10/52 User Instructions
CAIROX
15/12/2021
A [mm]
B [mm]
EASY PRO N/W/E-100
946
1000
EASY PRO N/W/E-150
1446
1500
EASY PRO N/W/E-200
1946
2000
8
INSTALLATION
Air curtains must be installed as close as possible to the door opening and cover:
-the entire width (applies to horizontal installation),
-full height (applies to vertical mounting).
CORRECT
WRONG
CORRECT
WRONG
9
MOUNTING
EASY PRO curtains are designed for horizontal mounting using 2 dedicated
brackets or 4 M8 threaded rods (max. threaded rods length 1 m). It is also
possible to install the curtains vertically using 2 brackets. During assembly, keep
the minimum distances from the partitions as shown in the figure below. In
addition, when installing the curtain, free access to the side of the device should
be taken into account (required minimum 100 mm). The electric curtain
(EASY PRO E) cannot be installed directly under the power socket. The device
must be leveled before starting work.
PIC. 8.1 Proper horizontal installation
PIC. 8.2 Proper vertical installation