed when door is 
closed (at rest), and contacts open when the door opens).

The “Push to Lock” switch should be a normally-open 
momentary switch. The door lock is connected to Relay 1 
(Terminals 3 & 4, or 4 & 5). Both fail safe, and fail secure locks 
may be used with the CX-22 controller.

The Automatic Door Operator is typically connected to Relay 2 
(N.O. Terminals 6 & 7). The unit will operate on 12 or 24 volts, AC or 
DC. Connect to Terminals 1 & 2, (they are non-polarity sensitive). 

Set up

Apply power to the CX-12 PLUS and observe the LED’s. 
Pot DOR/RL1 adjusts the Lock release time (up to 30 seconds). 
The Pot marked DOO/RL2 adjusts the delay before the Door 
operator relay fires, and the Operator hold time is adjusted 
with Pot DOR/RL2.

Normally Unlocked Mode 

(Mode 7)

:

Press the exterior wall switch. If the washroom is unoccupied 
the door will open automatically. After entering the washroom, 
wait for the door to close, then push the “Lock” button.

The CX-12 PLUS will energize the lock, and remove the outside 
wall switch from the circuit.

To exit the washroom, two options are available:

1.  To have the door unlock and open automatically, push the 

interior wall switch. This also resets the relay for the next 
person to use.

2.  Manual use. The door may also be used manually. To exit 

the washroom, turn the lever handle and pull (push) the 
door open. The magnet switch resets the relay for the next 
person to use.

If a CM-9600 switch is used with this system, you can connect 
the LED’s using a CM-9600C harness. Wire as per Diagram 6.

If using an “OCCUPIED WHEN LIT” sign, such as our CM-AF500, 
wire as per Diagram 6.

Normally Locked Mode 

(Mode 8)

:

In this situation the door is always locked from the exterior.

Enter code or swipe card. The door unlocks and after the 
adjustable delay, opens the door. After entering the washroom, 
wait for the door to close, then push the “Lock” button. You will 
hear a brief double click of the strike indicating the door is now 
locked, and the outside access control device is removed from 
the circuit.

To exit the washroom, two options are available:

3.  To have the door unlock and open automatically, push the 

interior wall switch. This also resets the relay for the next 
person to use.

4.  Manual use. The door may also be used manually. To exit 

the washroom, turn the lever handle and pull (push) the 
door open. The magnet switch resets the relay for the next 
person to use. Once the desired operation is achieved, 
proceed to Section 4, for System Inspection Instructions.

5. SYSTEM INSPECTION INSTRUCTIONS

After the Installation and operational check of the system:

1.  Place warning label on the door (as per ANSI A156.10 or 

A156.19 guidelines). This will advise the person entering the 
swing side zone that the door will move.

2.  Instruct the owner on door system operation and how to test 

it. This should be checked on a daily basis.

3.  Instruct the owner on what to do if the door or any of its 

components become damaged.

4.  Strongly recommend to the owner that the complete entry be 

inspected twice a year as part of the service agreement.

OFF / ON

1
2
3

OFF / ON

1
2
3

Summary of Contents for CX-12 PLUS

Page 1: ...Rating 3 Amps 30 VDC Current Draw 20 mA Idle 60 mA Operating Response Time 0 3 Seconds Inputs 2 Wet 2 Dry N O 3 30V AC DC Optically isolated non polarity sensitive Outputs 2 x Form C SPDT Electrical...

Page 2: ...o the Access System ie Keypad which then signals the CX 12 PLUS to unlock and open the door Once inside the occupant presses the Push to Lock button which removes the exterior wall switch from the cir...

Page 3: ...red therefore connect to WET 1 Terminals 9 10 The exterior activating switch is wired to DRY 2 Terminals 15 16 This input signals the door operator Relay 2 and is only active when the strike relay is...

Page 4: ...h the interior wall switch This also resets the relay for the next person to use 2 Manual use The door may also be used manually To exit the washroom turn the lever handle and pull push the door open...

Page 5: ...mm 0 12 3mm 2 31 59mm 3 25 83mm 0 61 15 5mm 0 71 18mm L4W 2T7 CX 12 CAMDEN DOOR CONTROLS 3 3 1 Power Input 12 24V AC DC Non Polarized 2 Power Input 3 Relay 1 NO FORM C 4 Relay 1 COM 5 Relay 1 NC 6 Rel...

Page 6: ...11 16 09 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 12 24 V AC DC Power Wet Input ie Radio Receiver Dry Input ie Push Switch Electric Strike Door Operator Wire MOV supplied directly to strike or...

Page 7: ...r Electric Strike If Mag lock used wire to Terminals 4 5 Exterior Switch in circuit only while Lock Relay is active Interior Switch always unlocks and opens door Access Control Time Clock sends a powe...

Page 8: ...Electric Strike If Mag lock used wire to Terminals 4 5 Interior Switch Unlocks and opens door Optional Vestibule Mounted Convenience Switch Only active when Lock Relay energized Switch opens door Wir...

Page 9: ...locks and opens door Optional Vestibule Mounted Convenience Switch Only active when Lock Relay energized Switch opens door Wire MOV supplied directly to strike or magnet Power for Strike DRY2 WET2 DRY...

Page 10: ...lea Blvd Mississauga Ontario L4W 2T7 Presence Sensor Dry contact output Fire Alarm Panel Shown with maintained powered signal wet Power for Strike DRY2 WET2 DRY1 WET1 POWER NO NO NC NC COM COM Relay2...

Page 11: ...TE 11 16 09 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 Electric Strike Dry Input ie Push Switch Wet Input ie Radio Receiver Wire MOV supplied directly to strike or magnet Power for Strike DRY2 WE...

Page 12: ...LE NONE DRAWN BY DGW REVISED 1 28 2020 DATE 02 08 09 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 Door Push Switch CAMDEN DOOR CONTROLS 1 5 2 3 4 6 7 8 9 10 11 12 13 14 15 16 RL1 RL2 DOR RL1 DOO RL...

Page 13: ...ario L4W 2T7 Door 1 Push Switch Door 2 Push Switch DRY2 WET2 DRY1 WET1 POWER NO NO NC NC COM COM Relay2 Relay1 CX 12 PLUS CAMDEN DOOR CONTROLS 1 5 2 3 4 6 7 8 9 10 11 12 13 14 15 16 RL1 RL2 DOR RL1 DO...

Page 14: ...COM Relay2 Relay1 CX 12 PLUS CAMDEN DOOR CONTROLS Note Optional annunciators may be used to indicate the door status A CM 9600 piezo switch uses optional harness for remote LED control B CM AF500 LED...

Page 15: ...Ontario L4W 2T7 Outside Wall Switch Inside Wall Switch Magnetic Contact Switch Inside Push to Lock Switch DRY2 WET2 DRY1 WET1 POWER NO NO NC NC COM COM Relay2 Relay1 CX 12 PLUS CAMDEN DOOR CONTROLS F...

Reviews: