FAST-Bi-1K5 – User’s Manual
20
The use of a Residual Current Device (RCD) shall be avoided because the
internal PFC can inject residual current when the PS is switched OFF.
The AC line input connector on the rear panel is a 7.62 mm terminal block plug
from Wurth-Elektronik (P/N: 691340400003) able of housing cables with 0.2-3.3 mm
2
of diameter (tightening torque required 0.56 [N·m]).
AC input cord is not provided with the PS. Refer to section 2.4.2 for
recommended cables and to
and
safe installation of the AC input cable.
Figure 4
: AC Power Line input without terminal block.
Figure 5
: AC Power Line input with terminal block.
Figure 6
: AC Power Line input with connector and cover unmounted.