C-TEC AlarmSense CFP702-2 Installation & Maintenance Manual Download Page 21

1.3 System faults

System faults are unique in that they do not automatically clear when rectified. Three different types of system 
fault can occur; watchdog fault, site memory corruption fault or PLL (phase lock loop) fault.

  To find out which type of system fault has occurred:

1.  Remove the panel’s lid using the Torx key provided and press the ACCESS LEVEL THREE FUNCTIONS    
 

button on the Main Control PCB to gain access to the panel’s engineer functions (see below). Note: If   

 

pressing the ACCESS LEVEL THREE FUNCTIONS button (or any other button) does not cause any change  

 

in state, the Main Control PCB is faulty and must be replaced.

2.  Continue pressing the ACCESS LEVEL THREE FUNCTIONS button until the SYSTEM FAULT light pulses.

 

If there is a Watchdog Fault, Zone 1’s Fault light will be lit.

 

If there is a Site Memory Corruption Fault, Zone 2’s Fault light will be lit.

 

If there is a PLL Fault, Zone 3’s Fault light will be lit.

 

For a detailed description of what each fault is, and suggested action on how to rectify it, see below:

  Watchdog Fault

This type of system fault occurs when the panel’s microprocessor has failed to operate correctly. In this case the  
panel’s ‘Watchdog’ circuit will attempt to bring the microprocessor back under control and return all outputs 
and indicators to their normal state. If the watchdog cannot restart the microprocessor then the General Fault 
and System Fault lights will be cycle continuously, plus the panel’s internal sounder will activate.

Suggested action:

Press the panel’s RESET button and, if still in access level 3, the ESCAPE ACCESS button. This should clear the 
fault. If the fault persists, the Main Control PCB is faulty and must be replaced.

  Site Memory Corruption Fault

This type of system fault occurs when site specific data held in the panel’s microprocessor is found to be corrupt.

Suggested action:

1.  Check all the site specific data (delays, disablements, etc) at user and engineering levels. The System Set- 
 

Up Data Chart in the User Manual / Log Book (page 13) includes relevant set-up information.

2.  If errors are found, reprogram the panel accordingly to clear the corruption.

3.  If no errors are found, temporarily change some data, e.g. disable zone 1, exit user mode and then re- 
 

enable zone 1 to return to the original settings. This should clear the fault. If the fault persists, the    

 

memory is damaged and the Main Control PCB must be replaced.

  PLL Fault

This type of system fault occurs as a result of a momentary disturbance in the panel’s microprocessor.

Suggested action:
Resetting the panel should clear the fault. If the fault persists, the Main Control PCB is faulty and must be 
replaced.

LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL

INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 21 of 24

DELAYS

TEST

NONLATCHING

COINCIDENCE

ACCESS

LEVEL THREE

FUNCTIONS

OPEN

CIRCUIT

SHORT

CIRCUIT

REPEATER

FAULT

SYSTEM

FAULT

SW8

CFP ALARMSENSE PANEL CONTROLS

HEAD

OUT

SOUNDER

STATUS

Summary of Contents for AlarmSense CFP702-2

Page 1: ...LPCB APPROVED CFP 2 4 8 ZONE FIRE ALARM CONTROL PANEL CFP702 2 2 Zone CFP702 2 2 Zone CFP704 2 4 Zone CFP708 2 8 Zone installation maintenance manual Approved Document No DFU7002020 Rev 4...

Page 2: ...non latching zones delays test sounder status 16 17 Fault Diagnosis 18 Fault indications 18 Zone faults 19 Power supply faults 19 System faults 21 Repeater faults 22 Conventional sounder faults 22 Re...

Page 3: ...lause 7 11 A delay facility selectable on a zone by zone basis is provided to delay the alarm sounders remote fire and or auxiliary outputs Test condition Clause 10 0 A zone test facility is provided...

Page 4: ...this document A basic understanding of fire alarm system components and their use is assumed We strongly recommend that a suitably qualified and competent person is consulted in connection with the d...

Page 5: ...of any personal electro static charge by momentarily touching any sound connection to safety earth e g a radiator Always handle PCBs by their sides and avoid touching the legs of any components PCBs s...

Page 6: ...switched fused spur at 3 A or a 6 A Type B circuit breaker to IEC EN 60898 1 The Mains supply MUST be exclusive to the panel and be reliably earthed at the indicated earthing post Hint As an alternat...

Page 7: ...e programmed into the panel using the Sounder Status function see Page 17 for details Also there are limitations on the number of sounders which can be used please refer to page 8 for important advice...

Page 8: ...d supplying the panel s battery charging circuit and any output relays which may be fitted As a safe margin and to allow for these other loads the total sounder loading for the panel should not exceed...

Page 9: ...limiting fuse which trips if one or more of the loads are shorted This affects all loads and results in appropriate faults being reported at the panel The current consumed by this output must be consi...

Page 10: ...connected directly to this connector block and NOT to the base earth distribution post which is provided for making off zone circuit and conventional sounder circuit screens The Power Supply PCB s ea...

Page 11: ...HR R V V 0V 1A 250 R 1A R Incoming Mains Cable This cable MUST be segregated from other cables Good quality cable glands MUST always be fitted Battery Connector CONN2 Leads supplied in the panel s acc...

Page 12: ...lihood of incorrect connection Figure 10 Main Control PCB layout INSTALLATION MAINTENANCE MANUAL Approved Document No DFU7002020 Rev 4 Page 12 of 24 LPCB APPROVED CFP ALARMSENSE 2 4 8 ZONE FIRE ALARM...

Page 13: ...All screens should be adequately insulated and connected between the nut and washers on the base earth distribution post see right using suitable eyed crimp connectors Do not disturb the lower nut th...

Page 14: ...el only The programming of coincidence double knock Note This function is non compliant with EN54 2 The setting up zones for non latching operation Note This function is non compliant with EN54 2 The...

Page 15: ...alse alarm pressing the CONTROL PANEL RESET button at access level 2 during the delay period will return the system to normal Important note If link PLK1 is fitted on the Main Control PCB see right tr...

Page 16: ...non compliant with EN54 2 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the COINCIDENCE light flashes any pairs of zones that are already programmed for coincidence will have their Zone Fault...

Page 17: ...LEVEL THREE FUNCTIONS button To program zones into test 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the TEST light flashes any zones that are already programmed for test will have their Zon...

Page 18: ...correct this fault see page 19 section 1 1 Supply Present This light should be lit green at all times If off see power supply faults page 19 section 1 2 Power Supply Fault This light flashes yellow w...

Page 19: ...rs this confirms there is a wiring fault 2 Refit and double check the wiring and the end of line capacitor on the zone Trace the fault with consideration for the type of fault indicated see above Note...

Page 20: ...power supply fault will automatically be cleared Depending on battery size and the depth of discharge this may take several hours If the batteries are in poor condition they must be replaced If the b...

Page 21: ...d System Fault lights will be cycle continuously plus the panel s internal sounder will activate Suggested action Press the panel s RESET button and if still in access level 3 the ESCAPE ACCESS button...

Page 22: ...ulty and must be replaced 3 If a sounder circuit fault is detected correct the fault and reconnect the sounder circuit The sounder fault will automatically clear within 60 seconds Note If the sounder...

Page 23: ...pecification on page 24 for quiescent consumption of AlarmSense devices A The total alarm current of the sounders plus any other devices connected to other alarm outputs See Zone Circuit specification...

Page 24: ...ored for open and short circuit YES Reverse voltage DC monitoring Indicated by common fault Alarm voltage 27VDC maximum 20VDC minimum final battery voltage Sounder circuit fuses Each circuit protected...

Reviews: