INSTALLATION INSTRUCTIONS

C-WP-E-TR Series

http://lighting.cree.com/warranty      |     1-800-236-6800     

 

CAUTION:

 Changes or modifications not expressly approved could void 

your authority to use this equipment. 

This device complies with part 15 of the FCC Rules. Operation is subject 

to the following two conditions: (1) This device may not cause harmful 

interference, and (2) this device must accept any interference received, 

including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits 

for a Class A digital device, pursuant to part 15 of the FCC Rules. 

These limits are designed to provide reasonable protection against 

harmful interference when the equipment is operated in a commercial 

environment. This equipment generates, uses, and can radiate radio 

frequency energy and, if not installed and used in accordance with 

the instruction manual, may cause harmful interference to radio 

communications. Operation of this equipment in a residential area 

is likely to cause harmful interference in which case the user will be 

required to correct the interference at his own expense.

CAN ICES-005 (A)/NMB-005 (A)

FCC NOTICE

Fixture is equipped with universal volt driver 120-277V 

(ie. 120V, 208V, 240V or 277V)

PHASE TO NEUTRAL WIRING 120/277V

1.  Connect supply ground to back box ground (green) leads.

2.  Connect supply common to fixture neutral (white) lead.

3.  Connect supply Vin to fixture hot (black) lead labeled  

 

 switched

Tuck all wires carefully into wiring chamber ensuring that no wires 

are pinched.

PHASE TO PHASE WIRING 208/240V

1.  Connect supply ground to back box ground (green) leads.

2.  Connect supply L1 (Hot) to fixture neutral (white) lead.

3.  Connect supply L2 (Hot) to fixture hot (black) lead labeled    

 switched.

Tuck all wires carefully into wiring chamber ensuring that no wires 

are pinched.

DIMMING
NOTE:

 If 0-10V dimming is to be used, switch setting for wattage must 

be 100%

1.  If 0-10V dimming is used, connect supply positive dimming 

lead to violet positive fixture dimming lead.  

Cap off violet dimming lead if dimming is not used.

2.  If 0-10V dimming is used, connect supply negative dimming 

lead to grey or pink negative fixture dimming lead. Cap off 

grey or pink dimming lead if dimming is not used.

ELECTRICAL CONNECTIONS