1005759 ISSUE 2   

Model

VPT12ALX

VPT16ALX

VPT22ALX

Refrigerant 

charge 

R32 kg

0.8

0.8

1.7

Minimum area  m²

5.4

5.4

24.6

Notes

*Assumed worst case for access category: a - general access and location 

class: I - mechanical equipment in occupied space; both as defined in line with 

EN378-1 2016 section 5.1 table 4 and section 5.3

*Minimum Area is calculated in line with section C.2 on EN378-1 2016 

(calculation C.2).

3�2 REFRIGERANT TYPE AND INSTALLED 
LOCATION

This heat pump contains R32, which is an 
environmentally friendly refrigerant with a GWP 
(Global Warming Potential) of 675. R32 has the safety 
in use classification of A2L, being low toxicity and 
lower flammability. In practical terms it is very difficult 
to ignite an A2L refrigerant, but this classification 
requires a risk assessment to be undertaken for the 
possibility of refrigerant being released by accident into 
an area connected to the heat pump, considering the 
application, location of components, and the installed 
refrigerant charge. This installation guidance can form 
the framework for such a risk assessment for the 
installation. 

All flammable refrigerants will not ignite if the 
concentration level in a room stays below their lower 
flammability limit (LFL). European standard EN378 
defines requirements to remain far below the lower 
flammable limit in case of accidental leakage. By 
choosing the location as dictated by EN378-1:2016 
the probability of forming a flammable atmosphere 
can be eliminated. Please refer to the minimum 
area for each product and the interpretation below 
regarding locations of heat pump and swimming pool. 
This information is provided as a guide only and does 
not supersede the regulations or health and safety 
requirements.

INTERPRETATION

Please refer to the installation situations below for how 
to apply the minimum area stated above. 

Pool outside and heat pump outside:  

Automatically meets the minimum area requirement 
because outside space is unlimited. 

Pool outside and heat pump inside a plant room:  

Automatically meets the minimum area requirement 
because the room must open to the outside for heat 
pump airflow and the outside space is unlimited.  

Pool inside and heat pump outside:  

The pool hall must exceed the minimum area 
requirement shown above.

Pool inside and heat pump inside a plant room, 
isolated from the pool hall:  

The pool hall must exceed the minimum area 
requirement shown above. 

Pool inside and heat pump inside a plant room, 
ventilated to the pool hall:  

The pool hall and plant room combined must exceed 
the minimum area requirement shown above. 

Summary of Contents for V-PAC VPT 12 ALX

Page 1: ...V PAC inverter heat pumps VPT 12 16 22 Owner Installation Manual 1005759 Issue 2...

Page 2: ...s This appliance can be used by children from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision...

Page 3: ...CKS 15 3 6 ELECTROLYTIC CORROSION IN SWIMMING POOLS 16 3 7 ELECTRIC WIRING AND SUPPLY 16 3 8 CONNECTING THE HEAT PUMP TO THE POWER SUPPLY 17 3 9 POOL PUMP OVERRIDE TERMINALS P1 P2 18 4 0 USING YOUR HE...

Page 4: ...e heat pump Please read and follow all safety advice The refrigerant used in this heat pump is R32 This refrigerant is environmentally friendly but safety instructions must be strictly adhered to The...

Page 5: ...e following location requirements must be fulfilled The heat pump must be kept away from sources of fire or naked flames The heat pump must be installed operated and stored where the floor area is lar...

Page 6: ...orms can damage electronic equipment Ideally the heat pump should be switched off at the mains HEAT PUMP MALFUNCTION WARNING Isolate heat pump electrically and wait 3 minutes before removing panels or...

Page 7: ...nts may not contain an odour Appliance shall be installed operated and stored in a room with a floor area larger than Xm2 where X is the minimum area shown in section 3 2 and section 8 0 The heat pump...

Page 8: ...e heat pump upright Do not lift the heat pump by the water inlet or outlet connections If this is done the titanium heat exchanger inside the heat pump could be damaged 2 2 ACCESSORIES These accessori...

Page 9: ...AND RANGE Air temperature operating range V PAC VPT X models 5 43 C Water temperature setting range Heating 18 C 40 C Cooling 12 C 30 C 2 5 OPERATING MODES The heat pump has three modes Powerful mode...

Page 10: ...air drawn through it To function effectively the heat pump must have access to the fresh air it needs Air must not recirculate The air leaving the heat pump must not be sucked back into the inlet Air...

Page 11: ...e areas m2 Model Discharge area VPT 12 0 188 VPT 16 0 188 VPT 22 0 220 Required free areas to provide air flow to and from heat pumps when installed in an enclosed area or where required to pass air t...

Page 12: ...WNER INSTALLATION MANUAL To comply with safety regulations regarding electrical installations in wet areas the heat pump must be installed at least 350cm away from the edge of the pool or spa 350 cm S...

Page 13: ...s below their lower flammability limit LFL European standard EN378 defines requirements to remain far below the lower flammable limit in case of accidental leakage By choosing the location as dictated...

Page 14: ...tiser fitted Non return valve Sanitiser or chemical dosing device If fitted Aux heater If fitted Filter Pump To waste for winterising drain down 100mm Condensate water to waste Spare port for winteris...

Page 15: ...r in Supported pipework 3 5 INITIAL CHECKS Start the filtration pump before the heat pump is turned on and turn off the heat pump before the filtration pump It is recommended to turn off the heat pump...

Page 16: ...s includes non electrical items such as metal filters pump strainer boxes heat exchangers steps and handrails It is highly recommended that bonding be retrofitted to existing pools which may not be pr...

Page 17: ...D Circuit Breaker P1 P2 Power terminals Pump terminals Cable clamp Single phase Terminals in Heat Pump Electrics enclosure Isolator which disconnects all poles fitted within 2m and in line of sight of...

Page 18: ...clock and the heat pump runs the pool filter pump for temperature sampling and if the pool subsequently requires heating cooling This feature operates by over riding the timeclock whenever the control...

Page 19: ...indicator light Powerful Smart Silent M 88 88 Silent mode indicator light Power HEAT COOL Heating indicator light Timer on indicator light Timer off indicator light Cooling indicator light Powerful Sm...

Page 20: ...Defrosting 1 Automatic defrosting When machine is defrosting the heating indicator lamp flashes after defrosting the flashing stops 2 Forced Defrosting When machine is heating and the compressor has b...

Page 21: ...o adjust these Press M again to and it will now show the timer off time Adjust these in the same way as the timer on Once complete press M to save the setting h Cancel timer There are two ways to canc...

Page 22: ...r will sound twice and all parameter values will change back to their default values QUERY CODE MEANING RANGE 1 Water inlet temperature 20 99 C 2 Water outlet temperature 20 99 C 3 Ambient temperature...

Page 23: ...wer supply immediately then contact your dealer The fuse blows frequently or leakage circuit breaker trips frequently If above solutions don t work please contact your installer with detailed informat...

Page 24: ...will resume standby once process is completed 3 Er 21 Ambient temperature is out of range either lower than 5 C or higher than 43 C If outside wait for ambient conditions to improve winterisation may...

Page 25: ...exhaust gas temperature alarm Er 15 Water inlet temperature sensor failure Er 16 Evaporator coil temperature sensor failure Er 18 Exhaust gas temperature sensor failure Er 19 DC fan motor error Er 20...

Page 26: ...Check bolts cables and connections regularly Repair service and disposal of redundant heat pumps must be completed by authorised technicians It is illegal to allow refrigerant gases to escape to air D...

Page 27: ...ated input current A 1 21 8 9 1 23 12 0 3 45 19 6 Maximum input current A 12 5 15 5 24 5 Rated RCD type F mA 30 30 30 Rated Fuse aM MCB type C A 16 20 32 Sound level at 10m dB A 29 30 30 Recommended w...

Page 28: ...N VPT12 ALX 650 98 362 650 626 220 835 600 92 490 190 430 588 130 VPT16 ALX 650 98 362 650 626 220 835 600 92 490 190 430 588 130 VPT22 ALX 752 138 387 745 721 240 967 695 92 530 228 505 705 157 F I B...

Page 29: ...provide frost protection To eliminate corrosion problems To inhibit electrical components 1 Switch off electrical supply to heat pump 2 Remove external fuses and keep in safe place away from heat pump...

Page 30: ...nd duct pressure are outside the specified limits 9 The air flow to and from the machine is outside the specified limits If in doubt or if advice is required please contact the Dantherm Group UK Servi...

Page 31: ...31 1005759 ISSUE 2 12 0 DECLARATION OF CONFORMITY...

Page 32: ...Dantherm Ltd Unit 12 Galliford Road Maldon CM9 4XD United Kingdom 44 0 1621 856 611 sales uk dantherm com Calorex is a brand of danthermgroup co uk...

Reviews: