background image

iL Series User Manual 
 

 
60 

Rev B 

California Instruments 

Step  Action 

Expected 
Result 

1. 

Make sure the AC source is turned off. Connect a DVM 
across the sense terminals. 

 

2. 

Turn on the AC source with no load on the output. 
Program the output for a 150 volt, 60 Hz sinewave, 
external sense. Set the output current limit to its 
maximum value. If the source you are verifying is in 
three-phase mode, start by verifying output phase 1 
(Ø1). 

CV

 annunciator 

on. 
Output current 
near 0. 

3. 

Record voltage readings at DVM and on front panel 
display. 

Readings within 
low voltage 
limits specified 
in Table 41. 

4. 

Program the voltage to 300 volts. 

 

5. 

Record voltage readings of DVM and on front panel 
display. 

Readings within 
high voltage 
limits specified 
in Table 41. 

6. 

If the AC source you are verifying is in three-phase 
mode, repeat steps 1 through 5 for output phases 2 and 
3.  Press Phase Select to select the next phase. 

 

Table 39 : Voltage programming readback test steps 

6.2.3  Current Programming and Readback Accuracy 

This test verifies the current programming and readback.  Connect the appropriate 
current monitoring resistor (see Table 38) as shown in Figure 19. The accuracy of 
the resistor must be as specified in the table. 

  

Step  Action 

Expected 
Result 

1. 

Turn off the AC source and connect the current 
monitoring resistor as shown in Figure 19. Be certain to 
use wire of sufficient size to carry the maximum rated 
current of the AC source (see Table 6 in chapter 2). 

 

2. 

Connect a DVM across the resistor 

 

3. 

Turn on the AC source and program the output for 5 volts 
and the Low Current value specified in Table 41.  If the 
AC source you are verifying is in three-phase mode, start 
by verifying output phase 1 

 

4. 

Enable the output (Output On/Off or OUTP ON) 

 

5. 

Observe the DVM voltage reading.  Divide this by the 
resistance of the current monitor resistor. Record the 
result as the Low Current value in Table 41. 

Value within 
low current 
limits 
specified in 
Table 41. 

6. 

Record the front panel display readback. 

Value within 
readback 
limits 
specified in 
Table 41. 

Summary of Contents for iL Series

Page 1: ...iL Series AC Power Source Analyzers User Manual Revision B April 1996 Copyright 1995 1996 by California Instruments All rights reserved P N 5001 967...

Page 2: ...ii Rev B California Instruments User s Manual AC Power Source Analyzers California Instruments Models 3000iL 3000iL 400 4500iL 4500iL 400 4801iL 4801iL 400 Copyright 1995 California Instruments Rev B...

Page 3: ...cedure practice or the like which if not correctly performed or adhered to could result in personal injury Do not proceed beyond a WARNING sign until the indicated conditions are fully understood and...

Page 4: ...mains through a grounded power cable with the ground wire firmly connected to an electrical ground safety ground at the power outlet Any interruption of the protective grounding conductor or disconnec...

Page 5: ...ary Checkout 19 3 2 Using the Keypad 19 3 3 Output Checkout 20 3 4 In Case of Trouble 23 4 Front Panel Operation 25 4 1 Introduction 25 4 2 Front Panel Description 25 4 2 System Keys 28 4 3 Function K...

Page 6: ...ooting Procedure 70 7 4 Firmware Revisions 71 8 Principles of Operation 76 8 1 Introduction 76 8 2 General Description 76 8 3 Assembly Descriptions 76 9 Replaceable Parts 80 9 1 Introduction 80 9 2 Re...

Page 7: ...l Overall View 25 Figure 13 Function Keys 29 Figure 14 Entry Keys 38 Figure 15 Pulse Transients 43 Figure 16 List Transients 44 Figure 17 Trigger Delays and Phase Synchronization 46 Figure 18 Phase Sy...

Page 8: ...26 Trigger control list display readouts 37 Table 27 List command display readouts 37 Table 28 Setting the output voltage amplitude 40 Table 29 Setting individuals output phases in three phase mode 4...

Page 9: ...iL Series User Manual California Instruments Rev B ix page intentionally left blank...

Page 10: ......

Page 11: ...formation on the following tasks in these manuals Refer to the table of contents of each manual for a complete list of the topics Table 1 User Manual Organization Topic Location Accessories and Option...

Page 12: ...d review this manual for safety warnings and instructions Safety warnings for specific procedures are located at appropriate places in the manual 1 4 General Description The AC source combines three i...

Page 13: ...rent and peak current Real reactive and apparent power Harmonic analysis of voltage and current waveforms gives amplitude phase and total harmonic distortion results up to the 50th harmonic Triggered...

Page 14: ...of a wide variety of AC source operating conditions Refer to the iL Series SCPI Programming Manual part number 5001 969 for further information about remotely programming the AC source 1 4 4 Output C...

Page 15: ...A available to a load can be determined by examining figure 1 3 the output power curve This curve rates the available VA versus output voltage Full VA is available only at full scale voltage Full curr...

Page 16: ...ments the AC source s specifications and supplemental characteristics 1 5 Options and Accessories Option Description 400 Input power 360 440 Vac three phase 47 63 Hz Table 3 Options Item CI Part Numbe...

Page 17: ...onnector cover 250578 4 terminal digital connector plug 410636 AC input safety cover 5001 226 1 AC input safety cover strain relief 211112 AC input safety cover bushing 211114 Screw 4 AC input safety...

Page 18: ...the AC source has to be returned Obtain a Return Material Authorization number by contacting California Instruments Customer Service department prior to returning any equipment for service Also attach...

Page 19: ...ck the fan exhaust at the rear of the unit Figure 4 Outline Diagram 2 6 Rack Mounting Due to their size and weight iL Series AC power sources are frequently rack mounted The three iL models weigh 87 7...

Page 20: ...r cord must be done by a qualified electrician and in accordance with local electrical codes See Figure 5 and proceed as follows Check the line fuses as follows Examine the FUSES label on the rear pan...

Page 21: ...as a termination for each of the output phases and a floating neutral line for the phase return connections A separate earth ground terminal is located near the output terminals To minimize the possib...

Page 22: ...e Gage AWG characteristics NOTES 1 Ampacity is based on 30 C ambient temperature with conductor rated at 60 C For ambient temperature other than 30 C multiply the above ampacities by the following con...

Page 23: ...inal Connect the Neutral COM sense terminal connector to the neutral side of the load Figure 7 Remote Sense Connections The sense leads are part of the AC source s feedback path and must be kept at a...

Page 24: ...information on programming external triggers is found in chapter 5 of the AC source SCPI Programming Manual Trigger IN allows negative going external trigger signals to trigger the ac source Trigger O...

Page 25: ...re of the fault via a service request SRQ generated by the Questionable Status summary bit Figure 8 FLT INH Examples 2 12 Controller Connections The iL Series comes standard equipped with both IEEE 48...

Page 26: ...s You can specify one of the following parity options seven data bits with even parity seven data bits with odd parity eight data bits without parity You can also specify one of the following baud rat...

Page 27: ...e power source sets DTR false under two conditions 1 When the input buffer is full approximately 100 characters have been received it will set DTR false When enough characters have been removed to mak...

Page 28: ...cter to be recognized by the power source while it holds DTR false the bus controller must first set DSR false Response Data Terminator All RS 232C response data sent by the AC source is terminated by...

Page 29: ...ator on and all others off Meter mode means that the VOLTS digits indicate the output voltage and the FREQ digits indicate the output frequency The voltage will be at or near zero and the frequency wi...

Page 30: ...y 425 V peak at their output DEATH on contact may result if the output terminals or circuits connected to the output are touched when power is applied The output checkout test requires that you connec...

Page 31: ...n Repeat steps 3 and 4 for phase 2 and phase 3 of three phase sources All three light bulbs should be lit when this action is complete 5 Press Voltage VOLT 120 6 Press Phase Select VOLT 120 Select unt...

Page 32: ...t is in current limit mode and the light bulbs are dimmer because the output voltage has dropped in its attempt to limit output current 16 Press Protect scroll to the CURR PROT item and press to selec...

Page 33: ...iled Error 6 Non volatile RAM LIST section checksum failed Error 10 RAM selftest Error 11 to 18 DAC selftest 1 to 8 Table 10 Power on selftest Error codes 3 4 4 Runtime Error Messages Under unusual op...

Page 34: ...s 4 If any fuses are defective replace all three with fuses of the same type see section 1 6 5 Turn on the AC source and check the operation If it is normal replace the fuse cover Note It is recommend...

Page 35: ...quency how to measure the output how to program output pulses and lists how to trigger output changes 4 2 Front Panel Description Figure 11 Front Panel Overall View Display 14 character vacuum fluores...

Page 36: ...se generators let you set the output voltage and frequency when the AC source is in local mode Their response is rate sensitive Turning a control rapidly provides coarse control of the value Turning a...

Page 37: ...iL Series User Manual California Instruments Rev B 27...

Page 38: ...t to scroll through the following command list Use and to scroll through the parameter list Display Command Function ADDRESS value Set IEEE 488 address INTF char Select interface GPIB or RS232 BAUDRA...

Page 39: ...it When off the AC source output is disabled and the Dis annunciator is on Shift Trigger Sends an immediate trigger to the AC source Phase Select This key selects the phase to which function commands...

Page 40: ...hase 3 selected phases coupled NONE Table 14 Phase selection display annunciators 1 Does not apply to Meter or Harmonic functions When the Meter and Harmonic functions are active Phase Select only rot...

Page 41: ...eter lists are circular you can return to the starting position by continuously pressing either key If the command has a numeric range these keys increment or decrement the existing value 4 4 3 Meter...

Page 42: ...current harmonic magnitude reading N PHASE index neutral current harmonic phase reading CURR THD current total harmonic distortion reading VOLT THD voltage total harmonic distortion Table 16 Harmonic...

Page 43: ...list Display Command Function Phase selectable CURR LEV value Set immediate rms output current limit yes Table 18 Current limit display readouts Freq Press this key to access the frequency menu list D...

Page 44: ...hapes will also appear in this list when created yes SHAPE M char Select the shape mode FIXED STEP PULSE or LIST no CLIP value Set the clipping level of the CSIN wave shape This specifies the point wh...

Page 45: ...ent of output impedance to value between 0 and 1 ohm 4801iL only IMP REAC value Set the reactive inductive component of output impedance to value between 0 00002 and 0 001 Henries 4801iL only PON STAT...

Page 46: ...in the following list commands ending in clear the registers when they are read For this reason the registers are read only after you press Enter not when you scroll to the command Display Command Fun...

Page 47: ...ndex value List of output frequency slew rates no PHASE index value List of output voltage phase angles yes SHAP index char List of output waveform shapes SINE SQUARE or CSIN CSIN clipped sine wave Us...

Page 48: ...point For example to enter 33 6 press 3 3 6 The backspace key deletes the last digit entered from the keypad This key lets you correct one or more wrong digits before they are entered Enter This key e...

Page 49: ...Generating step pulse and list transients Programming trigger delays and phase synchronization Programming slew rates Saving and recalling operating states Setting the IEEE 488 address or RS 232C par...

Page 50: ...s phase 2 to 180 Vrms and phase 3 to 235 Vrms Step Action Display 1 On the Function keypad press Voltage Note that in the power on default state the 1 2 and 3 annunciators are all lit indicating that...

Page 51: ...Step Action Display 1 On the Function keypad press Freq FREQ 60 2 You can set the frequency in either of two ways On the Entry keypad press 5 0 Enter FREQ 50 Rotate the panel Frequency knob to obtain...

Page 52: ...to sequence through a number of values as determined by points entered in the List menu FIXED disables transient operation for the selected function 4 6 5 Step Transient The Voltage Menu lets you spec...

Page 53: ...example the output is programmed to generate four 5 5 millisecond 120 Vrms pulses at 60 Hz Figure 14 shows the trigger pulse count pulse period and duty cycle Figure 14 Pulse Transients From the Outpu...

Page 54: ...d in example 1 for setting the immediate output voltage 4 6 7 List Transient Lists are the most flexible means of generating multiple or synchronized transient outputs The following figure shows a vol...

Page 55: ...until you access the voltage list This specifies the amplitude of each output point during its corresponding dwell period The first voltage list point 0 appears in the display From the Entry keypad e...

Page 56: ...the specified phase angle after the trigger signal is received Example describes phase synchronization on three phase sources Note that phase synchronization is referenced to an internal phase signal...

Page 57: ...mediate and triggered voltage levels followed by the voltage transient mode VOLT 120 VOLT T 150 VOLT M STEP 2 Press Trigger Control Press t until you access the delay parameter If necessary set it to...

Page 58: ...Press Trigger Control and t to access the sync source command On the Entry keypad press once to obtain PHASE Press Enter SYNC SOUR PHASE 4 Access the Trigger Control menu again and press t to access t...

Page 59: ...n example a triggered slew rate of 50 volts second steps the voltage level to its new value 50 volts second becomes the new immediate slew rate in step mode In example a triggered slew rate of 50 volt...

Page 60: ...the triggered slew command On the Entry keypad enter a value such as 5 0 Enter which sets the triggered slew rate to 50 volts second SLEW T 50 4 Then press Trigger Control Enter followed by Shift Tri...

Page 61: ...t filter capacitors to discharge completely This example shows you how you can measure the peak inrush current using the front panel meter The voltage is set to 120 V rms and the output is triggered a...

Page 62: ...PK NR 11 Enable the output by pressing Output On Off 0 V 60 HZ 12 Send the trigger to step the output from 0 V to 120 V Press Shift Trigger Control The inrush current is displayed on the Meter 48 A PK...

Page 63: ...d as follows Step Action Display 1 Set the instrument to the operating state that you want to save 2 Save this state to location 1 by pressing SAVE 1 and ENTER SAV 1 To recall a saved state proceed as...

Page 64: ...low range 120 A 40 A 120 A 40 A 96 A high range 60 A 20 A 60 A 20 A 48 A Crest Factor Current 6 0 4 0 3 0 Output Frequency Range 45 Hz 5 kHz 45 Hz 1 kHz Constant Voltage Ripple and Noise 60 dB 20 kHz...

Page 65: ...t 0 4 and 796 H Synchronization 1 ppm Current shunt burden 0 Volts Current harmonic smoothing filter 1 5 sec Pst Integration time 1 5 10 or 15 min Sample rate Window width Acq overlap 50 Hz Operation...

Page 66: ...0 1 08 X 106 s 0 4 30 X 105 s Triggering Accuracy With Respect to Phase Synchronization 250 s 100 s Trigger In Response Time 400 s 200 s Minimum Resolution for Dropout 500 s Output Response Time outp...

Page 67: ...TE6 RS 232C Interface Capabilities Baud rates 300 600 1200 2400 4800 9600 Data formats 7 bits even or odd parity 8 bits without parity Language SCPI Standard Commands for Programmable Instruments Regu...

Page 68: ...ired Description Digital Voltmeter Resolution 10 nV 1 V Readout 8 5 digits Accuracy 20 ppm Example HP 3458A Current Monitor The 4 terminal current shunt is used to eliminate output current measurement...

Page 69: ...6 2 Operation Verification Perform the following tests for operation verification in the order indicated 1 Turn On Checkout 2 Voltage Programming and Readback Accuracy 3 Current Readback Accuracy 6 2...

Page 70: ...programming readback test steps 6 2 3 Current Programming and Readback Accuracy This test verifies the current programming and readback Connect the appropriate current monitoring resistor see Table 38...

Page 71: ...tor resistor Record the result as the High Current value in Table 41 Value within high current limits specified in Table 41 10 Record the front panel display readback Value within readback limits spec...

Page 72: ...ng and Readback Low Current 5 A Iout 4 95 A A 5 05 A Front Panel Display Readback Iout 30 mA A Iout 30 mA High Current 10 A Iout 9 93 A A 10 07 A Front Panel Display Readback Iout 35 mA mA Iout 35 mA...

Page 73: ...to next step in sequence P1 P2 P3 or P4 CAL DATA value input a calibration measurement CAL VOLT AC begin AC voltage calibration sequence CAL VOLT PROT begin voltage protection calibration CAL CURR AC...

Page 74: ...directly to the AC source via the ratio transformer shown in Figure 19 Do not connect the load resistor or current shunt 6 Press Shift Calibration scroll to the CAL VOLT AC command and press Enter CAL...

Page 75: ...brating and Entering Current Calibration Values 19 Connect the appropriate current shunt and load resistor as shown in Figure 19 Connect the DVM ac rms mode across the current shunt If you are calibra...

Page 76: ...for DVM reading to stabilize Then read DVM and compute the second current value DVM reading shunt resistance Use the Entry keypad to enter the second current value CAL DATA 0 00 Calibrating the Outpu...

Page 77: ...password to 0 zero 6 4 4 Calibration Error Messages Errors that can occur during calibration are shown in the following table Error no Error Meaning 401 CAL switch prevents calibration 1 402 CAL pass...

Page 78: ...calibration functions are accessible after entering a numeric password The default password is 0 and is changeable by the user Clear Password The calibration password is reset to 0 and the remote prog...

Page 79: ...by ESD electrostatic discharge Failure to observe standard antistatic practices can result in serious degradation of performance even when an actual failure does not occur When working on the AC Powe...

Page 80: ...SP board To re initialize unit turn CAL ON then press 0 and 9 simultaneously Press scroll key to model number then press enter When unit is re initialized all CAL data user defined WAVEFORM data and L...

Page 81: ...lize the unit perform the following Turn the unit on then do the front panel CAL ON command Press 0 and 9 keys simultaneously EEINIT model should now be displayed Scroll to the correct model number an...

Page 82: ...lose Are fans running If not Check C1 for 300 VDC 300 VDC is initially supplied via 3 relays fuses and resistors at bottom of A9 board 6 Bias voltages are supplied from the A10 Auxiliary power supply...

Page 83: ...5 16 21 22 25 26 10 Are all phases missing If Yes Check 300 VDC rail from CR1 C1 to F1 F2 and F3 on A4 mother board Check for sine wave at A6J4 1 to A6J4 2 A6J4 3 to A6J4 4 A6J4 5 to A6J4 6 Table 46 A...

Page 84: ...iL Series User Manual 74 Rev B California Instruments Figure 21 Troubleshooting Diagram for No Output Present...

Page 85: ...iL Series User Manual California Instruments Rev B 75 Figure 22 Troubleshooting Diagram for One or More Outputs Missing...

Page 86: ...ase input is connected to the power rectifier CR1 L1 and C1 to create 300 VDC required by the power amplifiers A1 A2 and A3 The amplifier assemblies together with the output filter and range relays pr...

Page 87: ...t current setting The A8 board also contains all the logic circuits for generating arbitrary waveforms frequency changes and phase control At power on the DSP board performs a self test and reports fa...

Page 88: ...the A4 mother board via J2 the 15 V and 5 VSEC go to the A6 servo board via J4 and 5 VSEC goes to the A8 DSP board via J5 The A10 supply also supplies the 12 VDC to 24 VDC for the fan speed control A...

Page 89: ...iL Series User Manual California Instruments Rev B 79 Figure 23 AC Power Source Block Diagram...

Page 90: ...8 250650 Controller DSP Assembly 4801iL A9 5001 702 1 Input PS Assembly 208 volt A9 5001 706 1 Input PS Assembly 400 volt A10 5001 703 1 Auxiliary Power Supply Assembly A11 250571 Display Assembly A12...

Page 91: ...226 1 AC input safety cover strain relief 211112 AC input safety cover bushing 211114 Screw 4 ac input safety cover 6 32 x 1 5 in FS1144 Ac output safety cover 250576 Screw 2 ac output safety cover 6...

Page 92: ...is chapter contains drawings and diagrams for troubleshooting and maintaining the California Instruments iL family of AC power sources Unless otherwise specified in the drawings a drawing or diagram a...

Page 93: ...iL Series User Manual California Instruments Rev B 83 Figure 25 AC Input Board Parts Location...

Page 94: ...iL Series User Manual 84 Rev B California Instruments Figure 26 Mother Board Parts Location...

Page 95: ...wn below list all ESR error messages generated by the AC source Messages in the table are grouped by Code Error type Error Error String 100 Command error generic 101 Invalid character 102 Syntax error...

Page 96: ...eived 430 Query DEADLOCKED too many queries in command string 440 Query UNTERMINATED after indefinite response 0 No error 1 Non volatile RAM RDO section checksum failed 2 Non volatile RAM CONFIG secti...

Page 97: ...passcode is incorrect 403 CAL not enabled 404 Computed readback cal constants are incorrect 405 Computed programming cal constants are incorrect 406 Incorrect sequence of calibration commands 600 Syst...

Page 98: ...8 15 INH RI 14 input 10 output 11 RS 232 16 sense 13 trigger 14 controls front panel 3 Current key 35 CV 27 D DFI 14 diagrams 86 dimensions 9 Dis 27 E Enter 20 Enter key 42 entry keys 28 Err 27 Error...

Page 99: ...utions safety iv principles of operation 80 amplifier modules 80 auxiliary power supply 82 bias power supply 82 BNC assembly 82 display assembly 82 DSP assembly 81 input power supply assembly 81 82 is...

Page 100: ...iL Series User Manual California Instruments Rev B 91 trigger system 49 troubleshooting 73 U Unr 27 V Voltage key 34 W wire table 12...

Reviews: