IV.3.

 

IV.3 Variable pulley settings 

 

The variable pulley allows to set airflow. 

 

 

1 = fixed flange 
2 = threaded sleeve 
3 = variable flange 
4 = pulley locking screw 
5 = flange locking screw 
 

The variable flange can move on the threaded sleeve. To move the 
flange, first unscrew the flange locking screw, then turn the flange. 
Screwing the flange will expend pulley

s diameter, ie higher airflow. 

Uncrewing the flange will reduce pulley

s diameter, ie lower airflow. 

 
After settings, make sure both locking screws are secured and the the 
pulleys alignment is fine. 
 

 

V.

 

Troubleshooting 

 

Problem 

Main reasons 

How to solve 

Fan not running 

Main power off 
Thermal motor protection on 
Wrong wiring 
Broken belt 

Turn power on 
Check wirings 
 
Check  /  replace  belt  (one  spare  belt 
delivered) 

Boxfan abnormal vibrations 

Dirty impeller 
Tool left in casing 
Casing not fixed properly  

Clean impeller 
Check inner casing 

Belt short lifetime 

Bad belt tension 
Pulleys not aligned properly 

Check belt 
Check pulleys 

Wrong airflow 

Closed ducts 
Dirty filters 
Impeller turning the wrong way 
Wrong pressure drops calculation 

Check duct system 
Change filters if any 
Reverse two phases on main power 
 

 

 

 

Summary of Contents for PYROSTAR F400-120

Page 1: ...PYROSTAR SMOKE FAN F400 120 MS MTG 001 Ind E 01 10 2019 Page 1 8 INSTALLATION AND COMMISSIONING MANUAL...

Page 2: ...I 1 Handling 3 II 2 Space required for maintenance 4 II 3 II 3 Installation 4 III ELECTRICAL WIRING 4 III 1 Wiring 4 III 2 1 speed motors 4 III 3 III 3 2 speeds motors 5 III 4 III 4 2 speeds motors se...

Page 3: ...handled using a fork lift truck ensure this supports the load bearing structure and does not touch the panels enclosing the unit If the device is moved using a crane use four cables of identical lengt...

Page 4: ...outdoor or when installed indoor separated from other volumes by a 1 hour fire resistant wall The door of the technical room should be hour fire resistant Ventilation of this technical room should com...

Page 5: ...4 III 4 2 speeds motors separate windings 2 speeds 1 voltage separate windings 400 V 4 6 poles motors Low speed High speed Once wiring is done check if the impeller is turning in the right direction I...

Page 6: ...eck pulleys alignment both motor and impeller pulleys along with belt tension IV 2 IV 2 Belt tension Please refer to the following table for belt s tension I pulleys axle spacing F belt deflection P f...

Page 7: ...rflow After settings make sure both locking screws are secured and the the pulleys alignment is fine V Troubleshooting Problem Main reasons How to solve Fan not running Main power off Thermal motor pr...

Page 8: ...PYROSTAR SMOKE FAN F400 120 MS MTG 001 Ind E 01 10 2019 Page 8 8 VI NOTES Date Observations...

Reviews: