Supplementary notes to:

Installation, commissioning and servicing instructions

The following supplementary notes must be read in conjunction with the
installation, commissioning and servicing instructions, code 

....

, for the

Caleffi thermostatic mixing valves 5213TM series.

Product Range

Item code 521312TM: with strainers and check valves at the inlets 15 mm (1/2”) male,
compression end connection for copper pipe.
Item code 521319TM: with strainers and check valves at the inlets 20 mm (3/4”) male,
compression end connection for copper pipe

Approvals

SAI global approval

The Caleffi 5213TM series thermostatic mixing valves are approved by SAI Global as
satisfactory to the requirements of AS 4032.1 : 2005 and it has the Licence N° 2466.

NSW approval

The Caleffi 5213TM series thermostatic mixing valves are approved by the relevant authorities
for use in health care buildings.

This product must be installed and commissioned in accordance with the manufacturer’s
instructions, with the requirements of the local Water Supply Authority and with the documents
following:

1) “Hosplan Code of Practice for Thermostatic mixing valves”, 1990
2) Rule NSW 5.22 of the NSW Code of Practice “Plumbing and Drainage”, 1999
3) NSW Department “Code of Practice for the Control of Legionnaires’ Disease”, 1991
4)  AS 4032.1 2005 and AS 4032.3:2005 Australian Standard for Thermostatic Mixing Valves
5) Regulation under Nursing Homes Act 1998 and Private Hospitals and Day Procedure 

Centres Act 1988

12

F. istr. 38650_5213 9-07-2007 14:04 Pagina 12

Summary of Contents for 521312TM

Page 1: ...e i e within hospitals schools nursing homes etc The valve is designed to prevent the flow of water discharging from the mixed water outlet in the event of the failure of hot or cold supply The valve...

Page 2: ...e static 1400 kPa Maximum working pressure dynamic 500 kPa Minimum working pressure dynamic 20 kPa Maximum unbalanced dynamic supply hot cold or cold hot 6 1 Minimum temperature differential between h...

Page 3: ...ve If there are variations of temperature or pressure at the inlets the internal element automatically reacts attempting to restore the original temperature setting Thermal shut off In the event of a...

Page 4: ...ower bath or bidet The system must be sized taking into account the current legislation with regard to the nominal flow rate of each outlet The reference is AS NZS 3500 1 G l min 5 2 2 5 3 3 5 4 10 1...

Page 5: ...9 10 4 6 7 5 2 3 1 VALVE BODY UNION NUT SEAL INSERT CHECK VALVE TAIL PIECE BODY INSERT STRAINER TEMPERATURE SPINDLE LOCKING NUT FLOW CONVEYOR THERMOSTATIC ELEMENT O RING SEAL UNDER SPRING UPPER BODY...

Page 6: ...the outlet of the valve to any terminal fitting We recommend that the Caleffi 5213TM series valve is installed as close as practically possible to the outlet which it is serving The connecting hot an...

Page 7: ...ost Importance i e within hospitals schools nursing homes etc This type of valve is intended mainly for use in applications with set temperature below 45 C Thermostatic Mixing Valve Thermostatic Mixin...

Page 8: ...e established the valve can be commissioned Due to the unique design of the cap the temperature setting can be adjusted by removing the cap from the valve body and reversing the cap onto the temperatu...

Page 9: ...Temperature adjustment Remove the cap Direction of temperature adjustment Temperature adjustment Lock adjustment spindle with locking nut 1 2 3 4 9 F istr 38650_5213 9 07 2007 14 04 Pagina 9...

Page 10: ...213TM series valves can be accessed in a similar way to 1 to ensure freedom of operation and correct seating 3 In case of service work the internal components of the valve can be dis assembled for cle...

Page 11: ...e water supplies at the inlets of the valve c Incorrect commissioning of the valve a Insufficient water supplies b Fluctuations in supply pressures temperatures c Adverse effect created by other draw...

Page 12: ...ry to the requirements of AS 4032 1 2005 and it has the Licence N 2466 NSW approval The Caleffi 5213TM series thermostatic mixing valves are approved by the relevant authorities for use in health care...

Page 13: ...be used for temperatures and pressures outside the above limits please consult the Australian Agent 3 If the cold water temperature is near freezing point refer to AS 3500 1 2 4 Temperature setting m...

Page 14: ...Pressure ratio This pressure ratio is calculated as Hot dynamic inlet pressure Cold dynamic inlet pressure or Cold dynamic inlet pressure Hot dynamic inlet pressure The maximum dynamic pressure ratio...

Page 15: ...15 F istr 38650_5213 9 07 2007 14 04 Pagina 15...

Page 16: ...16 F istr 38650_5213 9 07 2007 14 04 Pagina 16...

Page 17: ...17 F istr 38650_5213 9 07 2007 14 04 Pagina 17...

Page 18: ...18 F istr 38650_5213 9 07 2007 14 04 Pagina 18...

Page 19: ...19 F istr 38650_5213 9 07 2007 14 04 Pagina 19...

Page 20: ...2 8491 R A Fax 39 322 863723 Http www caleffi com E mail info caleffi it AUSTRALIAN AGENT ALL VALVE INDUSTRIES Pty Ltd 30 205 Port Hacking Road Miranda NSW 2228 Tel 02 8543 5111 Fax 02 8543 5122 E mai...

Reviews: