All dimensions in mm
ELECTRICAL INSTALLATION / DIMENSIONS
!
!
Caution! Check the identification tags and ensure all
wiring is correct before applying power to the sensor.
* A choice of indicating controllers, providing
temperature display and relay outputs, is also available.
Contact Calex for more information.
+
+
-
-
PWR+
PWR-
OP+
21.5
Ø 31.0
30.0
13.3
AL
Optical field of view
Output cable
Standard length: 1 m
(Red)
(Blue)
(Green)
2 x mounting holes
M3 x 0.5 mm
Depth 7 mm
Mounting screws included
Ø 3.2
nominal
Configurable 0-5, 1-5 or 0-10 V DC
output, linear with measured
temperature, for display or controller*
Power supply
24 V DC
Open collector output
for alarm,
6 to 24 V DC, 50 mA max
Protection
diode
(Yellow)
6
POWER SUPPLY
Use a 24 V DC power supply.
Connect power between the PWR+ and PWR- wires. Do not apply voltage to the incorrect
wires as this will damage the sensor. See “Dimensions and Connections” for wiring.
IMPORTANT: Ensure the power supply is only connected to the PWR+ and PWR- wires, and the
polarity is correct, before switching the power on.
Ensure the supply voltage is suitable for the selected output type. For the 0-10 V DC output,
the supply voltage must be 12 to 24 V DC.
Do not switch the power off and on again quickly. If the power is switched off, allow 15
seconds before switching it back on.
If using the alarm output, choose a load that draws no more than 50 mA when powered from
1.2 to 24 V DC. For example, if the alarm supply voltage is 24 V DC, ensure the load is at least
480 Ω (24 V / 0.05 A = 480 Ω).