Adjustment Channels
Channel
Description
Factory setting
Page
Arr
x
System
3
39
DT O
x
Switch-on temperature difference
12.0 °Ra [6.0 K]
39
DT F
x
Switch-off temperature difference
8.0 °Ra [4.0 K]
39
DT S
x
Nominal temperature difference
20.0 °Ra [10.0 K]
39
RIS
x
Rise control R1
4 °Ra [2 K]
39
n1MN
x
Minimum pump speed R1
30 %
39
S MX
x
Maximum tank temperature
140 °F [60 °C]
40
OSEM
x
Option tank emergency shutdown
OFF
40
EM
x
Emergency temperature collector
270 °F [130 °C]
40
Emergency temperature collector if ODB is activated:
200 °F [95 °C]
40
OCC
x
Option collector cooling
OFF
41
CMX
x*
Maximum collector temperature
230 °F [110 °C]
41
OSYC
x
Option system cooling
OFF
41
DTCO
x*
Cooling switch-on temperature difference
40.0 °Ra [20.0 K]
41
DTCF
x*
Cooling switch-off temperature difference
30.0 °Ra [15.0 K]
41
OSTC
x
Option tank cooling
OFF
42
OHOL
x*
Option holiday cooling
OFF
42
THOL
x*
Holiday cooling temperature
110 °F [40 °C]
42
OCN
x
Option minimum limitation
OFF
42
CMN
x*
Minimum collector temperature
50 °F [10 °C]
42
OCF
x
Option antifreeze
OFF
42
CFR
x*
Antifreeze temperature
40.0 °F [4.0 °C]
42
O TC
x
Option tube collector
OFF
44
TCST
x*
OTC starting time
07:00
44
TCEN
x*
OTC ending time
19:00
44
TCRU
x*
OTC runtime
30 s
44
TCIN
x*
OTC standstill interval
30 min
44
OHQM
x
Option energy metering
OFF
44
FMAX
x*
Maximum flow
6.0 l
44
MEDT
x*
Antifreeze type
1
44
MED%
x*
Antifreeze concentration
45 %
44
AH O
s
Switch-on temp. for thermostat 1
110 °F [40 °C]
14
AH F
s
Switch-off temp. for thermostat 1
120 °F [45 °C]
14
t1 O
s
Switch-on time 1 thermostat
00:00
14
t1 F
s
Switch-off time 1 thermostat
00:00
14
t2 O
s
Switch-on time 2 thermostat
00:00
14
t2 F
s
Switch-off time 2 thermostat
00:00
14
t3 O
s
Switch-on time 3 thermostat
00:00
14
t3 F
s
Switch-off time 3 thermostat
00:00
14
ODB
x
Drainback option
OFF
45
tDTO
x*
ODB switch-on condition - time period
60 s
45
tFLL
x*
ODB filling time
5.0 min
45
tSTB
x*
ODB stabilization time
2.0 min
45
OTD
s
Option thermal disinfection
OFF
15
PDIS
s*
Monitoring period
01:00
15
DDIS
s*
Heating period
01:00
15
TDIS
s*
Disinfection temperature
140 °F [60 °C]
15
SDIS
s*
Starting time
00:00
15
MAN1
x
Manual operation R1
Auto
46
MAN2
x
Manual operation R2
Auto
46
ADA1
x
HE pump control
OFF
46
LANG
x
Language
En
46
UNIT
x
Temperature unit
°C
46
RESE
x
Reset - back to factory defaults
46
W0050100
Version number
Legend:
Symbol
Specification
x
Channel is available
x*
Channel is available if the corresponding option is activated.
s
Channel is specifically available in this system layout
s*
System-specific channel, only available if the corresponding option is activated