TG69B
Section A: Description and Operation (cont)
A2-339 regulator used with these units also:
• offers optional J1939 communication. See figure 3.
•
provides overvoltage cutout (OVCO). Regulator will trip
OVCO when system voltage rises above 46 volts for lon-
ger than 3 seconds. OVCO feature detects high voltage
and reacts by opening alternator field circuit and turning
off alternator. Removing and reapplying energize signal
at IGN terminal will reset OVCO circuit.
•
limits output power to 10kW throughout RPM range. See
Figure 4 for output curves.
Figure 4 — 10kW Output Limiting Curve with A2-339 Regulator
Figure 3 — A2-339 Connector Identification
Alternator harness
connector
Optional J1939
connector