Installing the Main Control PCB

The panel’s Main Control PCB provides all the 5mm connector blocks for the system’s zone circuits, conventional 
sounder circuits, auxiliary inputs and auxiliary outputs. It also provides the engineer with access to a wide range of 
engineering functions, details of which appear later in this manual.

Before any connections can be made, the Main Control PCB must first be securely positioned inside the fire alarm 
panel (see figure 10 below) using the five retaining screws. As the PCB is presented to the panel, remember to 
attach the telecoms-style connecting cable to SKT2 on the reverse of the Main Control PCB and to PL1 on the Power 
Supply PCB.

Important: SKT1 on the reverse of the Main Control PCB is for the connection of optional system expansion devices 
such as Network Driver Cards (for repeater panels) and Relay Output Boards. If any of these devices are to be used, 
refer to the individual installation instructions supplied with them as they will need to be fitted to the panel before 
the Main Control PCB.

Take care when reconnecting the 5mm connector blocks that you do so the correct way round. We recommend 
that you clearly label all system wiring to reduce the likelihood of incorrect connection.

Figure 10 : Main Control PCB layout

INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 12 of 24

LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL

SW4

SW3

SW8

SW1

SW2

CONN

2

SW7

SW6

SW5

     ACCESS

LEVEL THREE

  FUNCTIONS

  OPEN

CIRCUIT

DELAYS TEST

ACCESSED

TEST

 PSU

FAULT

Z2

Z3

GENERAL

 FAULT

DELAY MINUTES

0

1

2

3

CAUTION  - RISK OF EXPLOSION IF

INCORRECT TYPE OF BATTERIES FITTED.

DISPOSE OF USED BATTERIES ACCORDING

TO THE MANUFACTURERS INSTRUCTIONS.

4

NONLATCHING

5 6

7

 FAULT

OUTPUT

STATUS

SUPPLY

OK

REMOTE

 OUTPUT

   AUX

OUTPUT

STATUS

FOR OPERATIONAL DETAILS PLEASE

CONSULT THE MAINTENANCE MANUAL

Z4

COINCIDENCE

Z5

Z6

Z7

8

REPEATER

   FAULT

 SHORT

CIRCUIT

SILENCE

INTERNAL

SOUNDER

OUTPUTS

DELAYED

SOUNDER

 STATUS

REMOTE

OUTPUT

STATUS

  GENERAL

DISABLEMENT

GENERAL

FIRE

9

10

SYSTEM

  FAULT

NEXT OPTION

CODE ENTRY(3)

ENABLE/DISABLE

LAMP TEST

CODE ENTRY(4)

CODE ENTRY(1)

CODE ENTRY(2)

ESCAPE ACCESS

SILENCE/

RESOUND

SOUNDERS

RESET

FAULT

ZONE1

ZONE4

ZONE2

ZONE3

ZONE8

ZONE7

ZONE6

ZONE5

FIRE

VR1

+

+

+

+

+

+

+

4

C

S

3

C

S

2

C

S

8

Z

CC

S

T

U

P

N

I

T

I

U

C

R

I

C

  

  

  

  

  

 

R

E

D

N

U

O

S

OUTPUTS

AUX

AUX

24V

0V

ALT

REM

CONN

5

CONN6

CONN7

CONN8

CONN9

+

+

+

+

Z1

DETECTOR            CIRCUITS

REMOVING THIS CIRCUIT

BOARD EXPOSES HAZARDOUS

VOLTAGES -  PLEASE REFER TO

INSTALLATION INSTRUCTIONS

WARNING

SENSITIVE TO STATIC

ELECTRICITY -  OBSERVE

PRECAUTIONS BEFORE

HANDLING

I

O

ACCESS LEVEL 2

RST

FAULT

NO

NC

C

NO

NC

C

1

C

S

+

  

  

  

  

  

CONN10

Summary of Contents for AlarmSense CFP702-2

Page 1: ...LPCB APPROVED CFP 2 4 8 ZONE FIRE ALARM CONTROL PANEL CFP702 2 2 Zone CFP702 2 2 Zone CFP704 2 4 Zone CFP708 2 8 Zone installation maintenance manual Approved Document No DFU7002020 Rev 4...

Page 2: ...non latching zones delays test sounder status 16 17 Fault Diagnosis 18 Fault indications 18 Zone faults 19 Power supply faults 19 System faults 21 Repeater faults 22 Conventional sounder faults 22 Re...

Page 3: ...lause 7 11 A delay facility selectable on a zone by zone basis is provided to delay the alarm sounders remote fire and or auxiliary outputs Test condition Clause 10 0 A zone test facility is provided...

Page 4: ...this document A basic understanding of fire alarm system components and their use is assumed We strongly recommend that a suitably qualified and competent person is consulted in connection with the d...

Page 5: ...of any personal electro static charge by momentarily touching any sound connection to safety earth e g a radiator Always handle PCBs by their sides and avoid touching the legs of any components PCBs s...

Page 6: ...switched fused spur at 3 A or a 6 A Type B circuit breaker to IEC EN 60898 1 The Mains supply MUST be exclusive to the panel and be reliably earthed at the indicated earthing post Hint As an alternat...

Page 7: ...e programmed into the panel using the Sounder Status function see Page 17 for details Also there are limitations on the number of sounders which can be used please refer to page 8 for important advice...

Page 8: ...d supplying the panel s battery charging circuit and any output relays which may be fitted As a safe margin and to allow for these other loads the total sounder loading for the panel should not exceed...

Page 9: ...limiting fuse which trips if one or more of the loads are shorted This affects all loads and results in appropriate faults being reported at the panel The current consumed by this output must be consi...

Page 10: ...connected directly to this connector block and NOT to the base earth distribution post which is provided for making off zone circuit and conventional sounder circuit screens The Power Supply PCB s ea...

Page 11: ...HR R V V 0V 1A 250 R 1A R Incoming Mains Cable This cable MUST be segregated from other cables Good quality cable glands MUST always be fitted Battery Connector CONN2 Leads supplied in the panel s acc...

Page 12: ...lihood of incorrect connection Figure 10 Main Control PCB layout INSTALLATION MAINTENANCE MANUAL Approved Document No DFU7002020 Rev 4 Page 12 of 24 LPCB APPROVED CFP ALARMSENSE 2 4 8 ZONE FIRE ALARM...

Page 13: ...All screens should be adequately insulated and connected between the nut and washers on the base earth distribution post see right using suitable eyed crimp connectors Do not disturb the lower nut th...

Page 14: ...el only The programming of coincidence double knock Note This function is non compliant with EN54 2 The setting up zones for non latching operation Note This function is non compliant with EN54 2 The...

Page 15: ...alse alarm pressing the CONTROL PANEL RESET button at access level 2 during the delay period will return the system to normal Important note If link PLK1 is fitted on the Main Control PCB see right tr...

Page 16: ...non compliant with EN54 2 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the COINCIDENCE light flashes any pairs of zones that are already programmed for coincidence will have their Zone Fault...

Page 17: ...LEVEL THREE FUNCTIONS button To program zones into test 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the TEST light flashes any zones that are already programmed for test will have their Zon...

Page 18: ...correct this fault see page 19 section 1 1 Supply Present This light should be lit green at all times If off see power supply faults page 19 section 1 2 Power Supply Fault This light flashes yellow w...

Page 19: ...rs this confirms there is a wiring fault 2 Refit and double check the wiring and the end of line capacitor on the zone Trace the fault with consideration for the type of fault indicated see above Note...

Page 20: ...power supply fault will automatically be cleared Depending on battery size and the depth of discharge this may take several hours If the batteries are in poor condition they must be replaced If the b...

Page 21: ...d System Fault lights will be cycle continuously plus the panel s internal sounder will activate Suggested action Press the panel s RESET button and if still in access level 3 the ESCAPE ACCESS button...

Page 22: ...ulty and must be replaced 3 If a sounder circuit fault is detected correct the fault and reconnect the sounder circuit The sounder fault will automatically clear within 60 seconds Note If the sounder...

Page 23: ...pecification on page 24 for quiescent consumption of AlarmSense devices A The total alarm current of the sounders plus any other devices connected to other alarm outputs See Zone Circuit specification...

Page 24: ...ored for open and short circuit YES Reverse voltage DC monitoring Indicated by common fault Alarm voltage 27VDC maximum 20VDC minimum final battery voltage Sounder circuit fuses Each circuit protected...

Reviews: