CAMDEN CX-12 PLUS Installation Instructions Manual Download Page 3

Page 3 of 15

CX-12 PLUS DOOR INTERFACE RELAY

INSTALLATION INSTRUCTIONS

Note: Do not wire Safety devices to the CX-12.  If installed, 
wire your safety device directly to the operator control box 
as per usual.
 IMPORTANT: Do not apply power to the unit until all 
secondary wiring is complete, and dip switches have been set.

Both relay outputs are Form C and are rated at 3 amps maximum. 
Use relay # 1 for the strike or electromagnet. Generally, the N.O. & 
COM
. Terminals (#3 & 4) are used for a strike, and COM & N.C. (#4 & 
5) are used with an electromagnet.  The door operator will be wired 
to relay #2 

N.O. & COM

 terminals (#6 & 7). In a door sequencing 

application, door 1 is relay #1, and door 2 is relay #2.  The unit will 
operate on 12 or 24 volts, AC or DC.  Connect to Terminals 1 & 2, 
which are non-polarity sensitive.

4. APPLICATIONS & SET-UP INSTRUCTIONS

Standard Timer Mode 

(Mode 1)

Set dip switches as shown. Also refer to Diagram 1.

Connect a dry contact such as a wall switch to DRY1 (Terminals 
11 & 12). A Wet (powered) output connects to WET 2 (Terminals 
13 & 14).Upon a switch activation the strike relay will fire for the 
time set by potentiometer 1 (DOR RL1). After a delay, adjustable 
by potentiometer 2 (DOO RL2), the operator relay will fire. The 
hold time for relay #2 is set with potentiometer 2 (DOR RL2). 

Most modern door operators have built-in time delays, and 
if so, it is usually desirable to use them to add sufficient hold- 
open time. In this case adjust the CX-12 PLUS to send just a 
momentary pulse (1 or 2 seconds only).  Observe the door and 
adjust timers until desired operation is observed.

The above dip switch setting is also used for applications 
such as apartment entries with an interphone panel. Refer to 
Diagrams 2b & 2c.  In each case the interphone input (WET 1
will activate the strike relay only. If a courtesy switch is located in 
the vestibule, it is connected to DRY 2 (Terminals 15 & 16).

This input is only active when the strike relay is energized. 
Another application using this mode is door sequencing in 
one direction only. Connect Door 1 operator to relay 1, and 
door 2 operator to relay 2.  The delay between the two doors 
is adjusted via the DOO RL2 potentiometer. For bi-directional 
sequencing refer to specific set-up instructions below.

Access Control Mode 

(Mode 2)

Set dip switches as shown. Also refer to Diagram 2a.

Typically the access panel (or time clock) will be wet (powered) 
therefore connect to WET 1 (Terminals 9 & 10).

The exterior activating switch is wired to DRY 2 (Terminals 15 & 
16). This input signals the door operator (Relay 2), and is only 
active when the strike relay is energized.

An interior switch may be connected to DRY 1 (Terminals 11 
& 12). This input will always unlock and open the door when 
activated. (Regardless of the status of input connected to WET 
1
). If the interior switch is Wet (powered) connect to WET 2 
(Terminals 13 & 14).

Smoke Evac. Mode 

(Mode 3)

Set dip switches as shown. Also refer to Diagram 3.

Suitable for connection to a Fire Alarm Panel, this mode will fire 
the electric lock momentarily, then hold in the operator relay 
until the input is released.
Connect the Wet (powered) output of the Fire panel to WET 
2
 (Terminals 13 & 14) A device with a dry output such as a 
Presence sensor will connect to DRY 1 (Terminals 13 & 14).

Latching/Rachet Mode 

(Mode 4)

Set dip switches as shown. 
Also refer to Diagram 4a & 4b

Latching – Upon receipt of a signal (or contact closure) 
on WET1 or DRY1, RELAY1 will activate for an adjustable 
time.  Then after an adjustable time, RELAY2 will activate.  
RELAY2 will stay held until a second contact closure contact 
closure on DRY/WET1.

Ratchet - Upon receipt of a signal (or contact closure) on WET2 
or DRY2, RELAY1 will activate and stay latched.  Then after an 
adjustable time, RELAY2 will activate and stay latched.  A second 
activation of WET/DRY2 will release both relays. 

Bi-Directional Sequencing Mode

 

Mode 5: Momentary 
Mode 6: Maintained

Set dip switches as shown. Also refer to Diagram 4.
Turn on power and activate the Interior input (switch). Observe 
LED1, which should light immediately. The length of hold time is 
determined by adjusting the pot marked DOR/RL1, clockwise for 
more time, counter clockwise for less time. The delay between 
the two doors is adjusted via the DOO RL2 potentiometer. After 
the above-mentioned delay, LED2 should light. The length of 
hold time is adjusted by the pot marked DOR/RL2.

The ideal time delay between the two doors is best set by actual 
walk-testing. It should be set so that a person can walk in either 
direction without having to pause before the second door 
activates. Test in both directions.

If an emergency (or anti-entrapment) switch is desired in the 
vestibule, then wire that switch directly to one of the operator 
inputs. Usually the exterior door is used in this case. Once the 
desired operation is achieved, proceed to Section 4, for 
System Inspection Instructions.

OFF / ON

1
2
3

OFF / ON

1
2
3

OFF / ON

1
2
3

OFF / ON

MAIN

1
2
3

OFF / ON

MOM

1
2
3

OFF / ON

1
2
3

Summary of Contents for CX-12 PLUS

Page 1: ...Rating 3 Amps 30 VDC Current Draw 20 mA Idle 60 mA Operating Response Time 0 3 Seconds Inputs 2 Wet 2 Dry N O 3 30V AC DC Optically isolated non polarity sensitive Outputs 2 x Form C SPDT Electrical...

Page 2: ...o the Access System ie Keypad which then signals the CX 12 PLUS to unlock and open the door Once inside the occupant presses the Push to Lock button which removes the exterior wall switch from the cir...

Page 3: ...red therefore connect to WET 1 Terminals 9 10 The exterior activating switch is wired to DRY 2 Terminals 15 16 This input signals the door operator Relay 2 and is only active when the strike relay is...

Page 4: ...h the interior wall switch This also resets the relay for the next person to use 2 Manual use The door may also be used manually To exit the washroom turn the lever handle and pull push the door open...

Page 5: ...mm 0 12 3mm 2 31 59mm 3 25 83mm 0 61 15 5mm 0 71 18mm L4W 2T7 CX 12 CAMDEN DOOR CONTROLS 3 3 1 Power Input 12 24V AC DC Non Polarized 2 Power Input 3 Relay 1 NO FORM C 4 Relay 1 COM 5 Relay 1 NC 6 Rel...

Page 6: ...11 16 09 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 12 24 V AC DC Power Wet Input ie Radio Receiver Dry Input ie Push Switch Electric Strike Door Operator Wire MOV supplied directly to strike or...

Page 7: ...r Electric Strike If Mag lock used wire to Terminals 4 5 Exterior Switch in circuit only while Lock Relay is active Interior Switch always unlocks and opens door Access Control Time Clock sends a powe...

Page 8: ...Electric Strike If Mag lock used wire to Terminals 4 5 Interior Switch Unlocks and opens door Optional Vestibule Mounted Convenience Switch Only active when Lock Relay energized Switch opens door Wir...

Page 9: ...locks and opens door Optional Vestibule Mounted Convenience Switch Only active when Lock Relay energized Switch opens door Wire MOV supplied directly to strike or magnet Power for Strike DRY2 WET2 DRY...

Page 10: ...lea Blvd Mississauga Ontario L4W 2T7 Presence Sensor Dry contact output Fire Alarm Panel Shown with maintained powered signal wet Power for Strike DRY2 WET2 DRY1 WET1 POWER NO NO NC NC COM COM Relay2...

Page 11: ...TE 11 16 09 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 Electric Strike Dry Input ie Push Switch Wet Input ie Radio Receiver Wire MOV supplied directly to strike or magnet Power for Strike DRY2 WE...

Page 12: ...LE NONE DRAWN BY DGW REVISED 1 28 2020 DATE 02 08 09 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 Door Push Switch CAMDEN DOOR CONTROLS 1 5 2 3 4 6 7 8 9 10 11 12 13 14 15 16 RL1 RL2 DOR RL1 DOO RL...

Page 13: ...ario L4W 2T7 Door 1 Push Switch Door 2 Push Switch DRY2 WET2 DRY1 WET1 POWER NO NO NC NC COM COM Relay2 Relay1 CX 12 PLUS CAMDEN DOOR CONTROLS 1 5 2 3 4 6 7 8 9 10 11 12 13 14 15 16 RL1 RL2 DOR RL1 DO...

Page 14: ...COM Relay2 Relay1 CX 12 PLUS CAMDEN DOOR CONTROLS Note Optional annunciators may be used to indicate the door status A CM 9600 piezo switch uses optional harness for remote LED control B CM AF500 LED...

Page 15: ...Ontario L4W 2T7 Outside Wall Switch Inside Wall Switch Magnetic Contact Switch Inside Push to Lock Switch DRY2 WET2 DRY1 WET1 POWER NO NO NC NC COM COM Relay2 Relay1 CX 12 PLUS CAMDEN DOOR CONTROLS F...

Reviews: