LAMP
ACTION
MODE
FAN ON COMPRESSOR OFF
HEAT
COOL
MAINS
RED
ON
CHILL
RED
OFF
CHILL LIMIT
AMBER
ON
Check thermostat set point is not set too low
P
WATER FLOW OK
GREEN
ON
Check 12 hours elapsed since first power up.
OTHER LAMPS
OFF
MAINS
RED
ON
HEAT
RED
ON
Unit on defrost (normal) - check air flow not restricted
P
DEFROST
WHITE
ON
Ensure temperature is above 9°C for a standard model.
P
P
OTHER LAMPS
OFF
UNIT OPERATES INTERMITTENTLY
MAINS
RED
ON
P
CHILL
RED
OFF
P
FAULT
AMBER
ON
Check linked in external equipment is not the cause of
the fault.
WATER FLOW OK
GREEN
OFF
OTHER LAMPS
OFF
MAINS
RED
ON
CHILL
RED
OFF
CHILL LIMIT
AMBER
ON/OFF
FAULT
AMBER
OFF
Check thermostat set point is not set too low.
P
WATER FLOW OK
GREEN
ON
OTHER LAMPS
OFF
If the machine suffers from poor performance and the low pressure
switch(es) trip and cannot be reset (the fridge fault lights also
illuminate) then this may be a symptom of a refrigerant leak.
Put the unit is Standby mode and isolate from the power supply.
Contact a refrigerant technician authorised in accordance with EU
517/2014 as soon as possible.
31
SD566250 ISSUE 35
Summary of Contents for Pro-Pac 140
Page 1: ...Pro Pac system Pro Pac 30 45 70 90 140HC Owner installation manual SD566250 issue 35...
Page 2: ...2 SD566250 ISSUE 35 PR0 PAC SYSTEM OWNER INSTALLATION MANUAL...
Page 50: ...50 SD566250 ISSUE 35 PR0 PAC SYSTEM OWNER INSTALLATION MANUAL...
Page 51: ...51 SD566250 ISSUE 35...
Page 54: ...2 SD566250 ISSUE 35 SYSTEME PRO PAC MANUEL D INSTALLATION...
Page 102: ...50 SD566250 ISSUE 35 SYSTEME PRO PAC MANUEL D INSTALLATION...
Page 103: ...51 SD566250 ISSUE 35...