background image

27

  IM-BW4-5-02

[240013014 Rev. B [12/15/2020]

Annually

Recommend flue passages, combustion 

chamber area (target wall, fire door insulation, 

durablanket), burner adjustment, control operation, and 

boiler seals (fire door gasket or silicone seal, cast iron 

sectional seals, flue collector) be checked once each year 

by trained Service Technician. 

Before The Start Of Each Heating Season

 

(or when 

system has been shut down for extended periods of time) 

recheck whole system for water, oil, and vent piping leaks. 

Replace or patch any leaks or faulty seals.

Vent Pipe:

 Visually inspect entire venting system once a 

month for any signs of leakage, deterioration, or soot build 

up. If vent pipe shows any signs of leaking or deterioration, 

replace it immediately. If it shows any signs of soot 

build up, clean vent pipe and have burner settings and 

combustion checked by trained Service Technician.

Safety Relief Valve:

 Valve should open automatically 

when system pressure exceeds pressure rating (usually 30 

psi) of safety relief valve. Should valve ever fail to open 

under this condition, shut down the system. Drain system 

until system pressure is reduced below safety relief valve 

pressure rating. Contact Service Technician to replace the 

valve and inspect heating system to determine cause, may 

indicate equipment malfunction. Safety relief valve should 

be tested monthly during heating season. Prior to testing, 

make certain discharge pipe is properly connected to valve 

outlet and arranged so as to contain and safely dispose of 

boiler discharge. Hold trip lever fully open for at least five 

seconds in order to flush free any sediment that may lodge 

on valve seat. Permit valve to snap shut. Refer to valve 

manufacturer’s instructions packaged for more details.

 

Conventional Expansion Tank

:

 Tank may become 

water logged or may receive excess air. Frequent automatic 

opening of safety relief valve indicates water logging. High 

boiler temperature accompanied by unusually low radiation 

unit temperature (and “knocking” noises) indicates excess 

air in the tank. To correct either condition, close valve 

between boiler and tank. Drain tank until empty. Check all 

tank plugs and fittings, tighten as necessary. Open valve 

between boiler and tank. Water will rise to normal height in 

tank if system has automatic fill valve, otherwise manually 

refill system. 

Diaphragm Expansion Tank

:

 Tank may become 

water logged. Frequent automatic opening of safety relief 

valve indicates water logging. High boiler temperature 

accompanied by unusually low radiation unit temperature 

(and “knocking” noises) indicates excess air in the tank. To 

correct this condition, replace diaphragm expansion tank.

Water System:

 

If system is to remain out of service 

during freezing weather, drain it completely (water left in 

system may freeze and will crack pipes and/or boiler).

Tankless Coil (Or Cover Plate) Gasket:

 

Gasket 

should be checked at least twice year for leakage, replace if 

necessary. If gasket is replaced, make sure that when coil 

plate (or cover plate) is reattached, ten nuts are torqued 

in alternating pattern to insure equal force is applied to 

entire gasket creating good seal. Nuts should be torqued so 

gasket does not squeeze out from behind the plate.

Oil Burner:

 Oil burner maintenance is listed in this 

manual under “Operating The Boiler”.

Never burn garbage or paper in the unit, never leave 

combustible material around it.

MAINTENANCE

Oil Burner Maintenance

:

 Perform following 

preventative maintenance annually, preferably prior to 

heating season. Refer to burner manual provided with 

boiler.

1. 

Fuel Filter

  Replace to prevent contaminated fuel from 

reaching nozzle. Partially blocked fuel filter can cause 

premature failure of fuel pump.

2. 

Fuel Pump Unit 

 Replace pump screen and clean pump 

unit to maintain fuel delivery to nozzle.

3. 

Ignition Electrodes

  Clean and adjust per 

manufacturer’s recommendations, to maintain reliable 

ignition of oil.

4. 

Nozzle

  Replace to maintain safe and reliable 

combustion efficiency. Replace with nozzle as required 

in charts located in this manual.

5. 

Fan and Blower Housing

  Must be kept clean, free of 

dirt, lint and oil to maintain proper amount of air fuel 

requires to burn.

6. 

Check Final Burner Adjustments.

If any component parts must be replaced, always use parts 

recommended by burner manufacturer.

 WARNING

Burn, scald hazard.  Some maintenance tasks 

require draining the boiler. Verify boiler is cool and 

at zero pressure before draining.  Verify boiler is 

appropriately drained before removing relief valve, 

control well, tankless coil etc. Failure to follow these 

instructions could result in death or serious injury.

!

  

Summary of Contents for BW4BAH000112

Page 1: ...AH000112 BW5BAH000112 BW5RAH000112 BW4BAH000175 BW4RAH000175 BW5BAH000175 BW5RAH000175 Models Series D BW4BAH000217 BW4RAH000217 BW5BAH000217 BW5RAH000217 CAC BDP 7310 WEST MORRIS ST INDIANAPOLIS IN 4...

Page 2: ...nts portion of remaining heat that can be applied to heat radiation or terminal units finned tube baseboard cast iron radiators radiant floor etc Difference between Heating Capacity and Net AHRI Ratin...

Page 3: ...B R AH000217ADAA 1 55 217 189 164 86 0 5 13 7 21 6 11 Mbh 1 000 BTU per hour BTU British Thermal Unit Heating Capacity based on 13 1 CO2 with a 0 02 w c draft over fire and a 1 smoke or less Testing w...

Page 4: ...ing needs can scald and cause permanent injury Children elderly and infirm or physically handicapped persons are more likely to be permanently injured by hot water Never leave them unattended in batht...

Page 5: ...mance and life expectancy can be hindered by overfilling the boiler Recommend initial fill pressure of 10 12 psig For higher fill pressures expansion tank s air charge will need to be increased to mat...

Page 6: ...replacement of any parts that may normally require attention Install boilers at least 6 from combustible material on left side rear and above and at least 24 on right side and front Allow at least 24...

Page 7: ...ION FROM RADIATION CIRCULATING PUMP IN RETURN LINE OR AFTER THE EXPANSION TANK SHUT OFF VALVE OIL FILTER OIL LINES FOUNDATIONS TO OUTSIDE LINES TO OTHER APPLIANCES SERVICE LINE OVERCURRENT PROTECTED S...

Page 8: ...gs communicating directly with additional room s of sufficient volume so the combined volume of all spaces meets the criteria for unconfined space Total input of all combustion equipment installed in...

Page 9: ...all equipment in the enclosure 3 When communicating with outdoors through horizontal ducts each opening shall have minimum free area of one square inch per 2 000 Btu per hour of total input rating of...

Page 10: ...elbow provided with boiler See Figures 6a and 6b A Install safety relief valve with spindle in vertical position B Do not install shutoff valve between boiler and safety relief valve C Install dischar...

Page 11: ...o prevent this condensation in boiler and venting is 120 F Boiler used in heating system where design water temperatures below 140 F are desired e g radiant floor heating a 3 way or 4 way mixing valve...

Page 12: ...RRANGED FOR POWER PURGING AIR OUT OF THE SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 Figure 7 Bypass Piping Arrangement Diagram SYSTEM PIPING Adjust two thro...

Page 13: ...IPING PUMPS AWAY FROM EXPANSION TANK NOTE CIRCULATORCANALSOBEINSTALLED ON RETURN PIPING PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM...

Page 14: ...ON SUPPLY PIPING PUMPS AWAY FROM EXPANSION TANK PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 SYSTEM PIPING Figure...

Page 15: ...E BOILER CIRCULATOR ON SUPPLY PIPING PUMPS AWAY FROM EXPANSION TANK PER THIS MANUAL USE OPTION 2 IN FILLING THE SYSTEM WITH WATER THIS PIPING ARRANGEMENT CAN BE USED WITH ZONE VALVES OR ZONE CIRCULATO...

Page 16: ...t draws not continuous flow NOTICE Do not use tankless coil if your water is excessively hard with lime or other deposits which will accumulate inside the coil When using tankless coil boiler is confi...

Page 17: ...increase fuel consumption Tankless coil performance will fall as concentration of antifreeze is increased Refer to boiler and piping water volumes tables BOILER WATER VOLUMES Number of Boiler Section...

Page 18: ...d boilers for connections to vents or chimneys vent installations shall be in accordance with applicable provisions of NFPA 31 Standard for the Installation of Oil Burning Equipment latest edition and...

Page 19: ...T 1 4 INCH PER FOOT OF HORIZONTAL RUN MUST BE AT LEAST 4 INCHES THICK AND BE TIGHT TIGHT CLEAN OUT DOOR SEALED IN THIMBLE TIGHT SMOOTH CORRECTLY SIZED Minimum Height Must be 3 FT higher than highest p...

Page 20: ...comply with the latest revision of the National Electrical Code any other national state or local codes or regulations Connect 120 volt electrical supply to L1 and L2 terminals on limit and two therm...

Page 21: ...Control with Riello F5 Burner ELECTRICAL WIRING When low limit is used set ELL Parameter on L7248 Honeywell control to ON Boilers factory equipped with tankless coil are factory set to ON When low lim...

Page 22: ...lve When power purging drain valve runs air free close isolation valve or zone valve Repeat this procedure for remaining heating zones C Once all zones are filled with water and purged of air close po...

Page 23: ...a lack of combustion air burner flame will be dark orange and formation of soot will occur in heating unit In buildings of conventional frame brick or stone construction that do not have utility rooms...

Page 24: ...5 BAH000217 AFG50MDASN 1 55 2 1 2 1 25 60 B 155 NO V1 2 10 2 2 3 4 RIELLO 40F5 BOILER MODEL BURNER MODEL INPUT RATE gph INSERTION DEPTH DELAVAN OIL NOZZLE PUMP PRESSURE psi TURBULATOR SETTING AIR SHU...

Page 25: ...ero and four are scale indicators only From left to right first line is 4 and last line 0 On some models scale indicators are 0 and 3 Figure 15 Burner Adjustments and Settings Figure 16 Riello Electro...

Page 26: ...floor on inside wall Locate thermostat to sense average room temperature avoid the following THERMOSTAT LOCATIONS TO AVOID DEAD SPOTS HOT SPOTS COLD SPOTS Behind doors Concealed pipes Concealed pipes...

Page 27: ...boiler and tank Water will rise to normal height in tank if system has automatic fill valve otherwise manually refill system Diaphragm Expansion Tank Tank may become water logged Frequent automatic op...

Page 28: ...ly vacuum soot accumulations from combustion chamber area take care to not damage any of refractory or blanket insulation To gain access to combustion chamber first check that shut off valve on fuel o...

Page 29: ...5 Install burner drawer assembly make sure head location and size if applicable are per manufacturer s recommendations If burner being used has damaged head replace head with same head recommended fo...

Page 30: ...o instructions Radiators not heating Open radiator vents to excess air Check flow control valve if used It may be in closed position Circulating pump not running Check over current protection Check re...

Page 31: ...31 IM BW4 5 02 240013014 Rev B 12 15 2020 Taco 007 Pump Curve PUMP CURVE 007...

Page 32: ...l energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that r...

Reviews: