P
ocket
R
efeRence
G
uide
— 33
KEYSTROKE
DISPLAY
0.
1. Enter nameplate Current:
AMPS 19.2
2. Find Overload size:
AMPS 22.08 o l
3. Display percent used:
%FLC 115.
%
4. Find 125% Load:
AMPS 24. o l
5. Display percent used:
%FLC 125.
%
6. Reset Overload rating and Clear:
0.
ConDuIT sIZe
The
ElectriCalc Pro
can calculate the
size of Conduit required when running
single or multiple Wires using the
key and the calculator’s internal
tables. To select a specific Conduit
Type, enter the corresponding number
of the Conduit as shown below and
then press
.
1) EMT 4) IMC
7) LFMC 10) P-40
2) ENT 5) LFNB 8) RMC 11) P-A
3) FMC 6) LFNA 9) P-80 12) P-EB
(cont’d)