INSTALLATION INSTRUCTIONS
C-WP-E-TR Series
http://lighting.cree.com/warranty | 1-800-236-6800
CAUTION:
Changes or modifications not expressly approved could void
your authority to use this equipment.
This device complies with part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
CAN ICES-005 (A)/NMB-005 (A)
FCC NOTICE
Fixture is equipped with universal volt driver 120-277V
(ie. 120V, 208V, 240V or 277V)
PHASE TO NEUTRAL WIRING 120/277V
1. Connect supply ground to back box ground (green) leads.
2. Connect supply common to fixture neutral (white) lead.
3. Connect supply Vin to fixture hot (black) lead labeled
switched
Tuck all wires carefully into wiring chamber ensuring that no wires
are pinched.
PHASE TO PHASE WIRING 208/240V
1. Connect supply ground to back box ground (green) leads.
2. Connect supply L1 (Hot) to fixture neutral (white) lead.
3. Connect supply L2 (Hot) to fixture hot (black) lead labeled
switched.
Tuck all wires carefully into wiring chamber ensuring that no wires
are pinched.
DIMMING
NOTE:
If 0-10V dimming is to be used, switch setting for wattage must
be 100%
1. If 0-10V dimming is used, connect supply positive dimming
lead to violet positive fixture dimming lead.
Cap off violet dimming lead if dimming is not used.
2. If 0-10V dimming is used, connect supply negative dimming
lead to grey or pink negative fixture dimming lead. Cap off
grey or pink dimming lead if dimming is not used.
ELECTRICAL CONNECTIONS