Hydraulic characteristics
The hydraulic separator should be sized according to the maximum flow rate value at the inlet.The
selected design value must be the greatest required flow rate of either the primary circuit or the
secondary circuit.
Union
Flanged
Size
1"
1
¼
" 1
1
/
2
"
2"
2"
2
1
/
2
"
3"
4"
5"
6"
8"
10"
12"
14"
gpm
11
18
26
37
60
80
124
247
300
484
792 1330 1850 2500
l/s
0.7
1.1
1.6
2.3
3.8
5.0
7.8
16
19
30
50
84
117
158
gallons
0.5
0.7
1.3
3.5
4.0
4.0
8.0
8.0
22.5
23
95
175
255
450
liters
1.9
2.6
4.9
13.2 15.1 15.1 30.3 30.3 85.2 87.0 360
662
965 1703