background image

59 

23.7.   APPLIANCE START-UP 

The start-up must be performed by a qualified technician.  Make sure the installation is completed and the oil tank has 
been filled up.  The oil line must also have been purged.  

 

CAUTION: 

CLOSE THE BLOWER COMPARTMENT ACCESS PANEL BEFORE STARTING THE BURNER. 

23.8.   PROLONGED CLOSING 

A)  Cut off the electric circuit 
B)  Close the oil shut-off valve 

NOTE: THE SHUT-OFF VALVE MUST BE CLOSED WHEN THE APPLIANCE IS OUT OF SERVICE FOR A 

PROLONGED PERIOD OF TIME.  

24. TECHNICAL DATA 

24.1.  UH –MAX CADDY             

MODEL 

BURNER 

TYPE 

BTU 

INPUT 

NOZZLE 

FLOW 

HEAD 

STATIC 

PLATE 

PRESSURE 

AT THE PUMP 

H.P. FAN 

MOTOR 

TUBULATOR 

ADJUSTMENT 

AIR 

ADJUSTMENT 

EFFICIENCY 

UH–

MAX 

CADDY 

BECKETT AFG 

91,000 

0.65, 70

0

(DELAVAN) 

0.65 GAL US/H 

(2.46 L-H) 

F0 

--- 

100 PSI 

(690 kPa) 

1/2 

--- 

0/7 

85% 

UH–

MAX 

CADDY 

BECKETT AFG 

120,000 

0.65, 70

0

(DELAVAN) 

0.86 GAL US/H 

(3.26 L-H) 

F0 

--- 

175 PSI 

(1205 kPa) 

1/2 

--- 

1/6 

83% 

UH–

MAX 

CADDY 

RIELLO 40 F3 

91,000 

0.50, 70

0

(DELAVAN) 

0.60 GAL US/H 

(2.27 L-H) 

--- 

--- 

150 PSI 

(1035 kPa) 

1/2 

2.5 

87% 

UH–

MAX 

CADDY 

RIELLO 40 F3 

120,000 

0.65, 70

0

(DELAVAN) 

0.84 GAL US/H 

(3.18 L-H) 

--- 

--- 

165 PSI 

(1135 kPa) 

1/2 

2.5 

85% 

 
For any additional information, consult the rating plate on the left hand side of the appliance. 

25. MAINTENANCE  

At  the  beginning  of  heating  season,  have  the  complete  installation  inspected  by  a  qualified  service  man, 
especially the lighting system and the controls. 
 
 

25.1.  MAINTENANCE 

WARNING: TURN OFF ELECTRIC POWER SUPPLY BEFORE SERVICING THE UNIT. 

1.  The furnace, the burner and the flue pipe should be cleaned at least once a year. 
2.  The nozzle should be inspected and replaced if needed.  
3.  Handle the nozzle with care to avoid damaging its surface. 
4.  The electrodes should be adjusted as indicated in the burner manual. 
5.   Lubricate the burner motor bearings twice a year. (2 or 3 drops of SAE 20 non detergent lubricating oil). 
6.  The oil filter should be verified annually and replaced if needed. 

NOTE: THE UNIT’S MAINTENANCE, REPAIRS AND THE CLEANING OF 
THE OIL FILTER MUST BE DONE BY A QUALIFIED TECHNICIAN.  

Summary of Contents for PF01102

Page 1: ...available on the market We are confident that your furnace will provide years of comfort and safe operation Please keep this document Verified and tested for Canada and the United States by an accredited laboratory This manual is available for free download on the manufacturer s web site It is a copyrighted document Re sale is strictly prohibited The manufacturer may update this manual from time t...

Page 2: ...OTECTION 23 9 8 FLUE AND BAROMETRIC DRAFT CONTROL CONNECTION 24 9 9 ELECTRICAL CONNECTIONS 25 9 10 DAMPER 25 9 11 COMBUSTION AIR AND FRESH AIR INTAKE ADAPTER INSTALLATION OPTIONAL 25 9 12 HOT AIR PLENUM 26 9 13 PARALLEL INSTALLATION US ONLY 26 9 14 ELECTRICAL ELEMENT INSTALLATION OPTIONAL 29 9 14 1 INTRODUCTION 29 9 14 2 CONNECTING THE ELECTRICAL ELEMENT 29 10 THERMOSTAT INSTALLATION 30 10 1 WOOD ...

Page 3: ...IER 43 14 1 3 TEMPERATURE PROBE RTD 44 14 2 MAIN ERROR CODES POSSIBLE CAUSES AND SOLUTIONS 44 14 2 1 UNIT OVERHEAT 44 14 2 2 NO HEAT 45 14 2 3 COMMUNICATION ERROR 45 14 2 4 SMOKE SMELL 46 14 2 5 THE LCD TOUCH SCREEN DOES NOT LIGHTUP 46 14 2 6 AUXILIARY OVERRIDE 46 15 GENERAL ELECTRICAL DIAGRAM 47 16 ELECTRICAL DIAGRAM FOR PARALLEL FURNACE 48 17 ELECTRICAL DIAGRAM FOR ELECTRIC UNIT 49 WOOD OIL COMB...

Page 4: ...NANCE 59 25 1 MAINTENANCE 59 25 2 SERVICE 60 25 3 FILTERS 60 26 ELECTRICAL DIAGRAM BECKETT OIL UNIT 61 27 ELECTRICAL DIAGRAM RIELLO OIL UNIT 62 28 LINK BOARD OPTIONS CONNECTIONS 63 28 1 ELECTRICAL CONSUMPTION 63 28 2 OUTDOOR PROBE 63 28 3 HOT WATER 63 28 4 24V ADDITIONNAL EQUIPMENT 64 28 5 AIR CONDITIONNING DAMPER 64 28 6 HUMIDIFIER 64 28 7 HEAT PUMP 65 29 EXPLODED VIEW AND PART LIST 65 PSG LIMITE...

Page 5: ... applies to the lighting the ember bed and the minimum combustion air intake which was determined based on the use of good seasoned cordwood The Max Caddy furnace was tested and approved according to the CSA B415 1 10 Standard To optimize the efficiency of your furnace here is some advice that you should follow when installing or operating your Max Caddy Respect the local codes when in doubt consu...

Page 6: ... a significant impact in making heat circulation optimum 1 Values are as measured per CSA B415 1 10 except for the recommended heating area firebox volume maximum burn time and maximum input capacity Performances based on a fuel load prescribed by the standard at 10 lb ft and with moisture content between 18 and 28 2 Input value at 10lb ft fuel loading density and dry energy value of 8 600BTU lb 3...

Page 7: ...CFM Filter dimensions Width x Depth x Height included with optional blower assembly 16 in x 20 in x 1 in 406 mm x 508 mm x 25 mm Filter quantity 1 Particulate emission standard EPA CSA B415 1 10 USA standard safety UL 391 UL 1995 UL 727 Canadian standard safety CSA B366 1 CSA C22 2 no 236 CAN CSA B140 4 East west through the door you see the longitudinal sides of the logs north south through the d...

Page 8: ...mandatory exhaust pipe diameter 5 in Burner location of exhaust pipe Left or right Burner capacity at input 1 2 Beckett 91 000 BTU 27 kW 120 000 Btu 35 KW Burner orifice at input 1 2 Beckett 0 65 gal h 70 W 2 46 l h for both inputs Burner pump pressure at input 1 2 Beckett 100 PSI 175 PSI Burner capacity at input 1 2 Riello 91 000 BTU 27 kW 120 000 Btu 35 KW Burner orifice at input 1 2 Riello 0 50...

Page 9: ... DIRECT DRIVE THEORETICAL DEBIT TEMP VAR STATIC PRESSURE FILTER VENT MOT VIT CFM OF MIN MAX 1 INCH H2O MAX CADDY WITH BLOWER MAX CADDY ADD ON PARALLEL G 10 1 2 4 2 100 100 0 2 0 5 16 x 20 x 1 6 FURNACE DIMENSIONS WOOD AND WOOD ELECTRIC WOOD OIL ...

Page 10: ...10 ...

Page 11: ...T GLUE OR CHEMICAL PRODUCTS DO NOT BURN WASTES OR FLAMMABLE LIQUIDS SUCH AS GASOLINE NAPHTHA MOTOR OIL OR OTHER UNSUITABLE MATTERS DO NOT STORE WOOD IN THE VICINITY OF THE FURNACE RESPECT THE REQUIRED CLEARANCES BETWEEN COMBUSTIBLE MATERIALS AND THE SOURCE OF HEAT WARNING THE ASH DRAWER AND EXCHANGERS ACCESS PANEL GET VERY HOT DO NOT MANIPULATE WITH BARE HANDS 8 2 ODOUR FROM THE PAINT It is normal...

Page 12: ... intense fire will help keep the glass clean However in the event that your glass gets stained which should not occur under normal operating conditions you will have to clean it using a wet cloth and a fireplace glass cleaner Clean the glass ONLY when the unit has cooled down Do not use abrasive cleanser WARNING Avoid knocking or scratching the glass It could crack or break 8 6 1 GLASS SPECIFICATI...

Page 13: ...13 INSTALLATION AND OPERATION INSTRUCTIONS FOR MAX CADDY WOOD ONLY FURNACE COMBINED WOOD ELECTRIC OR PARALLEL ADD ON US ONLY PF01102 MAX CADDY FURNACE WOOD ONLY MAX CADDY FURNACE COMBINED WOOD ELECTRIC ...

Page 14: ...I National Fireplace Institute or in Canada by WETT Wood Energy Technical Training or in Quebec by APC Association des Professionnels du Chauffage Inspect the furnace to make sure that nothing has been damaged in the shipping Pull out the wiring kit and the instructions manual from the firebox of the furnace and the accessories from the flue pipe The following section contains installation instruc...

Page 15: ...d housing the holes on the side of the furnace Use the screws removed in the previous step to secure the housing to the furnace Once installed the link board must be connected to the system with the telecommunication wire of the power board The wire is located in the blower box To access it remove the air return box ...

Page 16: ...ng board is installed Once the telecommunication wire is out on the desired side run it along the back of the furnace and pass it through the grommet at the bottom of the link board housing Complete the connection by plugging the 8 strands telecommunication wire in the right connector shown by the arrow ...

Page 17: ...ce To do so open the cover of the power board housing Connect the power cord to the terminals N Neutral F Ground L Line Refer to wiring diagram for connecting components When done secure the wires with a BX connector not included and replace the blower box cover ...

Page 18: ...ink board with the touch screen using the telecommunication wire provided with the user manual Plug the telecommunication wire in connector labeled LCD and pull it out of the board housing through the top grommet Simply run the wire on the side of the furnace using the plastic ties supplied with the user manual Replace the access panel of the link board Note that the touch screen is removable if a...

Page 19: ... SUITABLE FOR 75 C not included STEP 1 Remove the two screws already secured to the furnace B on the side where you have chosen to install the link board Then secure the RTD support A using the two screws you previously removed STEP 2 Using a drill and a 9 32 bit drill a hole in the hot air plenum so that the RTD rod can pass into it STEP 3 and 4 Secure the RTD in place on the hot air plenum using...

Page 20: ...drilled holes in the front of the furnace using two screws as shown below Once installed install the chain linking the servomotor with the air inlet damper as shown above The chain must have a set of 1 8 When there is no call for heat the air inlet damper must be completely closed and the chain must be hooked to the servomotor at the 8 o clock position ...

Page 21: ...re outside air supply will be sufficient for proper combustion In airtight houses it might be necessary to install an outside air inlet See Section 9 11 COMBUSTION AIR AND FRESH AIR INTAKE ADAPTER INSTALLATION OPTIONAL The furnace must be positioned so that the connector is as short as possible Minimize the use of 90 o elbows The owner must ensure a proper installation to allow a safe operation of...

Page 22: ... 9 7 1 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS MINIMUM CLEARANCES A 24 610 mm G 8 204 mm B 18 458 mm H 1 1 2 38 1 mm C 6 153 mm I 6 153 mm D 1 26 mm J 24 610 mm E 72 1 829 mm F 24 610 mm 1 HEAT SHIELD ...

Page 23: ...the floor is made of combustible material a non combustible material floor protector is required see table below FLOOR PROTECTION CANADA USA A 18 457 mm From door opening 16 406 mm From door opening B N A USA only 8 203 mm From door opening C 8 203 mm N A Canada only D 8 203 mm Note 1 N A Canada only E N A USA only Note 2 Steel with a minimum thickness of 0 015 0 38 mm or ceramic tiles sealed toge...

Page 24: ...6 to 7 reducer must be installed at the flue outlet of the furnace If the draft exceeds 0 06 IN W C a barometric control must installed Never install a manual damper Secure the exhaust pipe to the flue adapter with three screws WOOD ONLY Diameter 6 WOOD OIL Reducer 7 to 6 Diameter 7 Unit oil Max Caddy pipe For a proper installation follow the advice below All the exhaust pipe joints must be secure...

Page 25: ...ate for all the situations When in doubt it is recommended to install a fresh air supply A fresh air supply may be needed if Solid fuel units present anomalies such as irregular draft smoke return bad combustion and or reversed draft whether there is combustion or not Existing solid fuel units such as a stove or fireplace release odours heat badly cause smoke returns or reversed draft whether ther...

Page 26: ...ONLY The installation of the Max Caddy with another furnace using the same ductwork is not allowed in Canada This type of installation is only allowed in the United States Ideally the maximum BTU input of the existing oil gas or electric furnace should be equal or higher than the maximum BTU input of the wood furnace It is mandatory to respect minimum clearances between the ductwork and combustibl...

Page 27: ...ces o The necessary adjustments are made to the furnace or hot air ducts to maintain a static pressure of between 0 20 and 0 50 IN W C o A backflow damper must be installed to prevent air return in one or the other of the two furnaces and to ensure that hot air will flow into the house and will not return through the plenum of the other furnace Depending on your system configuration it is possible...

Page 28: ...llation is shown below The existing furnace s thermostat must be connected to the Rh and Aux terminals of the link board on the Max Caddy furnace Those two wires must come from the R and W terminals of the existing furnace s thermostat so the link board receives the heat signal When a heat signal from the existing furnace s thermostat will be sent the Max Caddy furnace will shut itself down and an...

Page 29: ...0 amps 2 120 240 5 x 5 kW WOOD 2 100 100 180 000 5 15 amps 14 120 N A Electrical connections must conform to the wiring diagram supplied with the option The electrical element must be connected to the power board See Section 17 ELECTRICAL DIAGRAM FOR ELECTRIC UNIT For security reasons the electrical element has a manual reset thermostatic sensor that is located inside the electrical unit If the te...

Page 30: ...ostat Refer to the electrical diagram Once wired to the furnace it is possible to verify the signals coming from the wall thermostat Simply go on the touch screen main menu under the TROUBLESHOOT LINK menu and going to page 1 as shown below When a signal is sent from the thermostat the circle corresponding to the signal should appear green 10 1 1 COMBINATION WOOD ELECTRIC OR WOOD OIL FURNACE Only ...

Page 31: ...r will start immediately at the programmed speed For the air conditioning damper wiring see Section 28 LINK BOARD OPTIONS CONNECTIONS The capacity and characteristics of the air conditioning unit that has been tested with the MAX Caddy are stated below The use of another brand with similar capacity and characteristics is adequate Condenser brand Goodman GSX13048 Capacity 4 ton Coil type Type A CAU...

Page 32: ...1 CONFIGURATION AND OPERATING INSTRUCTIONS 11 1 CONTROLS SYSTEM The Max Caddy has a sophisticated electronic control This system is more versatile All connections are made from the control panel Terminal blocks are provided for all components and options Before you configure your system and learn how to operate it make sure that your wall thermostat is wired correctly to your furnace that the temp...

Page 33: ...OFF 11 3 1 ICONS DESCRIPTION Icons Description Icons Description Wood heating Green Heating mode Yellow Auxiliary heating mode Electrical Element Green Unit on Yellow On hold Heat pump Green Unit on Yellow On hold Oil unit Green Unit on Yellow On hold Settings Displayed when an auxiliary heat source has been selected Temperature in the hot air plenum Distribution blower is in circulation mode CIRC...

Page 34: ...ional time KIP Time and recheck the temperature in the plenum If the temperature has not reached the KIP the auxiliary heating will start The icon Wood will turn yellow and the auxiliary heat icon will turn green For the electrical element and or the oil unit the fan starts as soon as the thermostat asks for heat In other words for safety reasons the fan does not wait for the hot air plenum to rea...

Page 35: ... heat pump when it is too cold and the coefficient of performance becomes too low Electrical element should be prioritize during configuration the outdoor temperature probe When the temperature probe is functioning the ECO mode will show on the main page 11 4 4 1 BI ENERGY FUNCTION The bi energy function is used when a local utility company Hydro Quebec for instance offers a bi energy program unde...

Page 36: ...sing the central processing unit we have created 6 functional speeds Refer to the following table for the various speed configurations Functional Speed Corresponding data CFM Static pressure 1 Blower speed 1 using 98V 600 0 2 H2O 2 Blower speed 1 using 115V 760 0 2 H2O 3 Blower speed 2 using 98V 840 0 2 H2O 4 Blower speed 2 using 115V 950 0 2 H2O 5 Blower speed 3 using 115V 1150 0 2 H2O 6 Blower s...

Page 37: ...fter the blower increments its speed until it reaches the best efficiency point BEP determined by the manufacturer If the temperature inside the hot air plenum exceeds the limit determined by the manufacturer the blower automatically selects the maximal speed and the motorized damper closes in order to slow down combustion When the temperature returns to a safe level the blower speed gradually ret...

Page 38: ...he furnace lower the kindled pieces of wood and place them at the center of the combustion chamber before adding new logs 2 Do not overload Air must circulate freely in the upper part of the combustion chamber in order to obtain an efficient operation of the appliance secondary burn Please note that a small hot fire will produce much less residues than a large smouldering one IMPORTANT DURING THE ...

Page 39: ...ROLONGED POWER FAILURE In case of prolonged power failure over 10 minutes to reduce the risk of overheating it is recommended to heat moderately and to open the furnace filter compartment in order to facilitate air circulation by natural gravity around the firebox of the Max Caddy wood furnace 11 8 7 CHIMNEY FIRES This might occur when the fire gets extremely hot Burning cardboard branches or smal...

Page 40: ...t require tools just remove the decorative facing by just lifting it remove the wing nut that keeps the hinged access panel closed See pictures below Before cleaning the three exchanger pipes move the upper vermiculite baffle board of the combustion chamber forward see drawing on next page Using the scraper clean the three exchanger pipes The accumulated dirt in the lateral exchangers will fall in...

Page 41: ...sure that the smoke and the combustion gases are not transported into the air ducting system 12 4 BLOWER MOTOR MAINTENANCE Periodic cleaning of the fan housing as well as fan and fan blades using a vacuum cleaner is necessary in order not to affect performance and cause overheating of the latter DO NOT OVERLUBRICATE 12 5 FILTERS Never use the furnace without air filters To function as expected con...

Page 42: ...n order to maintain a good control of the combustion for maximum efficiency and security To replace your door gasket remove the old gasket and adhesive Clean the surface thoroughly apply a high temp adhesive silicone 650 o F sold for that particular use and put the new gasket onto the door Wait for at least 4 hours before lighting your furnace 14 TROUBLESHOOTING When you have issues with your furn...

Page 43: ...UBLESHOOT LINK then go to page 5 When the fan is on the selected speed is black 14 1 2 AIR DAMPER HOT WATER AND HUMIDIFIER To check the status of the air damper hot water or humidifier go to the main menu under TROUBLESHOOT LINK then go to page 3 When the furnace is in wood heating the damper is open The green square next to DAMPER should be on the left closed circuit When another heating mode is ...

Page 44: ...s section contains main error codes possible causes and many suggestions to guide you in resolving them To go back to the main menu press the RESET button NOTE IF AFTER PERFORMING ALL THE POSSIBLE SOLUTIONS MENTIONED IN THE FOLLOWING SECTION YOU ARE STILL EXPERIENCING PROBLEMS WITH YOUR FURNACE CALL YOUR LOCAL DEALER OR AFTER SALE SERVICE NOTE IF YOU NEED TO CONTACT YOUR DEALER OR TECHNICAL SUPPOR...

Page 45: ...ure in the plenum is too high Make sure your air distribution system is well balanced and that the filter is not dirty or clogged Ensure that returns side vents are not blocked 14 2 2 NO HEAT This message appears When the wood furnace failed to raise the temperature in the plenum enough to reach the KIP or When the temperature does not reach 100 F in the plenum in less than five minutes for auxili...

Page 46: ...as the air naturally flows from a high pressure point to a low pressure point a larger negative pressure can draw smoke from the inside of the furnace into the room The furnace can also be affected by other mechanical ventilation systems causing the same effect as mentioned previously Using a fresh air intake will prevent negative pressure Also make sure the recommended maintenance schedule has be...

Page 47: ...47 15 GENERAL ELECTRICAL DIAGRAM ...

Page 48: ...48 16 ELECTRICAL DIAGRAM FOR PARALLEL FURNACE ...

Page 49: ...49 17 ELECTRICAL DIAGRAM FOR ELECTRIC UNIT ...

Page 50: ...n of the Max Caddy wood oil furnace you have to assemble the blower assembly PA08566 sold separately The assembly instructions are in the instruction manual supplied with the blower assembly kit You must also assemble the oil assembly kit The assembly instructions are in the instruction manual supplied with the oil assembly kit PA08512 or PA08513 sold separately ...

Page 51: ...T THE BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN THE APPLIANCE IS FULL OF VAPOR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT DO NOT BURN WASTE OR PAPER IN THE APPLIANCE DO NOT LEAVE PAPER OR ANY COMBUSTIBLE MATERIAL AROUND THE APPLIANCE WARNING INSTALL THE NOZZLE ADJUST THE ELECTRODES ADJUST PRESSION NOTE IF A PROBLEM RESULTS FROM IMPROPER INSTALLATION NO PRODUCT WARRANTY WILL BE VALID DO NOT TRY T...

Page 52: ...he damper is to adjust the draft in the evacuation pipe of the oil burning unit to the recommended level Since the evacuation pipe of the oil burning unit is connected on the evacuation pipe of the wood burning furnace the minimum draft to be respected is 0 04 IN W C in the evacuation pipe of the wood burning side at all times In fact a barometric damper that would be opened too wide could cause a...

Page 53: ... its heat transfer tube and can be wired to shut off the oil burner It requires manual resetting 22 1 UNIT LOCATION See Section 9 6 UNIT LOCATION for more details regarding the unit location 22 2 PARALLEL INSTALLATION See Section 9 13 PARALLEL INSTALLATION 22 3 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS N B This appliance must be installed in conformity with the instructions on the certification ...

Page 54: ...G PIPE AND MANUAL DAMPER The pipe connecting the furnace to the chimney must be as short and as straight as possible If a deviation is required the use of 45 o elbows is highly recommended for a better evacuation of the smoke in the chimney of the wood burning furnace The barometric damper provided with the appliance must be installed on the oil unit evacuation pipe approximately 24 from the flue ...

Page 55: ...55 22 7 DIFFERENT INSTALLATION ...

Page 56: ...ing the control will then switch to the RECYCLE mode and cut the fuel supply to the burner for 60 seconds After this delay the control goes back to IGNITION mode If the flame goes out 3 times in a row the control will switch to the LOCKOUT mode to prevent a continuous cycling of the ignition process which would cause a premature soot up of the combustion chamber and smoke pipe To deactivate the LO...

Page 57: ...LOSE THE DOOR AND THE AIR INTAKE S OF THE WOOD BURNING FURNACE C LIGHT THE BURNER FOR AT LEAST 10 TO 15 MINUTES D OVER THE FIRE DRAFT 0 01 TO 0 02 IN W C THE DRAFT OVER THE FIRE MUST BE MEASURED BY THE SCEALED CAP OF THE VISION TUBE S PULSATION TRAP E SMOKE TEST BETWEEN 0 AND 1 ON THE SHELL BACHARACH SCALE TRACES F DRAFT IN THE CHIMNEY 0 02 IN W C G PERCENTAGE OF EXCESS AIR 20 TO 40 12 CO2 5 O2 H ...

Page 58: ...E OIL BURNER S INSTRUCTIONS MANUAL FOR DETAILS ON THE PUMP 3 FOR ELECTRODES SETTING SEE THE OIL BURNER S MANUAL 4 FOR THE START UP AND ADJUSTMENT OF THE BURNER SEE OIL BURNER S INSTRUCTION MANUAL 5 THE BURNER WILL PROVIDE YEARS OF EFFICIENT OPERATION IF IT IS PROFESSIONALLY INSTALLED AND MAINTAINED BY A QUALIFIED SERVICE TECHNICIAN IF AT ANY TIME THE BURNER DOES NOT APPEAR TO BE OPERATING PROPERLY...

Page 59: ...F3 91 000 0 50 70 0 W DELAVAN 0 60 GAL US H 2 27 L H 150 PSI 1035 kPa 1 2 1 2 5 87 UH MAX CADDY RIELLO 40 F3 120 000 0 65 70 0 W DELAVAN 0 84 GAL US H 3 18 L H 165 PSI 1135 kPa 1 2 1 2 5 85 For any additional information consult the rating plate on the left hand side of the appliance 25 MAINTENANCE At the beginning of heating season have the complete installation inspected by a qualified service m...

Page 60: ...______________ Service telephone no Day _________________________ Night _____________________________ Dealer s name and address ____________________________________________________________ TEST REPORT CO2 _____________ Temp at stack ___________________ Draft at stack _______________IN W C Nozzle output _______________________ GPH Smoke colour ______________________________ Inspected by ___________...

Page 61: ...61 26 ELECTRICAL DIAGRAM BECKETT OIL UNIT ...

Page 62: ...62 27 ELECTRICAL DIAGRAM RIELLO OIL UNIT ...

Page 63: ...is possible to find on the market options having higher or lower electrical consumption than those shown in the table below In the event that the combined electrical consumption of the installed options is higher than 1 66 amps contact our technical support for further information WARNING INCORRECT WIRING CAN DAMAGE THE LINK BOARD Option Approximate consumption mA Additional 24V equipment 500 Air ...

Page 64: ...64 28 4 24V ADDITIONNAL EQUIPMENT 28 5 AIR CONDITIONNING DAMPER 28 6 HUMIDIFIER ...

Page 65: ...65 28 7 HEAT PUMP 29 EXPLODED VIEW AND PART LIST ...

Page 66: ...66 ...

Page 67: ...67 ...

Page 68: ...68 ...

Page 69: ...69 ...

Page 70: ...70 ...

Page 71: ...71 ...

Page 72: ...72 ...

Page 73: ...342 REAR COVER GASKET 1 16 PL56480 REAR CABINET COVER 1 17 PL56411 RIGHT ACCESS COVER FOR ELECTRICAL ELEMENT 1 18 PL56410 RIGHT PANEL FOR THE ELECTRICAL ELEMENT OPTION 1 19 SE56407 RIGHT AIR JACKET PANEL WITH ISULATION 1 20 SE56414 RIGHT PANEL WITH INSULATION WATER LOOP OPTION 1 21 30153 METAL SCREW 8 X 1 2 PAN SQUARE TEK BLACK SELF DRILLING 2 22 SE44096 100 OHM RTD PROBE 38 WIRE WITH CONNECTOR 1 ...

Page 74: ...UNCTION WIRE MAIN CONTROL BOARD TO LCD 1 64 SE56777 MAX CADDY TOUCH SCREEN BOARD LCD WITH HOUSING 1 65 PL48251 PC BOARD HOUSING COVER 1 66 30412 BLACK UNIVERSAL SNAP IN BUSHING 1 67 PL48250 PC BOARD HOUSING 1 68 30408 ELECTRONIC BOARD CLIP 9 69 SE56823 POWER BOARD HOUSING ASSEMBLY 1 70 PL56823 LIMIT MAIN CONTROL BOARD WITH PROGRAM 1 71 30154 BLACK SCREW 10 X 5 8 ROBERTSON TYPE A 4 72 49068 ADAPTER...

Page 75: ...COVER ELECTRICAL UNIT 1 107 60202 SEQUENCER 15S X 441 1 108 60207 ALUMINUM LUG 14 6 STUD 17 64 1 109 60194 FUSE HOLDER 30A 600V PROTECTION 1 110 60237 THERMODISC L170 MANUAL RESET FOR ELECTRICAL ELEMENT 1 111 60365 60 COMMUNICATION WIRE 8 CONDUCTOR 1 112 44182 TRIAC BOARD 1 113 60368 TRANSFORMER 120 V 24 V 40 VA 1 114 44136 FUSE 12A 250V 1 4 DIA X 1 1 4 L 1 115 44137 FUSE 1A 250V 1 4 DIA X 1 1 4 L...

Page 76: ...CK DRAWER HANDLE 3 25 32 1 134 PA08566 BLOWER ASSEMBLY 1 135 PA08500 TOP AIR RETURN PLENUM KIT 1 136 SE45833 MAX CADDY INSTRUCTION MANUAL KIT 1 137 AC05961 PSG GREY 424C SPRAY PAINT 1 137 AC05963 METALLIC BLACK STOVE PAINT 85 g 3oz AEROSOL 1 138 PL48170 HEAT EXCHANGER SCRAPER 1 139 PL48171 ASH SHOVEL 1 140 PL48173 POKER 1 ...

Page 77: ...to standards Given the importance of the installation PSG recommends that it is carried out by a professional certified in the Building Code so that the furnace delivers its full potential This is why PSG offers an additional warranty that covers the cost of labor if your furnace has been purchased through an authorized PSG dealer If you want to enjoy the best service on the market and substantial...

Page 78: ...fter inspection and investigation of the defect The manufacturer may at its discretion fully discharge all obligations with respect to this warranty by refunding the wholesale price of any warranted but defective parts The manufacturer shall in no event be responsible for any special indirect consequential damages of any nature which are in excess of the original purchase price of the product A on...

Page 79: ... part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after inspection and investigation of the defect The manufacturer may at its discretion fully discharge all obligations with respect to this warranty by refunding the wholesale price of any warranted but defective par...

Reviews: