P
ocket
R
efeRence
G
uide
— 35
(cont’d)
9. Enter Conduit Type and find
Conduit Size:
(Cond Type)
RMC 1.25 in
COND SIZE
10. Find total number of Wires:
2.
TTL WIRES
11. Find Conduit Fill Percent:
FILL 24.3
% COND
12. Find actual Fill Area:
FILL 0.3710
TTL WIRE AREA
13. Find Remaining Area:
REM 0.1021
WIRE AREA
Finding Conduit Size —
Multiple conductors, Different Wire
Sizes and types
Three 1/0 THWN conductors and one
#2 XHHW conductor are to connect to
a panel board using a single Conduit.
What is Conduit Size needed and
actual Fill Area?
KEYSTROKE
DISPLAY
0.
1. Enter Conduit Type:
(Cond Type)
FMC nonE
COND
2. Enter first Wire Size:
*
AWG 0 Cu
WIRE SIZE
KEYSTROKE
DISPLAY