11
1006905 ISSUE 2
> 50 cm
Plant room
Calorex*
Wall
Calor
ex
Possible positions of a Calorex heat pump
Wall
Suitable opening
Calorex*
>70 cm
Calorex
>70 cm
>250 cm
Calorex The red lines represent the air inlet area
Required free areas to provide air flow to and from heat
pumps when installed in an enclosed area or where
required to pass air through a wall etc. Ensure the heat
pump is sealed against the wall so the outlet air cannot
recirculate. Ensure the hole through the wall is sealed
to avoid the outlet air entering cavities and is smooth
so the outlet air is not restricted.
Free area is the available area through which air can
pass through a grille or louvres.
Minimum free areas m
2
Model
Inlet area
Discharge area
CPT 6
0.313
0.13
CPT 8
0.313
0.13
CPT 12
0.422
0.17
CPT 15
0.422
0.17
CPT 20
0.515
0.20