background image

COMMERCIAL IN CONFIDENCE

Page 9

2.  ACTIONS REQUIRED TO COMMUNICATE WITH THE

INSTRUMENTS

These versions of the instruments have ModBus functions codes 1,3,5,6 and 16 implemented. Note
that although function code 16 (write multiple registers) is recognised, this cannot deal with more than
a single 2 byte register write and will return an error if more registers are attempted. There is no facility
to read multiple registers, nor to read or write multiple bits.

2.1 

Notes

 

Un-implemented function codes do not yet return error code 01.

 

Function code 15 (read multiple registers) is not implemented.

2.2 

Implementation restrictions

A number of restrictions are made :

 

Multiple register reads are not implemented, since the opportunity to use them is very
limited and there is not sufficient memory to buffer long messages.

 

Multiple bit reads and writes are not implemented, since we do not have any consecutive
bits available to the user.

2.3 

Security Messages

To allow communications to safely manipulate the instrument a number of security messages
have been implemented.  CAL Controls see these as important safety features, which offer a
number of advantages, especially when configuring a safety critical application.

The messages to enter program mode only have to be sent once to access the Internal
parameters of the instrument and then any number of adjustments can be made. The advantage
this offers is that sending the enter program mode message, causes the push buttons on the
instrument to be locked out. This feature prevents potentially dangerous conditions arising
from simultaneous adjustment of the instrument locally whilst adjustments are being sent over
the communications link.

The messages to exit program mode causes the instrument to write back any internal
parameter changes to the NVram, and then use these settings. This means that any changes
made will not take effect until the instrument has received the exit program mode message. The
advantage this offers is that all adjustments take place at the same time. If for instance you are
configuring alarm functions you will not get false alarms due to setting the alarm mode before a
valid alarm set point has been programmed, also all PID terms are implemented together,
whereas separate adjustment of PID functions may cause greater control instability.

To prevent inadvertent changes a 

security byte 

 must be set immediately before any security message

is transmitted - this byte is automatically reset after each message.

Each security message is numbered 1 to 6, this number must be set into the 

security byte

 immediately

prior to the message, if the 

security byte 

does not match the security message number, the message

will be ignored and no response will be issued. Messages 1 to 4 are implemented but currently have no
direct use.

Note: The 9500 does not require the security byte messages to be sent to enter and exit
program mode, the messages not required are noted below.

The correct sequence to set new parameters into the instrument is as follows:

Summary of Contents for 3300P

Page 1: ...COMMERCIAL IN CONFIDENCE CAL 3300 9300 9400 9500 P MODBUS RTU COMMUNICATIONS GUIDE 7th September 2000 ISSUE 1 10 Doc 33034 Iss 002...

Page 2: ...lers would perform before transmitting the new data out over the bus to the instrument The CAL controllers assume that the values they receive have been checked against limits and are valid no further...

Page 3: ...ing and should not occur however they will be interpreted as if bit 2 was 0 Bit 4 is used to indicate reserved messages see the section Security Messages below Two types of bit value may exist those w...

Page 4: ...s linear Also note that while linear input is selected the display of values on the instrument is effected by the setting in DECP not Disp The instrument provides no error checking on values transmitt...

Page 5: ...wer priority than the displays recorded by the Display Byte If no bit is set the instrument is not in a ramp soak sequence If the unit has finished a ramp but no soak time is specified SOAK bit 2 will...

Page 6: ...ending on disp selection min LoSc max HiSc Ofst 2 0083 RW 3 6 Degrees 10 LIN normal inc dec see separate details for limits Band 2 0085 RW 3 6 Degrees 10 LIN normal inc dec min 0 1 max 25 of Sensor Ma...

Page 7: ...1 0190 RW 3 6 No scaling step by 1 min 0 max 100 PL 2 1 0191 RW 3 6 No scaling step by 1 min 0 max 100 SP2 A 1 0192 RW 3 6 0 none 1 dvhi 2 dvlo 3 band 4 fshi 5 fslo 6 cool 9500P 7 EOP SP2 b 1 0193 RW...

Page 8: ...with degC to decF if required if unit 1 Read hi 2 007A R 3 Read hi 10 LIN Read lo 2 007C R 3 Read lo 10 LIN Data Ct A 2 0432 R 3 CtA 25 Data Ct B 2 0434 R 3 CtB 25 Data Ct 1 2 0436 R 3 Ct1 25 Data Ct...

Page 9: ...sc Rev 3 1 03E5 RW 3 6 0 3d 1 3r Set 3 2 02E8 RW 3 6 Degrees 10 LIN step 0 1 min 0 0 max 2500 When LIN sensor selected max 9999 Hys 3 2 02EA RW 3 6 Hys3 10 LIN step 0 1 min 0 1 max 100 of HiSc Note Th...

Page 10: ...ing the enter program mode message causes the push buttons on the instrument to be locked out This feature prevents potentially dangerous conditions arising from simultaneous adjustment of the instrum...

Page 11: ...n 5 15 4 not used any value may be sent xx 5 not used any value may be sent xx 6 not used any value may be sent xx 7 CRC lo byte 8 CRC hi byte The security byte must be set to 5 prior to this message...

Page 12: ...is not a valid readable bit an error response code 2 invalid address is returned otherwise the following response is sent Byte No Meaning Value hex 1 Slave address xx 2 ModBus Function code read coil...

Page 13: ...Starting Address MSB xx 4 Starting Address LSB xx 5 Data MSB xx 6 Data LSB xx 7 CRC lo byte 8 CRC hi byte The normal response is the same as the message An error response code 2 illegal address will b...

Page 14: ...ceives full message correctly but cannot act on it An error response as detailed under each message heading is returned as follows Byte No Meaning Value 1 Slave address xx 2 Original ModBus Function c...

Page 15: ...erformed 7 Repeat from step 2 for the next byte of the message until all bytes have been processed 8 The final contents of the CRC register is the CRC value to use 9 When the CRC is placed in the mess...

Page 16: ...to read the setpoint the various sections of this code would normally be held in separate functions and would be optimised for better speed but this example shows the thought process involved note als...

Page 17: ...he reply if the Function code is 03 and the CRC is correct The CALController stores the Setpoint internally in 10th degree units so the value can be computed as setpoint reply 3 8 reply 4 10 or in a l...

Page 18: ...rrectly the whole sequence must be re started from message 1 1st Message byte 0 Slave address xx byte 1 Function code write register 06 hex always byte 2 Register Address high byte 03 hex always byte...

Page 19: ...ce for the values to take effect 1st Message byte 0 Slave address xx byte 1 Function code write register 06 hex always byte 2 Register Address high byte 03 hex always byte 3 Register Address low byte...

Page 20: ...D 2 Detailed later dependant on other functions CYC 2 ON OF 0 1 9 9 10 81 Seconds LEVEL 2 Function Values Limits SP1 P 0 100 Read only HAND OFF 1 100 PL1 100 0 PL2 100 0 SP2 A NONE DV HI DV LO BAND FS...

Page 21: ...LOSC SP LK So set point 1 is adjustable between the current high and low scale settings as long as the setpoint lock is off OFST INPT LIN CYC T ON OF 0 0 to 25 of sensor full scale DECP 0 1 to 81 0 0...

Page 22: ...DISP 1 0 to 250 0 1 0 to 199 9 If you change SP3 A at any time then the value of SET 3 defaults to zero There are a number of functions which when changed can have an effect on the values of other fun...

Page 23: ...ting C to F Here is a list of the functions that are effected by a C to F conversion and if a relative or absolute conversion is needed FUNCTION CONVERSION NOTES Set point 1 Absolute HISC Absolute LOS...

Page 24: ...99 9 400 0 LIN1 0 400 0 0 400 0 LIN2 25 400 25 0 400 0 LIN3 0 3000 0 0 999 9 LIN4 250 3000 199 9 999 9 LIN5 0 3000 0 0 999 9 LIN 9500 0 9999 N A N A TABLE 2 MIN MAX SENSOR FULL SCALE DEGREE F SENSOR M...

Page 25: ...0 0 400 0 LIN1 0 400 0 0 400 0 LIN2 0 400 0 0 400 0 LIN3 0 3000 0 0 999 9 LIN4 0 3000 0 0 999 9 LIN5 0 3000 0 0 999 9 LIN 9500 0 9999 N A N A TABLE 4 HI SC LO SC DEFAULT SETTINGS DEGREE F SENSOR DEFA...

Reviews: