38

(Auto disabled after 
10h)

Automatically reset after 10 hours.

39

Operation mode

Set operation mode

Regulator

Pressure regulation function.

40

Sensor 0+2000

Pressure sensor function with 8 measurement 
ranges.

41

Digital input

Set D.IN function

DI1 function:

Function selector for digital input 1.

42

Motor alarm

Alarm function for fan motor thermal cut-out. 
Alarm in the event of interruption.

43

Force setpoint

Function for overriding a force setpoint. The over-
ride is not compensated for outdoor temperature.

44

100 Pa

Current override setpoint for digital input 1.

45

DI2 function:

Function selector for digital input 2.

46

Motor alarm

Alarm function for fan motor thermal cut-out. 
Alarm in the event of interruption.

47

Force setpoint

Other force setpoint function which is compen-
sated for outdoor temperature.

48

100 Pa

Current override setpoint for digital input 2.

49

Set time & date

Set time and date

Not available

Not available in this version.

50

Factory reset

Factory reset

Reset all settings?

Resetting CALAIR-PR-230V to factory settings.

51

No

Cancel resetting and return to Misc. Menu.

52

Yes

Complete reset to factory settings and return to 
Misc. Menu. NB! Zero pressure calibration must 
be carried out.

53

Back

Back to main menu.

54

MODBUS menu Address

Set MODBUS addr.

1

Current MODBUS address.

55

(1-247)

Settings range.

56

Baud rate

Set MODBUS baud 
rate

9600

Current baud rate.

57

(9600, 19200…)

Settings range.

58

Parity

Set MODBUS parity

NONE

Current parity.

59

(NONE, EVEN, 
ODD)

Settings range.

60

Back

Back to main menu.

61

Exit/save

Return to normal display mode and save all 
changes.

MODBUS REGISTER

Pressure regulator MODBUS register.

Holding register 
address

Register content

Value range

Read/Write

0

MODBUS  address

1  to  247

R

1

Pressure

-200Pa to +2000Pa

R

2

Mean pressure

-200Pa to +2000Pa

R

3

Output voltage (V)

0-100(*1)

R

4

Temperature (°C)

-300 to +700(*1)

R

5

Digital input 1

0,1

R

6

Digital input 2

0,1

R

7

Alarm relay

0,1

R

8

Setpoint

0Pa to 2000Pa

R

9

Manual setpoint

0Pa to 2000Pa

RW

10

Temperature from MODBUS (°C)

 -300 to +700(*1)

RW

11

Regulator speed

1-10

RW

12

Output range low

0-100%

RW

13

Output range high

0-100%

RW

14

Operation mode

1-9(*2)

RW

15

Mean operation mode

1-3(*3)

RW

Summary of Contents for CALAIR-PR-230V

Page 1: ...ngar t ex h g och l gtryckslarm De tio senaste larmen sparas i en larmlogg Funktion garanteras med slangl ngd upp till 100 m Efter montage kontrollera att luft kan str mma fritt genom slangen MONTERIN...

Page 2: ...0 C Inst llningsomr de 20 Temp kompens V lj temp komp 50Pa Antalet Pascal som b rv rdet s nkts vid Low se rad 17 ovan 21 Minskar b rv rdet med 0 500Pa F rklaring och inst llningsomr de 22 Temp justeri...

Page 3: ...t verstyrningsb rv rde f r digitaling ng 2 49 St ll tid och datum St ll tid och datum Ej tillg ngligt Ej tillg ngligt i denna version 50 Fabriks terst lln Fabriks terst lln terst ll allt terst llning...

Page 4: ...tor alarm function 2 Force setpoint DI1 DI2 setpoint 6 Register 30 Override DAC from MODBUS must be set to 1 7 FIFO Alarm log latest alarm on register 44 0 No alarm 1 High pressure alarm 2 Low pressur...

Page 5: ...hermal cut out or changed force setpoint The force setpoint on DI2 is compensated for outdoor temperature in the same way as the ordinary setpoint is compensated The setpoint on DI1 is however fixed R...

Page 6: ...dj Set temp adj 0 0 C Adjustment of temperature measurement 3 0 C to 3 0 C 23 Back Back to main menu 24 Alarm menu Alarm log Alarm log No items found Back Alarm log 25 High press alarm Set high press...

Page 7: ...all settings Resetting CALAIR PR 230V to factory settings 51 No Cancel resetting and return to Misc Menu 52 Yes Complete reset to factory settings and return to Misc Menu NB Zero pressure calibration...

Page 8: ...Das Produkt ist mit zugentlasteten Kabeldurchf hrungen versehen die beim Installieren zu spannen sind Beim Installieren die Zugentlastung pr fen und ggf nachstellen MEN SPRACHE W HLEN Gleichzeitig die...

Page 9: ...DI2 wird durch die Au entemperatur genauso kompensiert wie der normale Sollwert w hrend der Sollwert von DI1 ein fester Wert ist Siehe Zeilen 41 48 in der Tabelle unter Men system MODBUS RTU VIA RS485...

Page 10: ...C Einstellung der Temperaturmessung 3 0 C bis 3 0 C 23 Zur ck Zur ck zum Hauptmen 24 Alarm Men Alarmprotokoll Alarmprotokoll Nichts gefunden Zur ck Alarmprotokoll 25 Hochdruckalarm W hle Hochdruckalar...

Page 11: ...llung auf Werkseinstellung und zur ckgehen zum Misc menu ACHTUNG Nulldruckkalibrierung muss durchgef hrt werden 53 Zur ck Zur ck zum Hauptmen 54 MODBUS Men Adresse MODBUS Adresse 1 Aktuelle MODBUS Adr...

Page 12: ...1000Pa 8 Pressure sensor 0Pa to 1600Pa 9 Pressure sensor 0Pa to 2000Pa 3 Mean operation mode 1 Regulation on direct pressure value 2 1 28 sec mean value 3 2 56 sec mean value 4 Temperature sensor typ...

Reviews: