s.Cod.
= Access code for calibration menu.
This parameter should be
.
See NOTE 1 for programming.
222
A.CAL.
= Current calibration.
At this state, 20.000 mA current is applied to the
input of the device.
10.CA.
= 10V input calibration.
At this state, 10.000V is applied to the input of
the device.
1.CA.
= 1V input calibration.
At this state, 1.0000V is applied to the input of
the device.
For initializing calibration, first
then
keys are pressed together and held until ‘
'
message appears. See NOTE 3.
CAL
To initialize calibration, first
then
keys are pressed together and held until ‘
'
message appears. See NOTE 3.
CAL
To initialize calibration, first
then
keys are pressed together and held until ‘
'
message appears. See NOTE 3.
CAL
If increment key
is pressed and held 0.6 seconds, the value of the selected parameter changes rapidly. If
waited enough, the value increases 100 at each step. After 1 second following the release of the key, initial
condition is returned. The same procedure is valid for the decrement key.
For including decimal point first,
then,
keys are pressed and held together. And
then, by using
key decimal point can be
adjusted.
S.Cod.
d.C.sc.
Uo.sc.
D.Ca.s.
S.Cod.
a.CAL.
1.CA.
10.CA.
If
key is pressed and held for 5
seconds programming mode is entered
U.opt.
d.Cal.
SeCU.
d.pnt.
Cal.t.
l.sCl.
H.sCl.
l.inp.
H.inp.
CAL.t.=U.ýnP.
Evet
No
d.Cnf.
i.typ.
rate
Hold
dsp.C.
Unit
If first
and then
keys are
pressed together , measurement
unit appears. See
For programming.
Unit
parameter
If first
and then
keys are
pressed together, the maximum and the
minumum measurement values become
equal to the measured value at that time
and the message
appears on
display.
res.
Pressing this key the minumum
measured value up to that time
appears.
Pressing this key the maximum
measured value up to that time
appears
The minumum
measured value
The maximum
measured value
Measurement unit
870
1453
Bar.
&
Programming Mode
3/3
Running Mode
Measurement
value
1000
Res.
-E-05
EI141
SET
SET
SET
SET
SET
SET
SET
CAL.t.
= Calibration type.
Selectable as
or
.
If
is selected, input type is one the
four standard input types. If
is
selected, input types can be modified.
See NOTE 1 for modification.
S.inP
S.inp
U.inP
.
.
U.inP
i.typ.
= Input type.
Input type can be selected as 0-20mA,
4-20mA, 0-1V or 0-10V.
See NOTE 1 for programming.
RAtE
= Sampling rate.
Measurement is performed at each 200ms.
However,
for
rate, each measurement is displayed.
FASt
for
rate, the average of 4 successive
measurements is displayed.
SLo.1
for
rate,
for
rate,
SLo.2
SLo.3
the average of 8 successive
measurements is displayed.
the average of 16 successive
measurements is displayed.
See NOTE 1 for programming.
Hold
= Display holding parameter.
Selecting
, this parameter becomes
inactive.
Selecting
, always the minimum
measured value is displayed.
NonE
Lo.
Hi.
,
Selecting
always the maximum
measured value is displayed.
dSP.C.
= Display configuration.
Selectable as
or
. If
is
selected, process value appears. If
is selected, process value and then
measurement unit are displayed 4 and 2
seconds successively.
PrcS.
Pr.Un.
PrcS.
Pr.Un.
See NOTE 1 for programming.
Unit
= Measurement unit.
A constant, a message etc. to be displayed
can be entered. If a decimal point is desired,
it should be included before entering the
character.
d.Pnt.
= Decimal point.
Decimal point can be adjusted between
1. and 3. digits.
See NOTE 1 for programming.
L.SCL.
= Lower limit for the scale.
It can be adjusted between -1999 and
(
-100).
H.SCL
.
See NOTE 1 for programming.
H.SCL.
= Upper limit for scale.
It can be adjusted between (
+100)
and 4000.
L.SCL.
See NOTE 1 for programming.
SET
At this state, the reference voltage or
current that corresponds to
Parameter
is applied to the input.
To initialize calibration, first
then
keys are pressed together and held until ‘
'
message appears. See NOTE 2.
L.SCL.
CAL
SET
At this state, the reference voltage or
current that corresponds to
parameter is applied to the input.
To initialize calibration, first
then
keys are pressed together and held until
‘
' message appears. See NOTE 2.
H.SCL.
CAL
SET
SET
SET
s.Cod.
= Access code for safety menu.
This parameter should be
See NOTE 1 for programming.
333
.
d.C.Sc.
=
menu protection level
parameter.
= No menu is seen.
= Menu is seen but can not be programmed.
= Menu is seen and programming is possible.
ConF.
nonE
P. no
P.yES
.
See NOTE 1 for programming.
Uo.Sc.
=
U.oPt.
menu protection level
parameter.
= No menu is seen.
= Menu is seen but can not be programmed.
= Menu is seen and programming is possible.
See NOTE 1 for programming.
nonE
P. no
P.yES
.
d.Ca.S.
=
d.CAL.
menu protection level
parameter.
= No menu is seen.
= Menu is seen but can not be programmed.
= Menu is seen and programming is possible.
See NOTE 1 for programming.
nonE
P. no
P.yES.
CAL.
CAL.
C.end
C.end
s.err.
S.err.
C.err.
C.err.
The message on the left flashes approximately 5
seconds and calibration is completed.
The message on the left flashes approximately 5
seconds and calibration is completed.
If calibration is error free, the message
appears
. However,
if it is wrong, the message
appears for 1 seconds and the program
is shifted to the next step.
C.End
S.Err
.
for 1 seconds
If calibration is error free, the message
appears
. However,
if it is wrong, the message
appears for 1 seconds and the program
is shifted to the next step.
C.End
C.Err.
for 1 seconds
If the difference between the reference voltages or currents applied for the calibration of
and
is lower than one
half of the full scale, this error message appears on the display.
For example: Assume that the selected input type is 0-1V. In this case, if the difference
voltages
applied for calibration of
and
is lower than 0.5V, this error message appears.
H.inP.
L.inP.
H.inP.
L.inP.
between the reference
If the reference voltage or current applied to the input for calibration is too high or too low, this error message appears.
ERROR MESSAGES
CAL okey?
CAL okey?
CAL okey?
Yes
Yes
No
No
NOTE 2
NOTE 3
SET
For adjusting a selected parameter first press and hold
key. Then, by using
keys adjustment
can be made.
Parameter adjustment method
NOTE 1
Entering from programming mode to run mode:
If no key is pressed within 20 seconds during programming mode data is stored automatically and the run
mode is entered. Alternatively the same function occurs by pressing
key and holding for 5 seconds
SET