1005494 ISS 1
3�0 INSTALLATION
> 50 cm
Plant room
Calorex*
Wall
Calor
ex
Possible positions of a Calorex heat pump
Wall
Suitable opening
Calorex* >70 cm
Calorex
>70 cm
>250 cm
Calorex The red lines represent the air inlet area
Swimming pool or spa
* Controls are obscured by the wall� Connect to
Remote control panel or Wi-Fi before installing
the heat pump in position�
Required free areas to provide air flow to and from heat
pumps when installed in an enclosed area or where
required to pass air through a wall etc.
Free area is the available area through which air can
pass through a grille or louvres.
Minimum free areas m
2
Model
Discharge area
IPT 8
0.169
IPT 12
0.169
IPT 16ALX
0.169
IPT 16ALY
0.229
IPT 22
0.301
IPT 28
0.301