8.3
Fail to switch on the system
If the system is failed to switch on, battery module should be firstly tested, testing
methods are as followings:
Test the voltage of B+
if
<
24V, replace battery module
if
>
24v, battery module is normal
If battery module is normal, then check BMS-M.
114
Precharging failed
Replace BMS-P
Check inverter
communication
115
BIC balance failed
Replace BIC
116
PCB temperature sensor failed
Replace BMS-M
Replace BMS-P
117
Communication with BMU lost
Replace BMU
Replace BMS-M