background image

Technical specifications of insulation on union models

 

 

(purchase separately, field install)

Material:                                                                                               closed-cell expanded PE-X
Thickness:                                                                                                              13/16" (20 mm)
Density: - inner part:                                                                                      1.9 lb/ft

3

 (30 kg/m

3

)

 - 

outer part:                                                                                     3.1 lb/ft

3

 (50 kg/m

3

)

Conductivity (ISO 2581):                                        at 32°F (0°C): 9 BTU.in/hr.ft

2

.°F  (0.038  W/(m.K)                                                                                   

 

                                                         at -40°F (-40°C); 11 BTU.in/hr.ft

2

.°F (0.045 W/(m·K)

Coefficient of resistance to the diffusion of vapor:                                                                   > 1,300
Temperature range:                                                                                         32–210°F (0–100°C)
Fire resistance (DIN 4102):                                                                                                 class B2

Technical specifications of insulation, flanged versions to 4"

Internal part

Material:                                                                              rigid closed cell expanded polyurethane foam 
Thickness:                                                                                                                   2 3/8" (60 mm)
Density:                                                                                                             2.8 lb/ft3 (45 kg/m3)
Thermal conductivity:                                                                       6 BTU.in/hr.ft2.°F (0.023 W/(m.K))
Temperature range:                                                                                         32–220°F (0–105°C)

Outer part

Materials:                                                                                                           embossed aluminum 
Thickness:                                                                                                               7.0-mil (0.7 mm)
Reaction to fire (DIN 4102):                                                                                                    class 1

Head covers

Heat formed materials:                                                                                                                    PS

4

Summary of Contents for 548 Series

Page 1: ...steel with flanged connections vent drain and insulation connections 2 2 1 2 3 4 ANSI NA548 series Hydraulic separator in steel with flanged connections vent drain and insulation ASME and CRN connecti...

Page 2: ...nection size 1 inch 9 size 1 inch 9 size 1 inch 11 size 2 inch 12 Drain valve garden hose thread CAUTION If the hydraulic separator is not installed commissioned and maintained properly according to t...

Page 3: ...lve body brass Performance Suitable fluids water and non hazardous glycol solution up to 50 Max operating pressure 150 psi 10 bar Working temperature range with insulation 32 220 F 0 105 C without ins...

Page 4: ...efficient of resistance to the diffusion of vapor 1 300 Temperature range 32 210 F 0 100 C Fire resistance DIN 4102 class B2 Technical specifications of insulation flanged versions to 4 Internal part...

Page 5: ...t Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 18 Service Instructions There is no service required for the hydraulic separator CAUTION Corrosion or leakage can cause damage or inju...

Page 6: ...red flow rate of either the primary circuit or the secondary circuit Union Flanged Size 1 1 11 2 2 2 21 2 3 4 5 6 8 10 12 14 gpm 11 18 26 37 60 80 124 247 300 484 792 1330 1850 2500 l s 0 7 1 1 1 6 2...

Page 7: ...eparators NA10778 fits 1 and 1 union 548 series NA10796 fits 1 union 548 series NA10797 fits 2 union 548 series Replacement drain valve for 548 series union connection Hydro separators 538402 FD NPT x...

Page 8: ...eriodically inspect for signs of corrosion or leakage If corrosion or leakage is noted the vent must be replaced Failure to follow these instructions could result in property damage and or personal in...

Reviews: