Install the scene plate in a British standard flush box with a depth of at least 25mm.
Wire the plate using a CAT5 cable with the one end stripped and wired as per the diagram below.
If required wire the room divide terminals to a switch (see Room Divide section)
Connect the other end of the CAT 5 cable via an RJ45 plug into port 3 or port 4 of the nearest LCM.
Screw the assembly to the wall and clip on the cover plate.
Commission using the notes overleaf.
Installation and Wiring
The EBR-4SC provides advanced scene setting functions for the Rapid Lighting Control System. When
used in conjunction with Rapid dimming LCMs and suitable dimming luminaires, complex dimming can
be achieved to suit applications from conference rooms to individual offices. This product provides for
the selection of scenes and the programming of LCMs to provide set dimming levels. The EBR-4SC
provides the following features:
Up to 8 scenes selectable using 4 buttons, plus a separate off scene
Up/down override
Adjustable fade rates up to 99 minutes, individually selectable for each scene
Room divide
Support for up to 99 individual dimming circuits
IR support for scene selection and programming
Keypad scene programming
Description and Operation