5
TECHNICAL DATA SOLANO EASY PRO E
EASY PRO E-100
EASY PRO E-150
EASY PRO E-200
STEP
III
II
I
III
II
I
III
II
I
Power supply [V/Hz]
3N
400/50
1N
230/50
Fan power consumption [W]
130
95
80
195
115
95
250
165
165
Fan current consumption [A]
0,5
0,4
0,3
0,8
0,5
0,4
1,0
0,7
0,7
Air volume [m
3
/h]*
1300
950
800
2200
1500
1250
3000
1850
1850
Range [m]*
3,2
2,8
2,1
3,2
2,8
2,1
3,2
2,8
2,8
Acoustic
pressure
level
[dB(A)]** - 3 m
56,5
49
44
55
46
41
58
42
42
Acoustic
pressure
level
[dB(A)]** - 5 m
55,5
48
43
54
45
40
57
41
41
Acoustic
power
level
[dB(A)]***
71,5
64
59
70
61
56
73
57
57
Weight [kg]
15,1
19,6
24,6
IP
20
Max. operating temperature
[°C]
30
3N
400/50
STEP
III
II
I
III
II
I
III
II
I
Heating elements power
[kW]
5
9
12
Heating elements current
consumption [A]
8,5
13
17,3
Temperature increase (ΔT)
[°C]
20
22
24
20
26
32
19
29
29
1N
230/50
Heating elements power
[kW]
2
3
4
Heating elements current
consumption [A]
8,5
13
17,3
Temperature increase (ΔT)
[°C]
4
5
7
6
8
10
6
10
10
* according to ISO 27327-1;
** Acoustic pressure level has been measured in a 1500 m
3
space with a medium sound absorption coefficient, directional
factor: Q=2;
*** Acoustic power level according to ISO 27327-2;