FRP 4000 Fireplace Owner’s Manual

 

LTR20081045, Rev. A

Installation and Assembly

Natural Gas

The appliance and its individual shut off valve must be 

disconnected from the gas supply piping system during 

any pressure testing of the system at test pressures in 

excess of ½ psig (.5kPa).
This  appliance  must  be  isolated  from  the  gas  supply 

piping system by closing its individual manual shut off 

valve  during  any  pressure  testing  of  the  gas  supply 

piping system at test pressures equal to or less than /2 

psig (.5kPa).

Requirements

Always  check  the  rating  plate  to  make  sure  the  gas 

supply  you  are  hooking  up  to  is  the  gas  type  the 

 

fireplace is manufactured for.

Attempting  to  convert  a  Cal  Flame  fireplace  from 

one fuel to another may result in serious injury and 

void the warranty coverage .

Never  connect  the  fireplace  to  an  unregulated  gas 

supply.
The  installation  of  this  appliance  must  conform  with 

local  codes  or,  in  the  absence  of  local  codes,  to  the 

 

national fuel gas code, ANSI Z22.a-998. Installation 

in Canada must be in accordance with the standard CAN/

CGA-B49.2,  Propane  Installation  Code.  Natural  gas 

connection must be performed by a licensed contractor 

or local gas company representative.
Ensure that the service supplying the fireplace is fitted 

with a conveniently positioned shut off valve with easy 

access.

Your Cal Flame fireplace for use with natural gas comes 

equipped  with  its  own  regulator  which  MUST  NOT  be 

removed. If this regulator needs to be replaced, use only 

the type specified by Cal Flame for this appliance.

Remove the rear panel to gain access to the regulator 

and gas connection point.
Connect a suitable flex connector to the regulator.

Installation

Connect the incoming gas supply line to the on/off gas 

valve of the appliance. Make certain ALL gas connections 

are  tight,  turn  the  on/off  valve  at  the  unit  to  the  ‘on’ 

position and use soap and water to test for leaks. Gas 

will be released at the burner for this duration. DO NOT 

USE AN OPEN FLAME. 

An authorized gas appliance 

installer must provide this installation service.

 

High Elevation Installation

Your fireplace is approved for elevations up to 4500 feet 

in the US and Canada.
When  installing  this  appliance  at  an  elevation  above 

4500 feet in the US, it may be necessary to decrease 

the input rating by changing the existing burner orifice to 

a smaller size. Reduce the input by 4% for each ,000 

feet above sea level, unless the heating value of the gas 

has been reduced, in which case this general rule will 

not apply. To identify the proper orifice size, check with 

your local gas utility.
When installing this unit at an elevation above 4,500 feet 

in Canada check with your local authorities. Consult the 

local gas utility for assistance in determining the proper 

orifice for your location.

1.

2.

Summary of Contents for FPR 4000

Page 1: ...LTR20081045 Rev A 3 1 08...

Page 2: ...use Lloyds Material Supply L M S will not be held responsible for an improperly installed gas line Copyright 2008 Lloyds Material Supply Inc All rights reserved Duplication without written consent is...

Page 3: ...s well as solvents cleaning fluids and gasoline Do not block the vents located near the base of your fireplace as gas may build up in case of leak and cause serious damage Do not install or operate yo...

Page 4: ...ve the control compartment burner and circulation air passageways of the appliance be kept clean and free Any guard or other protective device removed for servicing the appliance must be replaced prio...

Page 5: ...precaution remember to always leak test your fireplace outdoors in a well ventilated area Never smoke or permit sources of ignition in the area while doing a leak test Do not use a flame such as a lig...

Page 6: ...Enclosures Ensure cylinder valves are always readily accessible A door on the enclosure to gain access to the cylinder valve is acceptable provided it is non locking and can be opened without the use...

Page 7: ...and restrain it to prevent it from tipping Connection Inspect the hose shipped with the unit for damage Never attempt to use damaged or plugged equipment See your local LP gas technician for repairs A...

Page 8: ...ned shut off valve with easy access Your Cal Flame fireplace for use with natural gas comes equipped with its own regulator which MUST NOT be removed If this regulator needs to be replaced use only th...

Page 9: ...nce Once the fireplace is in position level and safely hooked up to the proper fuel supply install the log grate over the plate burner Place the lava rock around the flat burner plate DO NOT place the...

Page 10: ...he burner FIRST You must have clear and easy access to the ON OFF valve AFTER the appliance is installed and connected to the gas supply in order to safely turn of the burner Make sure the burner is i...

Page 11: ...or gas suppliler Pushinthegascontrolknobandturncounterclockwise to the ON position 1 2 3 4 5 6 7 8 To light the burners turn the gas control that regulates gas flow to the burners Turn it from LOW to...

Page 12: ...ve buildup To clean the logs be sure the fire is out the gas supply is turned off and the logs are cool to the touch The soot can then be brushed of with a dry bristle brush or cloth Take care while c...

Page 13: ...y direct sunlight Damage caused as a result of failure to follow the operating instructions as defined in this owner s manual Misuse Lack of maintenance Accident Alterations Abuse Neglect The use of c...

Page 14: ...d below Fireplace model _______________________________________________________________________ Fireplace serial number _________________________________________________________________ Type of fuel c...

Reviews: