background image

Shut-off and check valves

The  shut-off  valves  are  equipped  with  a  built-in  check  valve,

positioned inside the ball.

1. To  allow  the  passage  of  the  fluid

in  both  directions,  the  ball  valves

must  be  opened  at  45°,  using  a

9 mm fixed wrench.

The check valve is opened by the

ball, see figure (A).

2. In  normal  system  operation,  the

ball  valves  must  be  completely

open.

Air separator device

The  solar  circulation  units  with  flow  and  return  connection  are

equipped with an air separator device on the flow line. The gases

separated from the thermal carrier medium collect at the top of the

deaerator.

The  collected  gases  must  be  evacuated  from  time  to  time  (every

day  after  commissioning  and  afterwards,  depending  on  the

quantity of air, once a week or once a month) using the manual air

vent with a suitably sized screwdriver.

To  maintain  optimal  efficiency  of  the  solar  thermal  system,

afterwards,  it  is  necessary  to

vent  the  system  every  six

months by using the deaerator.

A

Full closing and opening of the valve

The 

valve 

can 

be

completely  opened  or

closed.

A  slot  on  the  obturator

stem 

indicates 

the

status of the valve.

Correction for liquids with different density

The  variation  in  the  flow  rate  reading  remains  within  the  range  of

accuracy indicated (±10%), for glycol percentages up to 50%.

Fully closed

Fully open

7

Captive nut

Flow rate adjustment

Fitting 1/2” F

Graduation

Fitting 3/4” F

Flow meter

The  flow  meter  is  a  floating  gauge  flow  rate  measurator  with  a

built-in regulating ball valve.

It works within the range of 1–13 l/min.

The flow meter must be fitted in a vertical position only.

A  thermometric  label  is  placed  on  the  back  of  the  flow  meter  to

signal  if  the  maximum  permitted  temperature  (110°C)  has  been

exceeded: 

white color = temperature not exceeded;

dark color = maximum temperature exceeded.

The  label  removal  makes  the  manifacturer  warranty  on  the  device

expire.

The level is taken from the

top edge of the float.

N.B!

Use only a 9mm fixed

wrench to regulate the flow

meter.

13

11

9

7

open

closed

23

0

°

F

110

°

C

Thermometric

label

A

B

Summary of Contents for DeltaSol 268050

Page 1: ...devices for optimum control of the circuit are fitted in the units They are available with flow and return connection or with return connection only Some versions are also complete with the digital r...

Page 2: ...ges with hydraulic leaks and damage to property and or personal injury Water temperatures exceeding 50 C may cause severe burns When installing commissioning and servicing take the necessary precautio...

Page 3: ...ment 1 13 l min Flow rate indicator accuracy 10 Pressure gauge scale 0 10 bar Temperature gauge scale 0 160 C Connections 3 4 F Hose connection 3 4 M Fill drain connections with 15 mm hose connection...

Page 4: ...mperature indication 13 Regulating keys 14 Temperature probe 15 Stainless steel probe pocket code 257004 optional 16 Hose connection only for versions with DeltaSol C regulator 1 2 3 4 5 8 9 11 10 16...

Page 5: ...d in the assembly phase at the factory However when commissioning it is necessary to check the seal of the fittings performing a pressure test Make the electrical connections of the system as specifie...

Page 6: ...e deaerated again both in the highest point and on the air separator on the versions where this is contemplated Once deaeration has been completed check the system pressure and if necessary restore to...

Page 7: ...m every six months by using the deaerator A Full closing and opening of the valve The valve can be completely opened or closed A slot on the obturator stem indicates the status of the valve Correction...

Page 8: ...e nor me ISPESL 0 2 4 6 8 10 bar CL 2 5 1 13 11 9 7 5 3 l min 1 13 11 9 7 5 3 l min 1 13 11 9 7 5 3 l min a Shut off valve Pump Air vent Expansion vessel Temperature gauge Safety relief valve Automati...

Reviews: