Page 11
5.
ELECTRICAL (MACHINE WIRING AND SUPPLY).
SEE FIGURES 5,6,7 AND 8 FOR PREFERRED METHOD
Use of the Calorex Energy Management Controller will enable greater savings to be made because the
circulating pump need only run when required and this can be at a time preferred by the customer, i.e. in the
Economy 7 period.
All electrical work to be carried out in accordance with l.E.E. standards, latest issue, or local codes of practice
as applicable.
The machine should be installed in line with EMC2004/108/EC.
Protected supply
to incorporate fuses or motor type circuit breakers (Type GU, FAZC) to specified rating, (see
Data Sheet). H.R.C. fuses are recommended. An isolator must be fitted within 2m and in sight of machine.†
All units must be correctly earthed-grounded. An earth leakage trip of the Current operating type (30mA) is
recommended to be fitted to all pool electrics.
INCONSISTENT ELECTRICAL SUPPLY
The following limits of operation must not be exceeded if Calorex machines are to be guaranteed either in
performance or warranty terms:
Minimum
Maximum
Voltage
Single phase machines
207V
253V
Cycle frequency
47.5Hz
52.5Hz
N.B. This voltage must be available at the heat pump whilst running.
† Note the isolator must have a minimum of 3mm air gap when turned off.
IMPORTANT:-
The user should be made aware that on all the installations shown by figures 5, 6, 7 and
8 that to work on part of the intallation the supply to all parts of the installation must be
isolated.
Summary of Contents for 29 Series
Page 1: ...Page 1 Owner Installation Manual for AW629 829 AIR WATER HEAT PUMPS SD546250 Issue a...
Page 27: ...Page 1 Manual d utilisation pour LES POMPES A CHALEUR AIR EAU AW629 829 SD546250 Issue a...
Page 53: ...Seite 1 Gebrauchsanweisung f r AW629 829 LUFT WASSER W RMEPUMPEN SD546250 Ausgabe a...
Page 54: ......
Page 56: ......
Page 82: ......
Page 84: ......
Page 110: ......
Page 112: ......