To  make  sure  that  the  system  can  be  operated  normally,  please  use  BYD  compatible 
inverters  and  select  battery  quantity  correctly,  according  to 

the “B-Box configuration list 

with different inverter

” in Appendix 1 in this user manual.

 

8 Common Issues and Solutions 

8.1Alarm

 

indicated on the BMU and the solution 

LED of the BMU 

Possible cause 

Solution 

Flash 1 time 

Inverter and BMU communication 
failure 

step1. Check whether the CAN 
communication cable has been connected 

correctly and

 

tightly

 

step2. If the connection is incorrect, please 
reconnect the cable correctly; if the 
connection is correct and reliable, then 

replace the BMU

 

Flash 2 times 

Battery not found 

Check the connection between BMU and 
first battery. 

Flash 3 times 

Any of batteries are disconnected 

1. 

Check RS485 cable and battery 
address 

2. 

If the connection and the address are 
correct, please contact the after service 
provider 

Flash 4 times 

Any of battery failures 

Check battery led status. If the red led is on 
and buzzer alarms, please contact your 
after service provider to replace the battery. 

 

8.2 Alarm displayed on B-Plus 2.5 and the solution 

Alarm indicated by flashing LED

 

Info B-Plus displayed 

 

Flash 

Possible cause 

Solution 

Only yellow led is ON

 

0.5Hz 

Battery was powered off 
abnormally; 

Press ON/OFF button for 2-3 
seconds to restart the battery, If 
the battery cannot be 
recovered, contact the after 
service provider immediately; 

Flow led flashes and 
alternates with capacity led

 

10s per 
cycle 

Communication 
connection timeout 

Step1.Check the 
communication wire/cable 

Step2.check battery address 

NO.1/3 led and No.2/4 led 
flashing alternately 

 

Update statue status 

If the firmware is not updated, 
then reset the battery. 

Alarm indicted by flashing yellow Led

 

Summary of Contents for B-Box Res 10.0

Page 1: ...B Box Res 2 5 10 0 User Manual Rev 1 0 Feb 2018 Copyright BYD Lithium Battery Company Limited All rights reversed...

Page 2: ...1Alarm indicated on the BMU and the solution 10 8 2 Alarm displayed on B Plus 2 5 and the solution 10 8 3 Common issues displayed on inverter and the solution 12 9 Warranty 12 10 Registration 12 Appen...

Page 3: ...Sungrow 19 5 1 Minimum configuration with SH5K 19 Appendix 2 Common Issues Displayed on Inverter and Solutions 20 1 Alarm code displayed on the SRC of SMA sunny island and solution 20 2 Alarm displaye...

Page 4: ...to the product e g changes or modifications are only permitted with the express written permission of BYD Unauthorized alterations will void warranty claims BYD shall not be held liable for any damage...

Page 5: ...expose the battery to direct sunlight for extended periods of time Place battery in secure location away from children and animals Do not allow the battery power terminals to touch conductive objects...

Page 6: ...urrent adjustment 2 N Quantity of B Plus 2 5 battery Discharge current control under different temperatures Protect temp Resume temp Normal current A 10 50 0 7 1C N Remark 1 N Quantity of B Plus 2 5 b...

Page 7: ...P P 11 Cell voltage Single cell voltage 12 Failure Battery or BMS are broken need to be replaced 13 Alarm indicate that the battery is in abnormal status 14 Protect Battery stops charging or dischargi...

Page 8: ...s P N is U3A1 50P A 3 BMU BMU Battery management unit communicates with external equipment 5 3 General introduction of BMU BMU installed inside cabinet is battery management unit The function is to ma...

Page 9: ...running status ERR LED ERR ADDR Indicate error status ALM LED Alarm Indicate alarm status RJ45 terminal RS485 Communication ports Address ADDR Address needs to be set if they are connected in paralle...

Page 10: ...arly according to the following table with 0 5C 25A current for 1 hour after a long time of storage Recharge conditions when in storage Storage environment temperature Relative humidity of storage env...

Page 11: ...disconnected 1 Check RS485 cable and battery address 2 If the connection and the address are correct please contact the after service provider Flash 4 times Any of battery failures Check battery led s...

Page 12: ...it Contact the after service provider 7times Discharge over current protection Contact the after service provider 8times High temperature protection Contact the after service provider 9times Low tempe...

Page 13: ...n please refer to Appendix 2 in this user manual 8 4 Emergency Please cut off the power supply and turn off the battery in emergency 9 Warranty BYD provides warranty when the product is installed and...

Page 14: ...formation is required for timely customer service 2 Serial Number of Battery Box Cabinet 3 Serial Number of B Plus 4 Serial Number of BMS 5 Installation Date 6 Invoice Number If you have any questions...

Page 15: ...B Plus 2 5 Cabinet SI 3 0M 3 1 SI 4 4M 4 1 SI 6 0H 4 1 SI 8 0H 4 1 1 Phase off Grid2 Inverter Type B Plus 2 5 Cabinet SI 3 0M 3 1 SI 4 4M 3 1 SI 6 0H 5 2 SI 8 0H 5 2 3 Phase off Grid1 Inverter Type B...

Page 16: ...mum configuration with EM Inverter Firmware version minimum required firmware version for ARM is 03 B Box firmware version minimum required firmware version for BMU is V4 10 Shall bypass main circuit...

Page 17: ...3000 35 1 1 48 5000 70 1 1 3 Phase on Grid Inverter Type B Plus 2 5 Cabinet 48 3000 35 3 1 48 5000 70 3 1 1 Phase off Grid1 Inverter Type B Plus 2 5 Cabinet 48 3000 35 2 1 48 5000 70 3 1 3 Phase off G...

Page 18: ...00 110 100 100 1 1 48 10000 140 100 100 1 1 48 15000 200 100 100 1 1 3 Phase on Grid Inverter Type B Plus 2 5 Cabinet 48 5000 70 100 100 3 1 48 8000 110 100 100 4 1 48 10000 140 100 100 5 2 48 15000 2...

Page 19: ...Plus 2 5 Cabinet 48 3000 35 50 MPPT150 70 2 1 48 5000 70 100 MPPT150 100 3 1 3 Phase off Grid3 1 Inverter Type B Plus 2 5 Cabinet 48 3000 35 50 MPPT150 70 6 2 48 5000 70 100 MPPT150 100 9 3 Remark Max...

Page 20: ...1 Phase off Grid3 1 Inverter Type B Plus 2 5 Cabinet SH5K 2 1 Remark Maximum quantity of B Plus is 8 Cabinet quantity is 8 6 Minimum configuration with Selectronics 6 1 Minimum configuration with SP P...

Page 21: ...stem setting according to the guidelines F922 XA03DcLoVolt External Alarm Battery Low Voltage F923 XA04DcHiTmp External Alarm Battery High Temp F924 XA05DcLoTmp External Alarm Battery Low Temp F925 XA...

Page 22: ...ication fail Inverter and BMU communication failure 1 check whether the CAN communication cable has been connected correctly and tightly 2 Change BMU in cabinet 3 Alarm displayed on the screen of Sola...

Page 23: ...d Baolong Industrial Town Longgang Shenzhen 518116 China Local Contacts Australia Alps Power Pty Ltd Customer Service Mailbox service alpspower com au Telephone 61478 140 287 Address U201 15Chatham Ro...

Reviews: