ELECTRICAL FEATURES
Model
M.P.I. 80M
M.P.I. 100M
M.P.I. 160M
M.P.I. 190M
M.P.I. 190T
M.P.I. 240M
M.P.I. 240T
M.P.I. 320T
M.P.I. 380T
Power supply [V]
230 - mono
230 - mono
230 - mono
230 - mono
400 - tri
230 - mono
400 - tri
400 - tri
400 - tri
Nominal
absorption
[A]
13
13
19
28
13
29.5
13
19
21
Electrical
protection
[A]
16
16
25
32
16
40
16
32
32
Sezione del cavo
d’alimentazione
3 x 2.5 mm²
3 x 2.5 mm²
3 x 4 mm²
3 x 6 mm²
5 x 2.5 mm²
3 x 6 mm²
5 x 2,5 mm²
5 x 4 mm²
5 x 4 mm²
▪
The machine must be wired via the white connection box located next to the information plate.
▪
Remove the protective wrapping.
▪
Remove the 4 plastic screws from the cover of the connection box to release and remove the cover.
▪
Insert the power cable into the box, pushing it through the cable glands located at the bottom.
▪
Strip about 1 cm of each wire and connect them to the terminal, paying attention to respect the
phases, neutral and earth.
▪
Tighten the ferrule nuts to secure the cable and make sure the seal around the cable is well seated.
▪
Replace the cover and screws, then replace the cover.
Monophase
Black:Phase
Blu: Neutral
Yellow/Green: Grounding
Three-
phase
Black: Phase 1
Brown: Phase 2
Grey: Phase 3
Blu: Neutral
yellow/Green: Grounging