The controller checks the tanks regarding loading facilities
(switch-on difference). If the priority tank cannot be loaded,
the lower-ranking tank is checked. If the lower-ranking tank
can be charged this is effected by the so-called „oscilating
charge time“ (
tRUN
).When the oscillating charge time is
over the loading is stopped. The controller regulates the
increase of the collector temperature. If it increases by the
collector rising temperature (
∆
T-Col 4°Ra, fixed software
value), the expired break time is again reset to zero and the
oscillating break time starts again. If the switch-on conditions
of the priority tank are not reached, the loading of the
lower-ranking tank is continued. If the priority switch has
reached its maximum temperature, the oscillating charge is
not effected.
Oscillating break time / oscillating charge time /
collector rising temperature
4.1.17 Tube collector special function
If the controller measures an increase of 4°Ra compared
to the collector temperature stored at last, the solar pump
is switched-on to 100 % for about 30 seconds. After the
expiration of the solar pump runtime the current collector
temperature is stored as a new reference value. If the
measured temperature (new reference value) is again
exceeded by 4°Ra, the solar pump again switches-on for 30
seconds. If the switch-on difference between collector and
tank is again exceeded during the runtime of the solar pump
or the standstill of the system, the controller automatically
switches over to solar charging.
If the collector temperature drops by 4°Ra during standstill,
the switch-on value for the special tube collector function
will be recalculated.
O TC:
Tube collector special function
Adjustment range: OFF ... ON
Factory setting: OFF
4.1.16 Recooling function
If the adjustem maximum tank temperaute (
S MX, S1MX,
S2MX
) is reached, the solar pump remains activated in
order to avoid an overheating of the collector. The tank
temperature might continue to increase but only up to
205°F (emergency shutdown of the tank).
In the evening the solar system continues running until
the tank is cooled down to the adjusted maximum tank
temperature via collector and pipes.
OREC:
option recooling
adjustment rangeOFF ... ON
Factory setting: OFF
4.1.15 Oscillating charge
Respective adjustment values:
Factory setting
Adjustment range
priority
[PRIO]
(1 / Arr 5,6) (2 / Arr 4)
0-2
oscillating break-time [tST]
2 min.
1-30 min.
oscillating charge-time [tRUN]
15 min.
1-30 min.
Die iSolar Plus 24V priority logic
The above-mentioned options and parameters only have
a meaning in multi-tank systems (system Arr = 4, 5, 6). If
priority 0
is adjusted, the tanks which show a temperature
difference towards the collector are loaded in numerical
order (tank 1 or tank 2). Usually only one tank is loaded at
this point. For Arr= 5, 6 parallel loading is also possible.
priority: