CALEFFI SATK22107 Instructions For Installation, Commissioning And Maintenance Download Page 13

13

ACS a punto fisso

limite temperatura ritorno

compensazione

intervento limite temperatura ritorno

climatica

ACS a punto fisso

limite temperatura ritorno

compensazione

intervento limite temperatura ritorno

climatica

ACS a punto fisso

limite temperatura ritorno

compensazione

intervento limite temperatura ritorno

climatica

ACS a punto fisso

limite temperatura ritorno

compensazione

intervento limite temperatura ritorno

climatica

preriscaldo

ricircolo

Impostazione default limitazione 

portata massima

Esempio limitazione portata massima

Impostazione relè di default

Impostazione default limitazione 

portata massima

Ciclo antilegionella

DHW function

DHW Comfort functions (pre-heating, DHW recirculation)

The DHW cycle always takes priority over the heating cycle.

DEFAULT SETTING: fixed DHW set point (parameter t06 = 0)

When DHW cycle activation is requested, due to DHW tapping by 

the user (detected by the domestic water flow meter), the regulator 

modulates the valve opening in order to adjust the temperature 

detected by the domestic water probe to the selected set point value.

When tapping ends, the modulating valve is fully closed.

The DHW cycle ON condition is indicated by the blinking 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

 symbol.

OPTIONAL SETTING: primary return temperature limit 
(technical parameter t06 = 1)

When DHW cycle activation is requested, due to DHW tapping by 

the user (detected by the domestic water flow meter), the regulator 

modulates the valve opening in order to adjust the temperature 

detected by the domestic water probe to the DHW set point value 

if the return temperature is less than or equal to the set limit. If this 

condition is not met, the flow temperature is reduced (by a maximum 

of 7°C down to a temperature that can be no less than 40°C), in order 

to bring return temperature within the limit values. 

Due to the activation of the return temperature limitation 

function, DHW temperature can be lower than the set value.

DHW/primary return limit temperature setting

To set the DHW temperature press the <SET> key until the symbol in 
the red circle appears; for the return temperature limit press the key 
until the symbols in the green circle are displayed. Use the <R> knob 
to change the value (*).
The range of possible DHW temperatures is 42–60°C, while the range 
of possible return temperatures is 15–45°C.

(*) if these set points cannot be changed you must set parameter t07 to value 0 in the technical menu (see “access to technical menu” below). 
Parameter t07 = 1 “freezes” the operating set points to prevent inadvertent modifications by the user.

The comfort function can be, alternatively, preheating of the DHW 

plate heat exchanger or management of DHW recirculation. They are 

enabled by setting to ON or PROG the comfort function (see page 11).

DEFAULT SETTING: DHW exchanger preheating function 
(parameter t02 = 0)

During periods when the domestic water cycle is not used, if the DHW 

probe detects a temperature 10°C below the SET value, the regulator 

partially opens the domestic hot water modulating valve for the time 

required (max. 5 min.) to bring the exchanger to the condition wherein 

it can assure rapid DHW production.

The active pre-heating cycle is indicated by the blinking 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

 

symbol.

This function is of lower priority than any domestic water or heating 

cycles.

OPTIONAL SETTING: management of DHW recirculation in the 
apartment (parameter t02 = 1)

In alternative to the DHW comfort function it is possible to manage DHW 

recirculation, using a similar logic. During periods when the domestic 

water cycle is not used, if the DHW probe detects a temperature 10°C 

below the SET value, by means of an auxiliary microswitch (see page 

19), the regulator closes the circuit supplying the circulation pump (not 

supplied) generating a DHW cycle lasting for a pre-set amount of time.

This amount of time is pre-set to 2 minutes. It can be changed by acting 

on parameter t09 on the technical menu (1 unit = 10 seconds).

The circulator has to be fed through the auxilliary microswitch 

so that the control of recirculation is carried out by the heat 

interface unit. DHW recirculation (t02=1) disables the other 

functions operating on the auxilliary microswitch described on 

page 16. Refer to page 16 for the electrical characteristics of 

the microswitch.

Both comfort functions can be enabled according to user defined 

weekly time programming. Refer to the remote user interface manual.

preriscaldo

ricircolo

Impostazione default limitazione 

portata massima

Esempio limitazione portata massima

Impostazione relè di default

Impostazione default limitazione 

portata massima

Ciclo antilegionella

preriscaldo

ricircolo

Impostazione default limitazione 

portata massima

Esempio limitazione portata massima

Impostazione relè di default

Impostazione default limitazione 

portata massima

Ciclo antilegionella

preriscaldo

ricircolo

Impostazione default limitazione 

portata massima

Esempio limitazione portata massima

Impostazione relè di default

Impostazione default limitazione 

portata massima

Ciclo antilegionella

N.B.: In the presence of a DHW recirculation system a suitably 
sized expansion vessel must be installed.

Summary of Contents for SATK22107

Page 1: ...mestic hot water capacity 50 kW 1 With primary pump SATK22405 Direct wall mounted HIU for HIGH temp heating Domestic hot water capacity 60 kW 1 With primary pump SATK22407 Direct wall mounted HIU for...

Page 2: ...acteristics of both units into consideration 10 An combination coupling could compromise the operation of the device and or system IMPORTANT Risk of electric shock Live parts Shut off the electric sup...

Page 3: ...primary circuit Dp 600 kPa 6 bar Domestic water circuit max flow rate 24 l min 0 4 l s Minimum flow rate to activate domestic water flow meter 2 l min 0 3 Electric supply 230 V ac 10 50Hz Max power c...

Page 4: ...r primary circuit air vent Characteristic components SATK2210 LOW temperature Hydraulic diagram SATK2210 and SATK2220 TS TA 2 V V V V V V 3 4 7 12 13 5 6 8 9 10 11 21 14 15 19 24 20 17 16 17 22 23 25...

Page 5: ...draulic diagram SATK2230 and SATK2240 TS TA 2 V V V V V V 3 4 7 12 13 5 6 8 9 10 11 21 14 15 19 24 20 17 16 17 22 23 25 TA 2 V V V V V V 3 4 7 5 6 8 9 10 11 21 13 14 19 22 20 23 16 17 18 SATK2210 only...

Page 6: ...out template code 789023 Hydraulic installation Preliminary operations installation without template After having established the point of installation of the appliance perform the following operation...

Page 7: ...bottom Connections on the top Heat meter installation The HIU is fitted to house a compact heat meter with incorporated return probe with 1 threaded connections and length of 130 mm Before carrying o...

Page 8: ...directed toward the exterior of the HIU using the pathways provided in the insulation and on the frame All the low voltage lines must be routed through a single dedicated cable raceway using the path...

Page 9: ...ntrol Refer to the dedicated user manual for the procedure Filling the central heating system Open the shut off valves on the connections to the centralised line and in the central heating system proc...

Page 10: ...riarmabile funzione scaldamassetto R mode ACS ON OFF Risc ON OFF set Ora giorno corrente Temperature di set point k regolazione climatica day night Set diurno nottu prog Programmazione oraria riscalda...

Page 11: ...oint k regolazione climatica day night Set diurno notturno temp Visualizzazione temperature set point ambiente sonde prog Programmazione oraria riscaldamento e funzione comfort reset Reset errore riar...

Page 12: ...ed the display shows the symbol OPTIONAL SETTING weather compensation technical parameter t01 3 When the function is enabled the flow temperature is calculated based on the temperature detected by the...

Page 13: ...menu see access to technical menu below Parameter t07 1 freezes the operating set points to prevent inadvertent modifications by the user The comfort function can be alternatively preheating of the DH...

Page 14: ...ntrolling the maximum opening of the primary circuit modulating valve Since latter is controlled by a differential pressure limiter it is possible to supply direct correspondence between the opening p...

Page 15: ...wo seconds and then press the same key repeatedly until reaching the required characteristic refer to the figure below Having identified the required characteristic head flow rate chart shown below wa...

Page 16: ...xternal primary flow pump normally OFF The contact must be closed if any HIU function is active DHW production heating pre heating Parameter t05 must be set to 1 2 4 7 example 2 Distinction of consump...

Page 17: ...ire twisted cable Compliance with this requirement becomes even more significant the more extensive the RS 485 network If alternatively a shielded wire is used the shield must be connected solely on t...

Page 18: ...code 76 Corrective action Normal operating conditions are restored automatically once the faulty safety valve works properly again reriscaldo circolo Impostazione default limitazione portata massima...

Page 19: ...PAID AUX RS 4 IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN...

Page 20: ...pty the heat interface unit using the drain cocks provided Exchanger replacement As a preliminary step remove the flow sensor refer to replacing the DHW priority flow meter on page 21 and position it...

Page 21: ...e previous paragraph Extract the obturator unscrewing the locking nut F Replace the obturator screw on the locking nut F and then fit the actuator Insert the fixing clip respecting the correct directi...

Page 22: ...ature set point disable the function primary circuit strainer of the HIU clogged call qualified personnel to have it serviced exchanger partly clogged call qualified personnel to have it serviced modu...

Page 23: ...on in charge of system electronic regulator not working call qualified personnel to have it replaced primary circuit flow rate insufficient contact person in charge of system centralised system not wo...

Page 24: ...if required been carried out 13 Has the remote user interface been configured for installation on board thermostat function disabled inside the apartment with thermostat function enabled 14 Have the h...